53
MASTER
MASTER
FOLLOWER
FOLLOWER
0
0
8
8
6
6
R
R
1
1
4
4
2
2
240VAC/1PH
240VAC/1PH
SYSTEM PUMP
SYSTEM PUMP
TERMINAL BLOCK
TERMINAL BLOCK
L1
L1
DEDICATED
DEDICATED
240VAC POWER
240VAC POWER
A
A
B
B
240VAC COIL
240VAC COIL
PUMP
PUMP
RELAY
RELAY
240VAC/1PH
240VAC/1PH
USE COPPER CONDUCTORS ONLY
USE COPPER CONDUCTORS ONLY
IND DHW
IND DHW
SYSTEM
SYSTEM
BOILER
BOILER
PUMP DRY CONTACTS
PUMP DRY CONTACTS
L2
L2
GND
GND
L1
L1
240VAC/1PH
240VAC/1PH
USE COPPER CONDUCTORS ONLY
USE COPPER CONDUCTORS ONLY
IND DHW
IND DHW
SYSTEM
SYSTEM
BOILER
BOILER
PUMP DRY CONTACTS
PUMP DRY CONTACTS
L2
L2
GND
GND
TERMINAL BLOCK
TERMINAL BLOCK
Fig 38: Parallel Pump Wiring Diagram for MVB
®
/ XTherm
®
2503 - 4505
Parallel Pump Wiring Description
In the event of losing the Master unit, Follower units
are made capable of operating the System and IND
DHW pumps (as required) in “limp-along” mode (see
page 62). The System pump outputs from each cas-
cade member must be connected in parallel to activate
the system pump during “limp-along” operation. This
configuration will allow the system to continue to oper-
ate during Master unit failure or lose of the Master unit
WARNING:
Failure to properly install and/or wire
the System pump and IND DHW pump may result in
a system failure during limp-along mode as well as
damage to the equipment.
VERSA
®
board. The IND DHW pump (if applicable)
must be also connected in parallel from each individ-
ual cascade member output to ensure functionality
during “limp-along”.
The following wiring diagrams illustrate the proper par-
allel connections method to be used for the System
Pump. The same concept must be applied to the IND
DHW pump, when applicable.
Summary of Contents for 5000.72A
Page 2: ...2 Rev 2 is a software revision J1214G Aug 2014 completely new edition of this manual ...
Page 78: ...78 ...
Page 79: ...79 ...