ray 200i Installation And Operation Instructions Manual Download Page 31

31

P/N 42-9470 11/07 Copyright 2007 Mestek, Inc.

Cast iron condensing boiler

 

Cast iron condensing boiler

 — Installation and operation manual

Fill and test the system 

(continued)

Antifreeze

Antifreeze for hydronic systems contains propylene glycol and an inhibitor. With-
out the inhibitor the glycol is actually corrosive. So the system water must be 
checked at least annually to ensure that the inhibitor is at the correct level .

Never

 use galvanized piping in a system that contains antifreeze. Never use chromate 

water treatment. Either of these will react with the inhibitor in the antifreeze mix.

Antifreeze concentration

 — If not using a pre-mixed antifreeze solution, de-

termine the amount of antifreeze to add based on the total volume of the system 
piping, the boiler and the expansion tank. Follow the antifreeze manufacturer’s 
instructions for the ratio of glycol required for the lowest expected exposure tem-
perature. NEVER use a glycol mix greater than 50%.

Prevent leaks

 — Glycol will escape more easily than water through any leak in 

the system. So the glycol concentration will reduce if a leak is allowed to continue. 
Eliminate all leaks in the system and have the owner frequently inspect the visible 
portions of the system for leaks periodically. Do not use circulators or valves with 
packing glands, the packing glands can weep.

Install a water meter

 — Because the system must be installed with automatic 

water make-up to ensure pressure will always be at least 12 psig, you should install 
a water meter with one half-gallon resolution on the make-up water line. Th is will 
allow monitoring to see if excessive make-up water is entering the system.

Circulator sizing

 — Glycol/water mixtures do not move heat as well as water 

only. Th e circulator size must be increased to account for this. As a rule of thumb, 
increase the fl ow rate by 15%. Assume a 10% reduction in pressure drop compared 
to water only at a give fl ow rate.

Constant circulation

 — For areas of the system that will be exposed to low tem-

peratures, use continuous circulation to keep the water moving in the pipes.

Expansion tank sizing

 — Increase the expansion tank size about 20% to account 

for the eff ects of the antifreeze.

Indirect heat exchangers

 — Output from indirect heat exchangers (including 

indirect water heaters) can drop substantially when using antifreeze/water. Make 
sure the exchanger is sized correctly for the application.

System pressure

Once the system is cleaned, fi lled, purged and treated as 
required, set the make-up water pressure reducing valve 
to the  correct cold-fi ll pressure. Th is is usually 12 psig for 
systems using 30 psig relief valves. For higher pressure sys-
tems, set the cold-fi ll pressure such that the system pressure 
will never exceed about 80% of the boiler relief valve sett ing 
when system water temperature reaches the maximum op-
erating temperature that the system and boiler temperature 
controls will allow.

  Th e pressure in the boiler must never be below 

12 psig. Lower pressure could allow localized 
boiling in the boiler heat exchanger, causing 
possible damage and section failure.

At cold fi ll, the water level in closed-type expansion tanks 
should not be above center. Use the tank fi tt ing to verify 
tank water level is correct.

As the system heats up, the water will expand, causing the 
system pressure to increase. If the expansion tank is properly 
sized and installed, the system pressure will never exceed 
about 80% of the relief valve set pressure (24 psig for typical 
residential systems).

If the system operating pressure becomes too high, check the 
expansion tank to ensure it is large enough. For closed-type 
expansion tanks, make sure there are no leaks in the piping 
or the tank and the tank fi tt ing is correctly installed. For dia-
phragm or bladder-type tanks, you may have to remove the 
tank from the system and verify that it can hold pressure. If it 
cannot hold pressure, the membrane may be damaged.

  If the system pressure is allowed to rise too high, 

the boiler relief valve will open, allowing water to 
escape from the system. Th e resultant addition of 
make-up water will cause mineral deposits and 
oxygen corrosion in the boiler.

