Instruction book
2920 7101 22
109
Parameters
Units
55kW
75kW
90kW
110kW
Recoverable
energy
kW 48.4 66 79.2 80.4
Water flow
l/Min
69.3
94
113.4
114
Temperature at
inlet
°C 50 50 50 50
Temperature at
outlet
°C 60 60 60 60
Pressure
drop
bar 0.21 0.46 0.53 0.55
Data for high temperature rise/low water flow systems
Typical values
parameters
units
30kW
37kW
45kW
Recoverable energy kW
18.67
23.02
28
Water flow
l/Min
2.28
2.79
3.4
Temperature at inlet °C
20
20
20
Temperature at
outlet
°C 92 92 92
Pressure drop
bar
0.001
0.001
0.001
parameters
units
55kW
75kW
90kW
110kW
Recoverable
energy
kW 48.4 50.2 79.2 79.7
Water
flow
l/Min 9.8 10.3 16.0 16.5
Temperature at
inlet
°C 20 20 20 20
Temperature at
outlet
°C 91 91 91 91
Pressure
drop
bar 0.005 0.009 0.013 0.014
10.2 ECO6i
10.2.1 General description
Introduction
ECO6i
All graphic controllers can be used to control a number of other compressors. They can automatically start,
load, unload and stop the connected compressors in order to regulate the air net pressure within
programmable limits.
ECO 6i can be used to control up to 6 compressors.
This integrated central controller function (ECOi) can be activated when a software license is provided.