7-38
Field–Replaceable Units (FRUs)
511010 Rev. 07-01-19
7.17
Library Calibration Procedure
The RLS has been designed to detect when it needs to be calibrated and will place a
message on the control panel at that time. Normal library operation will not continue
until the calibration process has been completed.
Figure 7-36 Calibration Needed Message on Bottom of Home Page Screen
1.
To perform the calibration procedure the Private page must be accessed and it is
a privileged, password-protected page. This means that a password must be set
to gain access to the items in the Private page.
2.
The libraries Security Identity passwords are entered on the Configura-
tion/Library/Identification and Security screen. See Figure 7-37. To enter a
password press the Edit button, which will bring up a screen that allows data to
be entered as shown in Figure 7-38.
Figure 7-37 Configuration/Library/Identification and Security Screen