Cast iron condensing boiler

 

Cast iron condensing boiler

 — Installation and operation manual

Read before beginning the installation

Codes and standards

Boiler compliances

Th e 

200i

 has been design certifi ed by CSA for use with natural 

and propane gas under the latest revision of ANSI-Z21.13/CSA 
4.9, Gas-Fired Low Pressure Steam and Hot Water Boilers and 
CAN1-3.1, Industrial and Commercial Gas Fired Packaged 
Boilers. Each unit has been constructed and hydrostatically 
tested for a maximum working pressure of 100 psi (700 kPa), in 
accordance with Section IV of the A.S.M.E. Boiler and Pressure 
Vessel Code.

Code compliances

All aspects of the boiler installation must conform to the re-
quirements of the authority having jurisdiction, or, in the absence 
of such requirements, to the National Fuel Gas Code, ANSI 
Z223.1/NFPA 54-latest revision. Where required by the au-
thority having jurisdiction, the installation must conform to 
the Standard for Controls and Safety Devices for Automatically 
Fired Boilers, ANSI/ASME CSD-1.

In Canada, the installation must be in accordance with the re-
quirements of CSA B149.1 or .2, Installation Code for Gas 
Burning Appliances and Equipment.

Commonwealth of Massachusetts

If installing a 

200i

 boiler in the Commonwealth of Massachu-

sett s, you MUST FOLLOW the additional instructions contained 
in Mestek’s instruction sheet, MA CODE.  If you don’t have a 
copy, call your Mestek dealer or Mestek.

When installed in the Commonwealth of Massachusett s, ensure 
the following:

Th

  e boiler must be installed by a licensed plumber or gas fi tt er.

When antifreeze is used in the system, install an approved 
pressure back-fl ow preventer.

Before placing the boiler . . .

Verify boiler rating and gas supply

Before installing the 

200i

 boiler, check the rating plate to 

ensure that the unit has been sized properly for the job.
Ensure that the boiler is set up for the type of gas available at 
the installation site. 

Verify location is suitable

Ensure the availability of an adequate electrical supply, un-
contaminated air for combustion, and that vent (and air) 
piping can be correctly installed.
Ensure the boiler can be connected to system water piping 
and gas supply.
Th e boiler must not be exposed to dripping or spraying wa-
ter or to rain.
If replacing an existing boiler, fi nd out what caused the boiler 
to fail before installing a new boiler. Correct the problems that 
led to failure, or the failure may happen to the new boiler.


  Do not install or operate the boiler, or leave an installation, without 

complying with all of the following, and with all information 
supplied in the boiler manuals.

Should overheating occur

Do not shut off  power to the circulators if the boiler should overheat or 
the gas supply fail to shut off . Instead, shut off  gas supply to the boiler with 
a manual valve in the gas supply line.

When servicing or operating the boiler

Disconnect electrical power when servicing the boiler to avoid potential 
for electrical shock.
Allow the boiler, components and water to cool before att empting to re-
move or handle boiler parts.
Do not add cold water to the boiler if it is hot. Allow the boiler to cool 
completely before introducing cold water.
Do not operate the boiler if any part has been under water.
Follow the guidelines in the Maintenance section for dealing with fi ber-
glass and ceramic fi ber materials.

You must have the following equipment

Electric multimeter 

 

•    Ammeter

Surface temperature gauge  

•    Metric Allen wrenches

Pressure diff erential gauge or included DP manometer
(3) Gas pressure meters:   Two @ 0 – 14 inches w.c.;    One @ 0 – 5 psi
Combustion analyzer — You must use a combustion analyzer and follow 
all instructions in this manual to correctly start-up the boiler. As prescribed 
in this manual, the O

2

 levels must be between 5% and 7%. Th roughout all 

fi ring rate conditions, the burner surface must never show red areas. Fol-
low manual procedures to correct this condition.

