Floor protection
The floor protection plate must lie under the stove and extend 16” (41cm) in front of
the stove in USA and 18” (46cm) in Canada. The floor protection plate must extend
0” to the back of the stove in USA and 8” (20cm) in Canada. The floor protection plate
must extend 8” to the sides of the stove. For installations with horizontal rear con-
nector, the floor protection plate must extend under and 2” (50.8mm) to either side
of the connector.
The floor protection plate when used WITH the base, must be listed to UL 1618, and
is not required to have thermal protection (R=0).
Make sure that the floor and the sub-floor of the room in which the stove is installed
is designed to carry the extra weight of the stove. The floor protector plate must be
made of a non-combustible material.
When deciding where to install your stove, the heat distribution to other rooms
should be taken into consideration. Put the stove at a safe distance from combus-
tible materials; see the references at the name tag of the stove.
Thermal Floor Protection
Stove placed on combustible material must have thermal protection with an R =
0 or greater under the appliance and extending 16” in front of unit in US and 18” in
Canada.
Size of floor protector
USA
width = 43,4”
Debth = 36,15”
CANADA
width = 43,4”
Debth = 44,15”