
Instruction book
94
2920 7101 22
• (1): Single supply cables.
• (2): Parallel supply cables
• (3) is only valid for Y-D versions
Cable sizing according IEC
The tables below indicate the current carrying capacities of cables for 3 commonly used installation
methods, calculated according to standard 60364-5-52 - electrical installations of buildings part 5 -
selection and erection equipment and section 52 - current carrying capacities in wiring systems.
The allowed currents are valid for PVC insulated cables with three loaded copper conductors (see tables for
maximum conductor temperature 70 °C and 90°C).
Installation method B2 according table B.52.1.
Multi-core cable in conduit on a wooden wall
Maximum allowed current in function of the ambient temperature for installation method B2
Ambient temperature
Cable section
30 °C
40 °C
45 °C
50 °C
55 °C
4 mm²
< 27 A
< 23 A
< 21 A
< 19 A
< 16 A
6 mm²
< 34 A
< 30 A
< 27 A
< 24 A
< 21 A
10 mm²
< 46 A
< 40 A
< 36 A
< 33 A
< 28 A
16 mm²
< 62 A
< 54 A
< 49 A
< 44 A
< 38 A
25 mm²
< 80 A
< 70 A
< 63 A
< 57 A
< 49 A
35 mm²
< 99 A
< 86 A
< 78 A
< 70 A
< 60 A
50 mm²
< 118 A
< 103 A
< 93 A
< 84 A
< 72 A
70 mm²
< 149 A
< 130 A
< 118 A
< 106 A
< 91 A
95 mm²
< 179 A
< 156 A
< 141 A
< 127 A
< 109 A
120 mm²
< 206 A
< 179 A
< 163 A
< 146 A
< 126 A
Summary of Contents for QGS 40
Page 2: ......
Page 131: ......
Page 132: ...Performance You Demand Reliability You Trust www quincycompressor com COMPRESSOR...