20
The next items are shown and available for adjustment within the SETUP / ADJUST menu while MODE 2 is
selected:
Item
Range
Default
User
Settings
When is it Displayed
Description
Ind. Sensor
ON - OFF
OFF
PIM™ Identity is H
MODE = 2 or 3
Selects whether a DHW sensor is used
Ind. Setp.
Off, 50 to 180 °F
140°F
PIM™ Identity is H
MODE = 2 or 3
IND Sensor = ON
Target Indirect DHW Temperature. IND SENSOR
is Selected.
Ind. Diff
Off, 50 to 180°F
6°F
PIM™ Identity is H
MODE = 2 or 3
IND Sensor = ON
Differential for the target indirect DHW tank.
Ind. Supply
OFF, 70 to 200°F
180°F
PIM™ Identity is H
MODE = 2 or 3
IND Sensor = OFF
Target boiler temperature for the DHW heat
exchanger during indirect DHW operation
Ind Priori
OFF - ON
OFF
PIM™ Identity is H
MODE = 2
Selects whether or not indirect DHW priority is
active during indirect DHW operation
Pri Ovr
Au, 0:10 to 2:00 hr
Au
PIM™ Identity is H
DHW Priority = ON
Sets the length of the priority override time
The items below correspond to CWP operation. Ensure VERSA
®
DIP #3 is ON to enable CWP.
MIX TYPE
BOIL / PLNT
BOIL
H model & MIX DIP =
ON
MIX Type assumes that each individual unit will
have the proper wiring and pipe configuration to
control its own inlet temperature
MIX TARGET
50 TO 140°F
120°F
MIX DIP = ON
Inlet Target Temperature
MIX LOCK
ON / OFF
OFF
MIX DIP = ON
The equipment will trigger a warning when “MIX
Target” is not reached within 7 minutes. MIX
LOCK = ON Alarm and lockout, MIX LOCK =
OFF Alarm only
MIX TRIM
-5 TO 5
0
MIX DIP = ON
This adjustment is for various types and sizes of
units as well as various actuator motor speeds
and types supplied by Raypak
MIX SPEED
SLOW, MED,FAST
MED
MIX DIP = ON
This setting defines speed of response.
MIX INV
ON / OFF
OFF
MIX DIP = ON
This option is related to the use of spring-return
actuators with a proportional 2 or 3-way valve
When communication with BMS is required, user must enable Modbus port using the settings below by select-
ing other than “OFF” at Mode-Modbus scree. The following settings will become available.
Mode Modbus
Off, Monitor,
Temp, Rate
Off
Always
Modbus Operating Mode: Off, Monitor, Temp
Control, Rate Control
Address
1 to 247
1
Modbus Off
Modbus Slave Address
Data Type
RTU or ASCI
RTU
Modbus Off
Modbus Data Type
Baud Rate
2400, 9600,
19K2, 57K6,
115K
19K2
Modbus Off
Communication Speed of Network
Parity
None, Even, Odd
Even
Modbus Off
Error Detection of System. Integrator needs this
information
Table C: Mode 2 SETUP menu