Final checks

Aft er the system is cleaned, fi lled and purged, and the system 
pressure is correctly set, make sure the water chemistry is 
correct. Th e pH and chemistry must be as required (and 
specifi ed by the chemical treatment specialist when required).

Make sure all valves are correctly set. Isolation and fi ll valves 
should be open before start-up. Purge valves must be closed.

Open the valve on each automatic vent in the system about 
one quarter turn to allow venting.

Th oroughly inspect the system for leaks or weeping valves.

  Eliminate all system leaks to prevent excessive 

make-up water, which introduces oxygen as well 
as lime-forming minerals. Th is can lead to heat 
exchanger damage, resulting in possible severe 
personal injury, death or substantial property 
damage.

Watch the boiler pressure/temperature gauge throughout 
the start-up process. Make sure the pressure never drops 
below 12 psig and never goes higher than 80% of the boiler 
relief valve sett ing pressure.

 

Use only antifreeze sold for use in hydronic systems

 

— Never use automotive antifreeze.  Automotive antifreeze 
and ethylene glycol are toxic to humans and animals and will 
damage rubber components in the system.

 

Make sure the owner is aware that the antifreeze must be 
checked periodically by a qualifi ed technician to ensure 
the concentration is correct and that the inhibitor level is 
adequate.

 

Obtain the MSDS for the antifreeze and leave a copy with 
the owner. Follow antifreeze manufacturer’s guidelines for 
application and maintenance.

 

Failure to follow these guidelines could result in system or 
boiler failure, causing possible severe personal injury, death or 
substantial property damage.

11

Summary of Contents for 200i

Page 1: ...ated with a dust freeairsupply Followtheinstructionmanualprocedurestoductairtotheboilerairintake Iftheboilerhasbeencontaminatedbyoperation with contaminated air follow the instruction manual guideline...

Page 2: ...ication sensing Because of its low excess air operation and controlled combustion the burner also provides low NOX emissions and quiet operation Gas valve blower and venturi Most gas valves regulate a...

Page 3: ...mbly Pressure switches blocked flue and blocked air inlet Control connection board Electrical box power and control entrances Water return connection Air inlet sleeve Relief valve Relief valve piping...

Page 4: ...ore leaving the installation site after start or service fill out the Start up service history information on the back page Contents Customer service and technical support Please direct all questions...

Page 5: ...s Should overheating occur Do not shut off power to the circulators if the boiler should overheat or thegassupplyfailtoshutoff Instead shutoffgassupplytotheboilerwith a manual valve in the gas supply...

Page 6: ...ctrical requirements Voltage 120 vac 60 hz 1 phase Current draw 120 volt power line Amperes 2 75 Thermostat anticipator setting Amperes 0 5 Operating control Mestek SmartCycleTM control 4 Control oper...

Page 7: ...duct or other means of providing make up air if the intake air op tion isn t used Any building utilizing other gas burning ap pliances a fireplace wood stove or any type of exhaust fan must be checke...

Page 8: ...ftheboilerroom provides at least the minimum SERVICE OPERATION clearances given in Table 2 Failure to provide adequate ventilation could result in overheating of the boiler components or the room pote...

Page 9: ...dings as having all of the following Walls and ceilings exposed to the outside atmosphere have a continuous watervaporretarderwitharatingof1permorlesswithopeningsgasketed Weather stripping has been ad...

Page 10: ...losion causing possible severe personal injury death or substantial property damage Connecting the relief valve Connect inch NPT black iron pipe and fitting so the relief valve as shown in Figure 4 Fo...

Page 11: ...a section of the piping that will ensure enough flow to operate the switch Additional high limit controls For ASME CSD 1 or Canadian applications or when required by applicable codes install an additi...

Page 12: ...those that have air above the water in direct contact with the water See Figure 5 right side See Figure 7 for suggested piping Guidelines for closed type expansion tanks NEVER use automatic air vents...

Page 13: ...d 12 Extra high limit when required 13 Zone valve 14 Zone circulator 15 Differential pressure by pass valve Use when high head circulator may cause noise erosion or valve lifting problems when only a...