Boiler water

You must thoroughly fl ush the system, with the boiler isolated from the 
system, to remove sediment. Existing systems, in particular, oft en contain 
large amounts of iron sediment. Excess suspended solids in the water can 
lead to premature boiler failure.
High effi  ciency equipment requires suitable water for reliable operation. 
Follow the ASME recommendation for water treatment on hydronic ap-
plications that have dissolved solids greater than 200 parts per million. Fill 
water must be soft ened if the solids concentration is higher than this. See 
additional guidelines in this manual.
Do not allow the boiler to operate with frequent introduction of make-up 
water. Correct all problems causing leaks, relief valve weeping, or other 
factors that could cause fresh water to be added.
Do not use automotive anti-freeze in the boiler waterways.  If the use of 
antifreeze is necessary, an anti-freeze specifi cally formulated for hydronic 
heating systems must be used or damage to the boiler may occur, voiding 
the warranty.
On applications that use antifreeze or other low conductivity fl uid in the 
water, provide for increased water fl ow or ensure proper temperature rise.

Train the user

Before leaving, review the User’s Information Manual with the boiler 
user/homeowner, including the required maintenance to be performed 
by the user, the need for annual start-up/maintenance by a qualifi ed tech-
nician, the avoidance of combustion air blockage or contamination, and 
never bringing or storing fl ammable products into the boiler area.






1

Summary of Contents for 200i

Page 1: ...ated with a dust freeairsupply Followtheinstructionmanualprocedurestoductairtotheboilerairintake Iftheboilerhasbeencontaminatedbyoperation with contaminated air follow the instruction manual guideline...

Page 2: ...ication sensing Because of its low excess air operation and controlled combustion the burner also provides low NOX emissions and quiet operation Gas valve blower and venturi Most gas valves regulate a...

Page 3: ...mbly Pressure switches blocked flue and blocked air inlet Control connection board Electrical box power and control entrances Water return connection Air inlet sleeve Relief valve Relief valve piping...

Page 4: ...ore leaving the installation site after start or service fill out the Start up service history information on the back page Contents Customer service and technical support Please direct all questions...

Page 5: ...s Should overheating occur Do not shut off power to the circulators if the boiler should overheat or thegassupplyfailtoshutoff Instead shutoffgassupplytotheboilerwith a manual valve in the gas supply...

Page 6: ...ctrical requirements Voltage 120 vac 60 hz 1 phase Current draw 120 volt power line Amperes 2 75 Thermostat anticipator setting Amperes 0 5 Operating control Mestek SmartCycleTM control 4 Control oper...

Page 7: ...duct or other means of providing make up air if the intake air op tion isn t used Any building utilizing other gas burning ap pliances a fireplace wood stove or any type of exhaust fan must be checke...

Page 8: ...ftheboilerroom provides at least the minimum SERVICE OPERATION clearances given in Table 2 Failure to provide adequate ventilation could result in overheating of the boiler components or the room pote...

Page 9: ...dings as having all of the following Walls and ceilings exposed to the outside atmosphere have a continuous watervaporretarderwitharatingof1permorlesswithopeningsgasketed Weather stripping has been ad...

Page 10: ...losion causing possible severe personal injury death or substantial property damage Connecting the relief valve Connect inch NPT black iron pipe and fitting so the relief valve as shown in Figure 4 Fo...

Page 11: ...a section of the piping that will ensure enough flow to operate the switch Additional high limit controls For ASME CSD 1 or Canadian applications or when required by applicable codes install an additi...

Page 12: ...those that have air above the water in direct contact with the water See Figure 5 right side See Figure 7 for suggested piping Guidelines for closed type expansion tanks NEVER use automatic air vents...

Page 13: ...d 12 Extra high limit when required 13 Zone valve 14 Zone circulator 15 Differential pressure by pass valve Use when high head circulator may cause noise erosion or valve lifting problems when only a...

Page 14: ...tion of DHW tanks Makesuretoincorporateflow checkvalvesasshown Thesepreventforced flow in idle zones LEGEND 1 200i boiler 2 Boiler circulator 4 Boiler system circulator 5 Indirect fired DHW tank when...

Page 15: ...through the heating loop s This is important for summer time operation of DHW tanks Makesuretoincorporateflow checkvalvesasshown Thesepreventforced flow in idle zones LEGEND 1 200i boiler 2 Boiler ci...

Page 16: ...ation when required When heating system boilers are piped in parallel as in Figure 12 connect the DHW tank as a zone off of the main header or install boilers dedicated to the DHW application LEGEND 1...

Page 17: ...es If using variable speed control of the system circulator ensure that the flow never drops below the total minimum for all boil ers connected The boiler loop can be any of the designs in this manual...

Page 18: ...ock pressure test port Check the gas type The 200i comes from the factory ready to be piped to the gas supply If for any reason the boiler is not for the type of gas avail able at the installation sit...

Page 19: ...ipe sizing Required supply pressure at boiler Minimumgassupplypressure naturalgasorpropane bothfor flowing and static conditions 4 inches 102 mm water column Maximum gas supply pressure natural gas or...

Page 20: ...substantial property damage The electrical connections to this boiler must be made in accordance with all applicable local codes and the latest revision of the National Electrical Code ANSI NFPA 70 In...

Page 21: ...ith the boiler cannot be used for system circulation Itmustbeused assuppliedfromthefactory Itcirculateswateraftertheboiler stops firing to prevent potential damage from heat pocketing in the top of th...

Page 22: ...using 4 wire zone valves without a zone controller For other applications such as circulator relays or zone controllers see Appendix A in this manual Also see the Control manual Polarity The connectio...

Page 23: ...c Cast iron condensing boiler Cast iron condensing boiler Installation and operation manual Figure 21a 200i wiring summary see Boiler manual and Control manual text for additional information Wiring a...

Page 24: ...boiler Cast iron condensing boiler Installation and operation manual Figure 21b 200i wiring summary see Figure 21 for locations see Boiler manual and Control manual text for additional information Wir...

Page 25: ...ff switch ON The control will beep at least twice and the display will show the first STANDBY display in Figure 22 Note that pushing the DOWN button on the keypad will change the right side of the dis...

Page 26: ...xample The setpoint must never be higher than the OP LIMIT setting minus the LIMIT BAND minus half of the HEAT BAND setting This would cause the boiler to hit limit while trying to modulate Example If...

Page 27: ...e arrow keys until the cursor points at OA RESET The default setting is ON To change the setting press SELECT and use the arrow keys to change from ON to OFF Press SELECT then BACK If outdoor reset is...

Page 28: ...ndanyothergas burningappliance to their previous condition of use Any improper operation of the common venting system should be corrected so the installation conforms with the National Fuel Gas Code A...

Page 29: ...l a cover over the tubing or some other means to protect it from damage or movement Prevent freezing Do not route the line through or termi nate the line in any area that could expose the condensate t...

Page 30: ...atter Use cleaning chemicals sold for use in hydronic systems Replacementboilerinstallationsoftenhavelargeamountsofaccumulatedsediment and corrosion that must be removed to ensure boiler life and reli...

Page 31: ...tem water temperature reaches the maximum op erating temperature that the system and boiler temperature controls will allow The pressure in the boiler must never be below 12 psig Lower pressure could...

Page 32: ...smell Before start up and periodi cally afterwards have the propane supplier check verify the odorant level Never attempt to measure gas valve outlet pressure Donotattempttomeasuretheboilergasvalveou...

Page 33: ...sig 3 5 kPa Manual gas valve Open the main manual gas valve and check the gas piping and joints in the boiler Check for leaks if not already done following the instructions on page 18 Starting the boi...

Page 34: ...ow the bottom of the heat band 10 seconds PRE PURGE Ignition trial ON at ignition RPM 30 of maximum 4 seconds ON ON IGN 30 Flame is sensed Stabilization period ON at ignition RPM 30 of maximum 6 secon...

Page 35: ...4 5 Wait five minutes to clear out any gas Then smell for gas including near the floor If you smell gas Follow B in the safety information above If you don t smell gas go to the next step 6 Turn manu...

Page 36: ...36 P N 42 9470 11 07 Copyright 2007 Mestek Inc Cast iron condensing boiler Cast iron condensing boiler Installation and operation manual Illustration 26 En francaise Starting the boiler continued 12...

Page 37: ...p covering the flue gas sam pling hole Figure 27 The flue gas vent pipe may be hot Touching the pipe with unprotected skin could result in a severe burns 2 Slide the hose clamp off of the sample openi...

Page 38: ...he gas pressure at the manual gas valve Gas pressure should never fall off by more than 2 inches w c 50 mm To meter gas input natural gas only Meter gas input with the high fire jumper in place Turn o...

Page 39: ...erlysupported Remove the seven Phillips head screws securing the jacket top to the jacket sides Lift off the jacket top Leave the wire harnesses connected Move the insulation aside if necessary Adjust...

Page 40: ...ration with prepurge then continue through a normal start cycle With the manual gas valve closed the boiler should attempt ignition three times then lockout as described below Ignition failure Make su...

Page 41: ...er is damaged or blocked with debris consult the factory for corrective action Operating the boiler with a damaged or 13 obstructed heat exchanger could result in severe personal injury death or subst...

Page 42: ...afterwardstopre vent contamination of other clothing NIOSH First aid procedures Eye exposure irrigate immediately Breathing fresh air Read before proceeding Failure to adhere to the following could re...

Page 43: ...r 10 Replace the three thumbscrews and finger tighten securely 11 Turn the boiler on off switch ON Accessing the electrode assembly Turn the boiler on off switch OFF If the boiler ignition electrodes...

Page 44: ...of the assembly and a lock washer on top 8 Disconnect the three wire harnesses at the gas valve and blower items 2 and 3 Figure 36 In this illustration the wires are not shown 9 Lifttheuppercoverplate...

Page 45: ...45 P N 42 9470 11 07 Copyright 2007 Mestek Inc Cast iron condensing boiler Cast iron condensing boiler Installation and operation manual Maintenance continued 14 Notes...

Page 46: ...ABS UPPER COVER 1 24 59 1091 FILTER BOX ADAPTER GASKET 1 25 70 1237 FILTER BOX ADAPTER 1 26 57 2913 1 4 20 X 1 NYLOK SC HD CAP SCREW 4 27 54 3234 1 2 FLEX GAS LINE 1 ITEM PARTNo DESCRIPTION QTY 28 70...

Page 47: ...47 P N 42 9470 11 07 Copyright 2007 Mestek Inc Cast iron condensing boiler Cast iron condensing boiler Installation and operation manual Replacement parts continued 15...

Page 48: ...Connectingthewiresincorrectlycancausethe transformer to be shorted out and damaged 3 wirezonevalves Youwillhavetorewireexisting3 wirezonevalves tomeettherequirementsshowninFigure A1 Movethethermostat...

Page 49: ...replace with a circulator zoning controller or install relays that provide a 24VAC common terminal Heat Demand terminal connections using circulator relays The end switch leadsfromtherelaysmustconnect...

Page 50: ...s shown in Figure A3 The connections to the IAR negative terminals IAR must be from the zone controller s 24VAC common terminal as shown Connecting the wires incorrectly can cause the transformer to b...

Page 51: ...densing boiler Installation and operation manual Figure A3 Indoor Air Reset wiring to IAR terminals Heat Demand and DHW Demand using typical zone controller for either circulators or zone valves see F...

Page 52: ...alled correctly Air purged from water system Boiler operated through several cycles Air vents checked and opened as needed Limits and interlocks tested Water piping correct and operational Metered gas...

Reviews: