D9000/D7000 Series Operation & Installation Manual
Page 11
74-07692-000-C 4/97
Installation
Before You Begin
This
Installation section contains a general
installation procedure. It refers you to other
sections of the manual for detailed instructions.
Radionics recommends you review this manual
and the
D9000/D7000 Series Program Entry
Guide
(74-07695-000) before you begin the installation
to determine the hardware and wiring
requirements for the features you want to use.
Have the following additional documents handy
as you read through this manual:
•
D9412/D9112 Program Record Sheet (74-
07697-000) or
D7412/D7212 Program
Record Sheet (34583)
•
D9000/D7000 Series Approved Applications
Compliance Guide (74-07693-000)
•
User’s Guide (74-06141-000) and User’s
Guide Supplement (33267)
•
D1255 Command Center Installation
Manual (74-06118-000) or D720 Command
Center Installation Manual (74-06935-000)
Before you begin the installation of the D9412/
D9112 you should be familiar with the operation
of the D5200 programmer or the Remote Account
Manager (RAM III).
Enclosure Options
Mount the Control/Communicator assembly in
any of the Radionics enclosures listed below.
Refer to the
D9000/D7000 Approved
Applications Compliance Guide (74-07693-000)
to determine if your application requires a
specific enclosure.
•
D8103 Universal Enclosure (tan)
•
D8109 Fire Enclosure (red)
•
D8108A Attack Resistant Enclosure (tan)
Beginning the Installation
Mounting the Enclosure
Mount the enclosure in the desired location. Be
certain to use all five mounting holes. See Figure
2.
Premises Wiring
Run the necessary wiring throughout the
premises and pull the wires into the enclosure.
EMI (Electro Magnetic Interference) may cause
problems: EMI may occur if you install the
system or run system wires near the following:
•
Computer network system
•
Electrical lines, fluorescent fixtures or
telephone cabling
•
Ham radio transmitter site
•
Heavy machinery and motors
•
High voltage electrical equipment or
transformers
•
PBX telephone system
•
Public service (police, fire departments, etc.)
using radio communications
•
Radio station transmitter site, or other
broadcast station equipment
•
Welding shop
If you think that EMI may be a problem, use
shielded cable. The drain wire for the shielded
cable must have continuity from terminal 10 on
the panel to the end of the wire run. If continuity is
not maintained, the shielded cable may
aggravate potential noise problems rather than
eliminate them.
Connecting the drain wire to ground at other than
terminal 10 may also produce problems. If you
cut the drain wire to install devices be certain to
splice it together. Solder and tape all splices.
P O I N T C H A R T L A B E L
M O U N T IN G
S K IR T H O O K
M O D U LE M O U N T IN G
L O C AT I O N S
M O D U L E
M O U N T IN G
LO C AT IO N S
TA M P E R S W IT C H
M O U N T IN G LO C AT I O N
M O U N T IN G
S K IR T H O O K
S K IR T M O U N T IN G H O LE
B A C K O F D 941 2
M O U N T IN G
S K IR T H O O K
O P E N IN G S
LO C K D O W N T A B
Figure 2: Enclosure Mounting