Page 14: ...tion of DHW tanks Makesuretoincorporateflow checkvalvesasshown Thesepreventforced flow in idle zones LEGEND 1 200i boiler 2 Boiler circulator 4 Boiler system circulator 5 Indirect fired DHW tank when...

Page 15: ...through the heating loop s This is important for summer time operation of DHW tanks Makesuretoincorporateflow checkvalvesasshown Thesepreventforced flow in idle zones LEGEND 1 200i boiler 2 Boiler ci...

Page 16: ...ation when required When heating system boilers are piped in parallel as in Figure 12 connect the DHW tank as a zone off of the main header or install boilers dedicated to the DHW application LEGEND 1...

Page 17: ...es If using variable speed control of the system circulator ensure that the flow never drops below the total minimum for all boil ers connected The boiler loop can be any of the designs in this manual...

Page 18: ...ock pressure test port Check the gas type The 200i comes from the factory ready to be piped to the gas supply If for any reason the boiler is not for the type of gas avail able at the installation sit...

Page 19: ...ipe sizing Required supply pressure at boiler Minimumgassupplypressure naturalgasorpropane bothfor flowing and static conditions 4 inches 102 mm water column Maximum gas supply pressure natural gas or...

Page 20: ...substantial property damage The electrical connections to this boiler must be made in accordance with all applicable local codes and the latest revision of the National Electrical Code ANSI NFPA 70 In...

Page 21: ...ith the boiler cannot be used for system circulation Itmustbeused assuppliedfromthefactory Itcirculateswateraftertheboiler stops firing to prevent potential damage from heat pocketing in the top of th...

Page 22: ...using 4 wire zone valves without a zone controller For other applications such as circulator relays or zone controllers see Appendix A in this manual Also see the Control manual Polarity The connectio...

Page 23: ...c Cast iron condensing boiler Cast iron condensing boiler Installation and operation manual Figure 21a 200i wiring summary see Boiler manual and Control manual text for additional information Wiring a...

Page 24: ...boiler Cast iron condensing boiler Installation and operation manual Figure 21b 200i wiring summary see Figure 21 for locations see Boiler manual and Control manual text for additional information Wir...

Page 25: ...ff switch ON The control will beep at least twice and the display will show the first STANDBY display in Figure 22 Note that pushing the DOWN button on the keypad will change the right side of the dis...

Page 26: ...xample The setpoint must never be higher than the OP LIMIT setting minus the LIMIT BAND minus half of the HEAT BAND setting This would cause the boiler to hit limit while trying to modulate Example If...

Page 27: ...e arrow keys until the cursor points at OA RESET The default setting is ON To change the setting press SELECT and use the arrow keys to change from ON to OFF Press SELECT then BACK If outdoor reset is...

Page 28: ...ndanyothergas burningappliance to their previous condition of use Any improper operation of the common venting system should be corrected so the installation conforms with the National Fuel Gas Code A...

Page 29: ...l a cover over the tubing or some other means to protect it from damage or movement Prevent freezing Do not route the line through or termi nate the line in any area that could expose the condensate t...

Page 30: ...atter Use cleaning chemicals sold for use in hydronic systems Replacementboilerinstallationsoftenhavelargeamountsofaccumulatedsediment and corrosion that must be removed to ensure boiler life and reli...

Page 31: ...tem water temperature reaches the maximum op erating temperature that the system and boiler temperature controls will allow The pressure in the boiler must never be below 12 psig Lower pressure could...

Page 32: ...smell Before start up and periodi cally afterwards have the propane supplier check verify the odorant level Never attempt to measure gas valve outlet pressure Donotattempttomeasuretheboilergasvalveou...

Page 33: ...sig 3 5 kPa Manual gas valve Open the main manual gas valve and check the gas piping and joints in the boiler Check for leaks if not already done following the instructions on page 18 Starting the boi...

