BOILER View Menu
The “
BOILER 1
” icon is turned on. Boiler 1, 2, 3 or 4 are displayed for their respective boilers.
Table H: Boiler menu
Item
Display Range
User Settings
When is it Displayed
Description
BOILER 1
ON < > OFF
FT_Bus 1 is connected
Enables Boiler for operation
BOILER 2
ON < > OFF
FT_Bus 2 is connected
Enables Boiler for cascade operation
BOILER 3
ON < > OFF
FT_Bus 3 is connected
Enables Boiler for cascade operation
BOILER 4
ON < > OFF
FT_Bus 4 is connected
Enables Boiler for cascade operation
IGNITION
IDLE, PREP, IGN, BURN,
POST, HARD, SOFT
N/A
Always
IDLE=no CFH PREP=pre-purge or
inter-purge between trials for ignition
IGN=trial for ignition BURN=burner
operating POST=post purge HARD=a
hard lockout fault has occurred requir-
ing manual reset (Ignition Lockout or
manual high limit) and SOFT=a soft
lockout fault has occurred which inter-
rupts the heating cycle (any safety
other than ignition or manual high
limit). The CFH will resume after the
soft lockout fault has been corrected
and a 15 min. waiting period has
expired.
VENT WALL
---, 22 TO 266°F
N/A
Always, model dependent
Current Vent temperature
LIMIT TEMP
---, 22 TO 266°F
N/A
Always
Current Outlet -Limit temperature
EMS VDC
0.0 to 10.0
N/A
Always
Current EMS signal in Volts DC
FIRE RATE
0 – 100%
N/A
Always
PIM™ firing rate
SPEEDX 1000
0.0 to 20.00
N/A
PIM™ Identity Modulating
Blower speed in revolutions per minute
(rpm) x 1000
OUTLET MAX
20 TO 40°F
PIM™ identity H
Defines max outlet temperature offset
above target setpoint (press and hold
up and down arrows for 3 seconds to
enable adjustment).
OPERATOR
70 to 210°F
Always
Operator Potentiometer setting on
PIM™
DIFF
2 to 42°F
N/A
PIM™ Differential DIP set to
Auto
Current auto differential – Fixed by
PIM™
Pump post
OFF, 0:20 to 10:00 min.
PIM™ DIP = purge
Sets the length of the boiler pump
purge.
FLAME CUR
0 - 25
N/A
Always
Flame current in micro-amps (µA)
MASS
1 < > 2
Always
Thermal mass recovery
IDENTITY
H, WH, P
N/A
Always
Identifies the unit as boiler, water
heater or pool heater
IGN TYPE
1STG, 2STG, MOD
N/A
Always
PIM™ Board type
ID CARD
0 – 255
N/A
Always
Identifies Raypak Identity Card
SW ID
0 - 65535
N/A
Always
PIM™ Software identification number
ERROR CODE
0 -255
N/A
Always
LATEST ERROR CODE