Page 34: ...ow the bottom of the heat band 10 seconds PRE PURGE Ignition trial ON at ignition RPM 30 of maximum 4 seconds ON ON IGN 30 Flame is sensed Stabilization period ON at ignition RPM 30 of maximum 6 secon...

Page 35: ...4 5 Wait five minutes to clear out any gas Then smell for gas including near the floor If you smell gas Follow B in the safety information above If you don t smell gas go to the next step 6 Turn manu...

Page 36: ...36 P N 42 9470 11 07 Copyright 2007 Mestek Inc Cast iron condensing boiler Cast iron condensing boiler Installation and operation manual Illustration 26 En francaise Starting the boiler continued 12...

Page 37: ...p covering the flue gas sam pling hole Figure 27 The flue gas vent pipe may be hot Touching the pipe with unprotected skin could result in a severe burns 2 Slide the hose clamp off of the sample openi...

Page 38: ...he gas pressure at the manual gas valve Gas pressure should never fall off by more than 2 inches w c 50 mm To meter gas input natural gas only Meter gas input with the high fire jumper in place Turn o...

Page 39: ...erlysupported Remove the seven Phillips head screws securing the jacket top to the jacket sides Lift off the jacket top Leave the wire harnesses connected Move the insulation aside if necessary Adjust...

Page 40: ...ration with prepurge then continue through a normal start cycle With the manual gas valve closed the boiler should attempt ignition three times then lockout as described below Ignition failure Make su...

Page 41: ...er is damaged or blocked with debris consult the factory for corrective action Operating the boiler with a damaged or 13 obstructed heat exchanger could result in severe personal injury death or subst...

Page 42: ...afterwardstopre vent contamination of other clothing NIOSH First aid procedures Eye exposure irrigate immediately Breathing fresh air Read before proceeding Failure to adhere to the following could re...

Page 43: ...r 10 Replace the three thumbscrews and finger tighten securely 11 Turn the boiler on off switch ON Accessing the electrode assembly Turn the boiler on off switch OFF If the boiler ignition electrodes...

Page 44: ...of the assembly and a lock washer on top 8 Disconnect the three wire harnesses at the gas valve and blower items 2 and 3 Figure 36 In this illustration the wires are not shown 9 Lifttheuppercoverplate...

Page 45: ...45 P N 42 9470 11 07 Copyright 2007 Mestek Inc Cast iron condensing boiler Cast iron condensing boiler Installation and operation manual Maintenance continued 14 Notes...

Page 46: ...ABS UPPER COVER 1 24 59 1091 FILTER BOX ADAPTER GASKET 1 25 70 1237 FILTER BOX ADAPTER 1 26 57 2913 1 4 20 X 1 NYLOK SC HD CAP SCREW 4 27 54 3234 1 2 FLEX GAS LINE 1 ITEM PARTNo DESCRIPTION QTY 28 70...

Page 47: ...47 P N 42 9470 11 07 Copyright 2007 Mestek Inc Cast iron condensing boiler Cast iron condensing boiler Installation and operation manual Replacement parts continued 15...

Page 48: ...Connectingthewiresincorrectlycancausethe transformer to be shorted out and damaged 3 wirezonevalves Youwillhavetorewireexisting3 wirezonevalves tomeettherequirementsshowninFigure A1 Movethethermostat...

Page 49: ...replace with a circulator zoning controller or install relays that provide a 24VAC common terminal Heat Demand terminal connections using circulator relays The end switch leadsfromtherelaysmustconnect...

Page 50: ...s shown in Figure A3 The connections to the IAR negative terminals IAR must be from the zone controller s 24VAC common terminal as shown Connecting the wires incorrectly can cause the transformer to b...

Page 51: ...densing boiler Installation and operation manual Figure A3 Indoor Air Reset wiring to IAR terminals Heat Demand and DHW Demand using typical zone controller for either circulators or zone valves see F...

Page 52: ...alled correctly Air purged from water system Boiler operated through several cycles Air vents checked and opened as needed Limits and interlocks tested Water piping correct and operational Metered gas...

Reviews: