background image

Appendix F – On-Board LED Functionalities and CPU MMI Modes 

 

 

200

www.qualitrolcorp.com

Appendix F 

On-Board LED Functionalities 

and CPU MMI Modes 

Summary of Contents for INFORMA PMD-A

Page 1: ...User Manual www qualitrolcorp com INFORMA PMD A Data Acquisition Unit Document ID 40 08557 01...

Page 2: ...ed without the express prior written permission of Qualitrol QUALITROL endeavors to ensure the accuracy and quality of its published materials however no warranty expressed or implied is provided QUAL...

Page 3: ...Certificate www qualitrolcorp com Note Please contact Qualitrol for detailed test report for Class A certification...

Page 4: ...3U Device 16 3 5 2 Rear Panel of the INFORMA PMD A 6U Device 17 3 6 Standard MMI 18 3 6 1 MMI CPU Mode 18 3 6 2 MMI LCD Navigation 18 3 6 3 MMI Overview Screen 20 3 6 4 CPU Overview Screen 21 3 6 5 CP...

Page 5: ...onfiguration 90 6 2 1 Configuration Overview 94 6 2 2 Communications 95 6 2 3 PQ Overview 98 6 2 4 PQ Configuration 99 6 2 5 Continuous Recording 99 6 2 6 EN 50160 reports standard threshold and user...

Page 6: ...ons DSI 157 Rapid Voltage Change RVC 158 Power Quality Sensors 160 PQ Sensor Functionality 160 PQ Sensor Types 161 Handling Time Changes 163 Forward Time Shift 163 Backward Time Shift 163 PQ Calculate...

Page 7: ...Contents Contents iv www qualitrolcorp com References 240...

Page 8: ...About This Manual 1 www qualitrolcorp com Chapter 1 About This Manual...

Page 9: ...evice Operate the device Maintain and troubleshoot the device 1 1 Symbols Used The following table lists the symbols used on the device and in the manual Symbol Description A Warning identifies condit...

Page 10: ...MC Electro Magnetic Compatibility FPGA Field Programmable Gate Array FR Fault Recording GPS Global Positioning System HIA AFE High Impedance Anti aliasing Analog Front End iQ Master Station Software L...

Page 11: ...storting installations to MV HV and EHV power systems IEC 61000 3 7 Electromagnetic compatibility EMC Part 3 7 Limits Assessment of emission limits while connecting fluctuating installations to MV HV...

Page 12: ...Overview 5 www qualitrolcorp com Chapter 2 Overview...

Page 13: ...INFORMA PMD A License The INFORMA PMD A device is a licensed product Consequently some features of this multifunctional device may not be available as described in this manual Additional licenses may...

Page 14: ...he authorized service personnel if any damage or defect is found 2 3 Customer Helpline Information For any customer or technical support contact Qualitrol Corporation Instrumentation Division 15 Wildf...

Page 15: ...Components and Specifications 8 www qualitrolcorp com Chapter 3 Components and Specifications...

Page 16: ...y 0 to 95 RH non condensing Note Conforms to RoHS and WEEE Cold start is not possible below 0 C 3 2 Power Supply and Earthing This section provides the power requirements for the device 3 2 1 Standard...

Page 17: ...earth An ON OFF switch is provided on the rear panel to control the power to the device 3 2 2 UPS The UPS card provides power supply to the INFORMA PMD A device for a minimum of 15 minutes In normal o...

Page 18: ...C to 45 C 80 RH Discharging 20 C 60 C Maximum 90 RH 10 C to 50 C 80 RH Storage Environment Short Period less than 1 month 20 C 45 C Maximum 90 RH Long Period more than 3 months 10 C 30 C Maximum 90 R...

Page 19: ...0087 Note Refer to Section 7 2 5 for further information about UPS maintenance 3 2 3 12 VDC External Power Supply TB2 provides an auxiliary DC output for external devices Figure 3 2 External Power Sup...

Page 20: ...mm wide 132 5 mm high 362 2 mm deep 15 kg without battery 15 5 kg with battery 15 kg without battery Includes packaging and accessories if any 15 5 kg with battery Includes packaging and accessories i...

Page 21: ...ices The following table lists the labels for the front panel of the INFORMA PMD A 3U and INFORMA PMD A 6U devices Label Name Description 1 LED Indicators Status is configured to indicate different al...

Page 22: ...Components and Specifications 15 www qualitrolcorp com A picture of the front panel of the INFORMA PMD A 6U device is shown below Figure 3 4 INFORMA PMD A 6U Front View...

Page 23: ...connector 2 DC Power Socket TB2 DC power output connector 12 V 750 mA 3 Phoenix Connector TB3 Alarm output 4 2 4 Pin connector TB4 TB5 NA 5 2 10 Pin connector TB6 TB7 NA 6 Phoenix Connector TB8 Differ...

Page 24: ...er output connector 12 V 750 mA 3 Phoenix Connector TB3 Alarm output 4 4 4 Pin connector TB4 TB5 NA 5 4 10 Pin connector TB6 TB7 NA 6 Phoenix Connector T B8 Differential PPS Out Master mode In Slave m...

Page 25: ...MA PMD A 3U device Refer to Appendix F for MMI CPU modes 3 6 2 MMI LCD Navigation The LCD display format is 240X80 dots A keypad is provided to navigate between the screens The front panel keypad cons...

Page 26: ...DFR Log TR Log Log FR CSS PQ Continuous PQ Othres RMS Env FL TR Clock synch Status Digital Inputs Analog Inputs FL Lines FR Manual trigger FL Manual trigger TR Manual trigger Ethernet 2 MMI Overview C...

Page 27: ...ress the left arrow key and for details about CPU 2 the user must press the right arrow key Figure 3 9 MMI Overview Screen The following screen is displayed if there is only one CPU For the purpose of...

Page 28: ...has been unlocked since the device was switched on Indicates that the device is running with an internal UPS Indicates that the Power Health status is bad Indicates that an alarm condition has occurre...

Page 29: ...options Pressing Enter on each option displays its details Figure 3 12 CPU Main Menu Screen System information This menu provides information about the following Figure 3 13 System Information Firmwar...

Page 30: ...splays the last five reboot conditions Time Sync Status Log Displays the status log for time synchronization Event Status Log Displays information about the FR and PQ trigger events DTF Results Displa...

Page 31: ...com Communication This menu provides the communication status It displays the serial communication and Ethernet communication status This menu displays the following options Figure 3 16 Communication...

Page 32: ...ay the submenus to download the log DFR record CSS record PQ Continuous record PQ reports RMS record and FL TR record respectively USB should be connected to the device in order to download logs and r...

Page 33: ...the Time mode of CPU Source of clock status of synchronization and additional information based on source Figure 3 18 Clock Synchronization Manual Trigger This menu provides options for the user to g...

Page 34: ...log channel status The analog channel is selected using the up and down arrow keys Digital Inputs Displays the channel state of all 64 digital channels FL Lines Displays the FL channel status Relay Te...

Page 35: ...from bottom to top in green Once the firmware is upgraded successfully only the Health LEDs flash in green and the others are in an OFF state If a communication failure occurs during the upgrade all...

Page 36: ...power and device is not fitted with UPS card Battery backup is not available in the device Green DFR TR FL trigger in progress Red Nil LED 5 Trigger To check DFR TR triggering status Off No trigger Gr...

Page 37: ...configured event Channel Check Mode in 1 CPU Mode Without LCD When the Enter key in the MMI keypad is pressed or when the shutdown switch refer to Section 3 7 1 for shutdown information is pressed fo...

Page 38: ...6 indication provided in the table in Section 3 6 6 For standalone the Phase error indication is not applicable The Digital inputs screen displays the state of the 64 digital channels The user has to...

Page 39: ...to section 7 4 4 3 8 Communication Ports 3 8 1 PPH PPM IRIG B In IRIG B Out Figure 3 23 INFORMA PMD A PPH PPM Note A default 75 IRIG B termination is provided by the INFORMA PMD A device If a 120 term...

Page 40: ...is used for longer range communication over fiber optic cables The white connector is used to transmit and the grey connector is used to receive The connectors are suitable for 62 5 125 micron multi m...

Page 41: ...TP FTP is used to transfer files between INFORMA PMD A and the user s computer over the network IP Forwarding IP Forwarding allows network requests to be redirected to a specified IP address that migh...

Page 42: ...RS232 2 PPPD on MODEM Standard modem cable DTE DCE Protocols Simple null modem without handshaking IRIG J Simple null modem without handshaking PPPD on SERIAL Null modem with loop back handshaking RS...

Page 43: ...dshaking Figure 3 26 Standard Modem Cable 3 9 USB 3 9 1 USB Functionality When a user plugs in a USB storage device to INFORMA PMD A the device checks for a specific folder and validates the unique se...

Page 44: ...SB performs operations according to the script because the script has higher priority Both the script file and the LCD interface are not available The USB does not perform any operation The script fil...

Page 45: ...nchronization all INFORMA PMD A devices can be synchronized to the same time and synchronously sampled to the GPS internal RTC IRIG B or IRIG J 3 10 1 INFORMA PMD A as Master Using an External GPS PPS...

Page 46: ...quent Abrupt Time Shifts External PPH signal is validated only if it is within 5 minutes of an hour boundary as determined by RTC time If the PPH signal is received beyond this 5 minute time window it...

Page 47: ...nnection for PPS synchronization Using IRIG J INFORMA PMD A can be configured to use an external IRIG J time source as the time reference Connect the serial cable from the IRIG J time source to the RS...

Page 48: ...MA PMD A is not synchronized with the PPS time marker the accuracy of time synchronization is impacted 3 10 3 INFORMA PMD A Time Accuracy Figure 3 30 INFORMA PMD A Time Accuracy 3 10 4 PPS Detection S...

Page 49: ...any of the following conditions occurs The external PPS does not pass the stability check The time difference is not within the acceptable jitter limit When there is a transition of INFORMA PMD A int...

Page 50: ...f 2 5 M at 63 V 2 M at 110 V 1 M at 230 V and 0 1 M at 440 V 3 11 2 HIA AFE HIA AFE analog channels have the following characteristics 24 bit resolution for voltage current Phase angle between channel...

Page 51: ...ng a CT circuit Fast Transient Recording optional The fast transient recording card is optional and need to fit in the factory The signals taken from the HIA AFE channel are processed in order to dete...

Page 52: ...ve 35 V Activation The scanning rate of digital inputs is 2 kHz The minimum pulse width of the digital inputs that can be detected and recorded is greater than 0 5 ms The debounce time of digital inpu...

Page 53: ...ut connections are done through terminal blocks that plug into TB10 for an INFORMA PMD A 3U device and TB10 and TB12 for an INFORMA PMD A 6U device Terminals 1 8 are digital inputs Terminal 9 is commo...

Page 54: ...and 4 are configurable iQ does not support Figure 3 32 INFORMA PMD A Alarm Outputs Relay Specifications Contact Form SPST NO SPST NC Coli Voltage 5 VDC Contact Rating 5 A at 250 VDC 30 VAC 8 A at 250...

Page 55: ...record threshold crossed Histogram 10 Min threshold crossed Histogram Free Interval threshold crossed Busbar1 EN 50160 Standard threshold Report memory threshold crossed Busbar1 EN 50160 User threshol...

Page 56: ...ng Busbar1 EN 50160 Standard threshold Report memory threshold recording Busbar1 EN 50160 User threshold Report memory threshold recording Busbar1 IEC 61000 3 6 7 report memory threshold recording Bus...

Page 57: ...Components and Specifications 50 www qualitrolcorp com The relay default settings are done at the factory as per the customer order Note Wire gauge to be used for Alarm outputs 14 26 AWG...

Page 58: ...Installation 51 www qualitrolcorp com Chapter 4 Installation...

Page 59: ...ify contents from package 4 2 Accessories Following accessories are provided Serial port cable RJ45 cable 2 m straight RJ45 cable 2 m crossover Operating manual Configuration CD containing the standal...

Page 60: ...53 www qualitrolcorp com 4 3 INFORMA PMD A Installation Specifications The following figure shows a single INFORMA PMD A communication to a computer through Ethernet or Modem 1 Figure 4 1 Standalone I...

Page 61: ...and 4 are configured as time slaves Note The twisted pair Ethernet communications are also known as 10 100 Base T and have a maximum range of 100 m 300 ft under normal conditions for error free commun...

Page 62: ...m electric shock Make sure that the device is installed in an area where heat dissipation is not restricted Ensure that the device is in the operating temperature range and humidity conditions as spec...

Page 63: ...p of INFORMA PMD A the LEDs on the right flash from top to bottom and the LEDs on the left flash from bottom to top in green This is in addition to the normal boot up mode 4 5 3 Checking for Correct O...

Page 64: ...Serial Connection to Informa PMD A 57 www qualitrolcorp com Chapter 5 Serial Connection to INFORMA PMD A...

Page 65: ...D A device is connected directly to a PC without a modem The type of cable need to be used for this service is Null Modem with loop back handshaking Steps to establish a PPPD connection over Serial 1...

Page 66: ...corp com Figure 5 2 Network Connection Type 4 Select the radio button Set up an advanced connection and click on Next button Figure 5 3 Advanced Connection Options 5 Select the radio button Connect di...

Page 67: ...on to Informa PMD A 60 www qualitrolcorp com Figure 5 4 Host or Guest Page 6 Select the radio button Guest and then click on Next button Figure 5 5 Connection Name 7 Mention any name say LnT and click...

Page 68: ...PMD A 61 www qualitrolcorp com Figure 5 6 Select a Device 8 Select Communications Port COM x and then click on Next button Figure 5 7 Connection Availability 9 Select the radio button Anyone s use an...

Page 69: ...the New Connection 10 Check on Add a shortcut to this connection to my desktop and then click on Finish button A shortcut icon for serial connectivity is created on the desktop of the PC 11 Now double...

Page 70: ...ction to Informa PMD A 63 www qualitrolcorp com 12 Click on Properties then the below wizard appears Figure 5 10 LnT Properties 13 Click on Configure then the below wizard appears Figure 5 11 Modem Co...

Page 71: ...400 The default baud rate of serial port on INFORMA PMD A device is set to 38400 15 User has to de select the Enable hardware flow control 16 Click on OK then the below wizard appears Figure 5 11 Mode...

Page 72: ...he status of connection 1 Go to Start Control Panel Network and Internet Connections Network Connections Figure 5 13 Status General 2 Double Click on Direct LnT to know the status of connection 3 A po...

Page 73: ...2 in the above mentioned example screen to access the INFORMA PMD A device via PPPD serial link PPPD ON MODEM User can enable use this service when the INFORMA PMD A device need to be accessed via mo...

Page 74: ...PMD A 67 www qualitrolcorp com In the PC go to Start Control Panel Printers and Other Hardware Phone and Modem Options Figure 5 15 Phone and Modem Options Under the tab Modems user can observe the ins...

Page 75: ...Conexant ACF External PnP Modem Steps to establish a PPPD connection over Modem Once the Pre requisites are met user has to follow the below steps for establishing the PPPD connection over Modem 1 In...

Page 76: ...nnection to Informa PMD A 69 www qualitrolcorp com The following wizard will appear for creating the new connection Figure 5 17 New Connection Wizard 3 Click on Next button Figure 5 18 Network Connect...

Page 77: ...ww qualitrolcorp com 4 Select the radio button Connect to the network at my workplace and click on Next button Figure 5 19 Network Connection 5 Select the radio button Dial up connection and click on...

Page 78: ...it is LnT and click on Next button The below wizard appears Figure 5 21 Phone Number to Dial 7 User has to enter the phone number which user wishes to dial under Phone Number and click on Next button...

Page 79: ...ilability 9 User can select either Anyone s use My use and then click Next button Figure 5 23 Completing the New Connection Wizard 10 Click on Finish by selecting the option Add a Shortcut to this con...

Page 80: ...able to see a connection formed with LnT in this example short cut in the desktop as well as in the Network connections in control panel Figure 5 24 Network Connections 11 Now double click on LnT shor...

Page 81: ...to Informa PMD A 74 www qualitrolcorp com 12 For setting the Baud rate user has to click on Properties A window appears as shown below Figure 5 26 Lnt Properties 13 Click on Configure Figure 5 27 Mod...

Page 82: ...8400 15 Ensure that all Hardware Features are enabled 16 Click on OK The below mentioned wizard appears Figure 5 28 Connect LnT Note If user wishes to change the number then edit in the click on Dial...

Page 83: ...A 76 www qualitrolcorp com Figure 5 29 Verifying and Completing Registration 19 This implies the connection is formed To check the status of connection 1 Go to Start Control Panel Network and Internet...

Page 84: ...igure 5 30 LnT Status 2 Double Click on Direct LnT to know the status of connection 3 A popup screen LnT Status will be displayed 4 In the General tab the status should be connected 5 Click on Details...

Page 85: ...and meant only for the PPPD on modem link Client IP address It is the new temporary IP address assigned to PC and meant only for the PPPD on modem link The Server IP address Client IP address is user...

Page 86: ...Configuration 79 www qualitrolcorp com Chapter 6 Configuration...

Page 87: ...ORMA PMD A supports the following cabling configuration 6 1 1 Connection Diagrams Single Phase Network Single phase 2 conductor network connections are shown in Figure 5 1 The connections to the chann...

Page 88: ...the systemic phase shift of 30 between phase to phase voltage and associated current the individual phase power values are calculated values and might deviate considerably from the actual values The...

Page 89: ...re network 3U3I Three Wattmeter method connections are shown below The connections to the channels must be made as per the labels on the analog channel port shown in Section 3 5 Figure 6 3 3 Wire Netw...

Page 90: ...k 4U4I 4 wire network 4U4I connections are shown below The connections to the channels must be made as per the labels on the analog channel port shown in Section 3 5 Figure 6 4 4 Wire Network 4U4I Not...

Page 91: ...N conductor voltages can be determined in two star connected three phase systems Two 4 wire network 2M4U connections are shown below The connections to the channels must be made as per the labels on...

Page 92: ...ase to phase voltages in two delta configured three phase systems Two 3 wire network 2M3U connections are shown below The connections to the channels must be made as per the labels on the analog chann...

Page 93: ...U Star configuration connections are shown below The connections to the channels must be made as per the labels on the analog channel port shown in Section 3 5 Figure 6 7 3U Configuration Note Refer t...

Page 94: ...U Star configuration connections are shown below The connections to the channels must be made as per the labels on the analog channel port shown in Section 3 5 Figure 6 8 4U Configuration Note Refer t...

Page 95: ...6I Star configuration connections are shown below The connections to the channels must be made as per the labels on the analog channel port shown in Section 3 5 Figure 6 9 3U6I Configuration Note Refe...

Page 96: ...3I Star configuration connections are shown below The connections to the channels must be made as per the labels on the analog channel port shown in Section 3 5 Figure 6 10 6U3I Configuration Note Ref...

Page 97: ...Configuration 90 www qualitrolcorp com 6 2 Software Configuration To establish the communication using iQ the following steps must be performed 1 Start iQ Figure 6 11 Starting iQ...

Page 98: ...Configuration 91 www qualitrolcorp com 2 To create a new device right click All Devices as shown below Figure 6 12 Creating a New Device...

Page 99: ...Configuration 92 www qualitrolcorp com 3 Select INFORMA PMD A from the device list Figure 6 13 Selecting INFORMA PMD A Device...

Page 100: ...ormation Figure 6 14 Creating a Device 5 A new device is created 6 Right click the INFORMA PMD A device and select Retrieve Configuration The previously configured settings are loaded Factory default...

Page 101: ...me through navigation across all subfields of the overview tree structure as described in the following sections 2 After modifying the configuration the user can save it in the database or save and se...

Page 102: ...RS232 2 must be configured for the internal or external modem the user needs to select the Modem Type RS232 2 is the configuration editor for INFORMA PMD A device in iQ If the user selects the Modem T...

Page 103: ...Configuration 96 www qualitrolcorp com Figure 6 17 RS232 2 Note Internal modem is optional For more information about configuration refer to iQ Help...

Page 104: ...Configuration 97 www qualitrolcorp com Figure 6 18 RS232 3 Note For more information about configuration refer to iQ Help...

Page 105: ...Configuration 98 www qualitrolcorp com 6 2 3 PQ Overview Figure 6 19 PQ Overview Flow Chart Note Each record and report can be enabled or disabled...

Page 106: ...be logged according to the configured window 6 2 5 Continuous Recording Ten Minute Recordings Standard PQ measurement according to IEC 61000 4 30 Class A Minimum Maximum and Average values are calcul...

Page 107: ...terval as 200 ms 200 ms data is considered and the record will contain only the average value 200 ms data is aggregated for aggregation intervals of 1 second and 2 seconds 3 seconds data is aggregated...

Page 108: ...Configuration 101 www qualitrolcorp com Figure 6 22 PQ Free Interval Continuous Recording...

Page 109: ...ounts across a reporting period of one week Parameter limits are defined in the standard Figure 6 23 EN 50160 Standard Report Standard Limits Busbar 1 EN 50160 Report with User Defined Limits For Busb...

Page 110: ...Configuration 103 www qualitrolcorp com Figure 6 24 EN 50160 User Report User defined Limits Busbar 1 6 2 7 IEC 61000 3 6 7 Report Figure 6 25 IEC 61000 3 6 7 Report...

Page 111: ...The number of bins for each histogram is common for all the parameters selected Configurable data types 10 minute MMA data 10 minute flicker and 10 minute frequency Output Histogram data of all parame...

Page 112: ...er fraction of the report duration for proper data points The user can configure the number of bins and their sizes The user can also select the minimum maximum or average values of the parameter for...

Page 113: ...t the values of Pre trigger time Voltage Dead band and Current Dead band as required Dead band is a non sensitive band that is used to avoid the recording of multiple half cycle data with minor variat...

Page 114: ...option to set the default values of Dip Swell and Interruptions as per the IEC 61000 4 30 standard Alarm1 and Alarm2 configurations are applicable for UA Under UA Over and UA Both sensor types Figure...

Page 115: ...tude of change between the two steady state averages and is used for voltage magnitude change and voltage gradient checking Time window Defines the time at which the rate of change of voltage is calcu...

Page 116: ...qualitrolcorp com Power Quality PQ Sensor Channels Figure 6 31 PQ Sensor Channels Note For details about PQ Sensor Channels refer to PQ Sensor Types in Appendix B For more information about configura...

Page 117: ...er can specify the following settings Pre fault time between 10 ms and 10000 ms Sample rate as 32 64 128 256 or 512 samples per cycle Post fault time between 10 ms and 10000 ms Operational limit betwe...

Page 118: ...t the FR parameter sensor type threshold limits nominal value and other specifications for each sensor channel as required Figure 6 33 FR Sensor Channels Note For details about FR Sensor refer to DFR...

Page 119: ...user has an option of configuring in linear or circular mode Recording is stopped if configured in the linear mode and the memory limit has been reached If configured in the circular mode the oldest f...

Page 120: ...Maintenance 113 www qualitrolcorp com Chapter 7 Maintenance...

Page 121: ...full scale Current source error 0 02 of full scale The following steps must be performed for calibration 1 Open a Web browser and enter the following URL http Board_ip_address mfgindex Board IP is th...

Page 122: ...voltage channels in the following manner Channels 1 4 and 7 are current channels with tap settings 10 A and Channels 2 3 and 5 are voltage channels with tap settings 140 V In this situation perform th...

Page 123: ...Maintenance 116 www qualitrolcorp com 4 Select the group that needs to be calibrated and then click Continue The device performs offset calibration Figure 7 3 Offset Calibration...

Page 124: ...llows the user to short the input channels under calibration After shorting all the channels displayed click Continue to proceed further When calibrating with Relay Test Set apply Zero current voltage...

Page 125: ...sensors are disabled and the data recording is paused Figure 7 5 Calibration in Progress 7 After the offset calibration is done the system prompts the user for confirmation to perform a low gain calib...

Page 126: ...Maintenance 119 www qualitrolcorp com Figure 7 7 Voltage Calibration...

Page 127: ...he device to perform low gain calibration The utility sends the command to the device after a 10 second delay For normal TX AFE current calibration the device performs a high gain calibration The same...

Page 128: ...e calibration is done properly the user has to form a DFR and check whether the values are proper with respect to the applied values to the device If the user changes the frequency of the device in th...

Page 129: ...eep the original packaging intact It might be required at a later stage for transport Store the device in a dry room maintain a temperature range of 30 C to 70 C and a maximum humidity of 95 Keep the...

Page 130: ...osure to the battery fluids direct contact with skin and eyes are to be considered serious and must be treated immediately In the event of a contact with the battery fluids rinse with large volumes of...

Page 131: ...this folder 6 Save the pic_bank1 bin file in this folder If the kernel has to be changed then save the ulmage_x y_with_crc file in this folder 7 Communication between the computer and the device can...

Page 132: ...p 192 168 1 11 tabindex html when the communication is through RJ45 or to http 10 38 0 2 tabindex html when the communication is through a modem Default user and password mfgindex tabindex Username qu...

Page 133: ...tus of used memory can be seen on the Diagnostic Information page on http device_ip mfgindex html Once it becomes 1 we shall proceed with next step 10 Open a Web browser and enter the following URL ht...

Page 134: ...CPU_Application DSP FPGA FPGA_HI_A PICFirmWare MMIFirmware All of the above The PMD A Upgrade page also allows the user to upgrade the CPU Kernel Note The CPU Kernel should only be sent along with the...

Page 135: ...rading CPU Kernel click on CPU Kernel browse button to locate the ulmage_x y_with_crc file and then click on Send button On receiving the confirmation that the file is sent successfully click the Togg...

Page 136: ...ile Upload to INFORMA PMD A During the upload process a progress bar is displayed that signifies that communications and re programming are in progress Note For the purpose of this manual the URL show...

Page 137: ...com 7 3 3 During CPU File Upload to INFORMA PMD A During the upload process a progress bar is displayed that signifies that communications and re programming are in progress similar to other file uplo...

Page 138: ...or_string SUCCESS is displayed Figure 7 16 File upgrade status 7 3 4 System and Diagnostic Information After the INFORMA PMD A device has restarted and the Healthy LED is on open a Web page and enter...

Page 139: ...ayed Figure 7 17 System Information Ensure that the newly installed firmware versions displayed in the page are correct Consult Qualitrol for the latest versions Note The Firmware versions shown in th...

Page 140: ...lcorp com Click the Diagnostic Information tab and the following page is displayed Ensure that the DSP FPGA and PIC are programmed successfully and Power Health PIC and CPU are working Figure 7 18 Dia...

Page 141: ...om 7 4 Troubleshooting No part of the equipment is serviceable by the user Always follow the safety instructions and safety precautions mentioned in SAFETY SUMMARY Before attempting to troubleshoot a...

Page 142: ...not working Motherboard not working Refer to Section 6 4 1 for initial inspection and rectification No Communication Only COMMS LED is OFF and all other LEDs on the front panel are working Communicat...

Page 143: ...r is correctly available on the rear panel Resolve Power Connection Issue Reboot the system by pressing the RESET switch that is present on the Mother Board Refer section 6 4 4 Contact Qualitrol Suppo...

Page 144: ...Maintenance 137 www qualitrolcorp com 7 4 2 Communication LED is Off To find the cause for the communication failure follow the steps mentioned below Figure 7 21 Communication Failure...

Page 145: ...ation cable in slave mode is connected properly Make proper connection Yes If problem persists contact Qualitrol for further help Check the voltages at the respective test points on the motherboard Re...

Page 146: ...Maintenance 139 www qualitrolcorp com Figure 7 23 Location of Reset and Shutdown Switches and Supply Voltage Test Points on the Motherboard Shutdown switch Reset switch 5V DGND 12V 12V...

Page 147: ...Appendix A Technical Specifications 140 www qualitrolcorp com Appendix A Technical Specifications...

Page 148: ...EDs Healthy Communication clock sync battery trigger alarm and sensors status Quality System Developed designed and manufactured according to DN ISO 9001 2000 Calibration Solid state design no user ad...

Page 149: ...resolution for voltage Input Option 2 HIA AFE Impedance 4M 24 bit resolution for voltage current channels Accuracy 0 1 Analog Inputs Voltage AC Optional for HIA AFE Fast Transient Recording The trans...

Page 150: ...tes system Healthy Relay 2 3 are user configurable for PQ parameters Relay 4 is user configurable for either temperature under over temperature threshold Resistive load 250 VAC 5 A 110 VDC 0 5 A 48 VD...

Page 151: ...bus IEC 60870 5 IEC 61850 GSM GPRS Standard Compliance IEC 61000 4 30 Class A IEC 61000 4 7 harmonics and inter harmonics IEC 61000 4 15 flicker CBEMA ITIC IEEE 1159 IEEE 519 Temperature Operating 5 C...

Page 152: ...quasi peak and 60 dB V average at 0 50 MHz to 5 MHz 73 dB V quasi peak and 60 dB V average at 0 50 MHz to 5 MHz Tested on Complete Device Passed the Emission levels are within the Specified limits of...

Page 153: ...Hz 5 MHz 1890 MHz 10 MHz keyed at frequency 200 Hz 1 50 duty cycle 2 5 ms ON 2 5 ms OFF Tested on Complete Device Passed with Criteria A IEC 60255 5 Clause 6 Dielectric test ANSI IEEE C37 90 1989 SWC...

Page 154: ...55 6 Supply voltage limit test Tested for PSU Tested for DC range 80VDC to 132VDC IEC 60068 2 1 EN60068 2 1 Cold tests Tested for Cold Storage 45 C 49 F for 96 hours Cold Operating 5 C 23 F for 16 hou...

Page 155: ...input Supply Voltage Dips and Swells N A N A 0 2 of Udin Voltage interruptions N A N A 0 2 of Udin Voltage Unbalance 1 5 0 100 If unbalance is in the range 1 to 5 0 15 Harmonics up to 50th order 10 t...

Page 156: ...Appendix B INFORMA PMD A Functions 149 www qualitrolcorp com Appendix B INFORMA PMD A Functions...

Page 157: ...second Magnitude of supply voltage Flicker Voltage unbalance Harmonics Inter harmonics Mains signaling 3 second Over deviation and under deviation Non Steady State Phenomena In these phenomena INFORM...

Page 158: ...quency Record Note Applied Frequency 50 Hz Measured Frequency 50 Hz Magnitude of Supply Voltage The RMS value of the voltage at a given time at the supply terminals measured over a given interval The...

Page 159: ...ow cyclical variation of the amplitude of the RMS voltage envelope It is the impression of unsteadiness of visual sensation induced by a light stimulus whose luminance or spectral distribution fluctua...

Page 160: ...alance is a condition in which the RMS values of the phase voltages or the phase angles between consecutive phases are not equal The level of unbalance is typically monitored from 10 minute average in...

Page 161: ...a multiple of the fundamental frequency The power quality recording function in the INFORMA PMD A provides a comprehensive harmonic recording function comply with IEC 61000 4 7 The user can select up...

Page 162: ...ate the voltage harmonic of fundamental values on all the three phases Inter Harmonics Harmonics that have frequencies equal to non integer multiples of the fundamental are inter harmonics The inter h...

Page 163: ...oltage RMS because of the delay in the transition of voltage inter harmonics from 10 to 5 of nominal voltage Mains Signaling Voltage Voltage signals whose frequencies are different from the fundamenta...

Page 164: ...s indicate the signaling voltage values on all the three phases Dips Swells And Interruptions DSI The power quality recording is equipped with a software power quality sensor that automatically detect...

Page 165: ...te conditions To measure rapid voltage changes thresholds are defined for each of the following The minimum rate of change The minimum duration of the steady state conditions The minimum difference in...

Page 166: ...Appendix B INFORMA PMD A Functions 159 www qualitrolcorp com Figure B 9 RMS Envelope PQRVC...

Page 167: ...1 2 RMS Current RMS voltage Current X X X Harmonic up to 50 individually and inter harmonic up to 49 individually voltage current X X X THD TDD X X X Power 1 Ph Active 3 Ph Active 1 Ph Reactive 3 Ph...

Page 168: ...it The device may be configured in order to perform one or more functions Sensor Inhibit Using Software Configuration Each PQ sensor can be individually enabled disabled by user configurations Sensor...

Page 169: ...ponding logs and records are generated UA Both Applied on Urms 1 2 data If the Urms 1 2 value exceeds the UA_Over Start threshold calculated value OR reduces below the UA_Under Start threshold calcula...

Page 170: ...uration is configured for more than 10 minutes the data corresponding to the duration of drift will not be available o In the IEC 61000 report data will not be available for the duration of the drift...

Page 171: ...boundary till then all recorded data will be discarded Backward time shift of more than 10 minutes The device will not record data until the device time reaches the current recording time PQ recordin...

Page 172: ...eleting Records Note The user may be prompted for a password to access this Web page 3 Select all records by clicking on the individual check boxes and then click the Delete selected data from system...

Page 173: ...for 3U star cabling Ph N type Parameters Total Nos 10 seconds Frequency 1 RMS 3 Zero Sequence 1 Positive Sequence 1 Negative Sequence 1 Unbalance and Zero Unbalance 2 Harmonics up to 50th order 150 I...

Page 174: ...32 Flicker short term 10 minutes Pst 3 Frequency 10 minutes 1 Signaling Voltages 3 3 Crest Factor 3 10 12 Cycle Calculation Under and Over Deviation 6 Voltage Urms 1 2 Calculation RMS 3 366 The follow...

Page 175: ...Ph Ph type Parameters Total Nos 10 seconds Frequency 1 RMS 3 Zero Sequence 1 Positive Sequence 1 Negative Sequence 1 Unbalance and Zero Unbalance 2 Harmonics up to 50th order 150 Inter harmonics up to...

Page 176: ...Flicker short term 10 minutes Pst 3 Frequency 10 minutes 1 Signaling Voltages 3 3 10 12 cycle calculation Under and Over Deviation 6 Voltage Urms 1 2 Calculation RMS 3 Zero Sequence 1 Positive Sequenc...

Page 177: ...e 1 Positive Sequence 1 Negative Sequence 1 Unbalance and Zero Unbalance 2 Harmonics up to 50th order 150 Inter harmonics up to 50th order 147 THD THD THD Odd THD Even 9 Flicker instantaneous Pinst 32...

Page 178: ...e power factor 1 cos phi 0 Power Harmonic Power 0 Crest Factor 6 Energy 8 695 The following calculations are possible for 4U 4I star cabling Ph N type Parameters Total Nos 10 seconds Frequency 1 RMS 4...

Page 179: ...hase Reactive Power 3 Three Phase Reactive Power 1 Single Phase Apparent Power 3 Three Phase Apparent Power 1 Single Phase Distorted Power 3 Three Phase Distorted Power 1 Single phase power factor 3 T...

Page 180: ...uence 1 Negative Sequence 1 Unbalance and Zero Unbalance 2 RMS 3 Harmonic up to 50th order 150 Inter harmonics 147 TDD 3 Current 10 12 cycle calculation k Factor 3 Urms 1 2 Calculation RMS 3 Single Ph...

Page 181: ...t 32 Flicker short term 10 minutes Pst 3 Frequency 10 minutes 1 10 12 cycle calculation Signaling Voltages 3 Under and Over Deviation 6 Voltage Urms 1 2 Calculation RMS 4 Zero Sequence 1 Positive Sequ...

Page 182: ...ero Sequence 1 Positive Sequence 1 Negative Sequence 1 Unbalance and Zero Unbalance 2 Harmonics up to 50th order 150 Inter harmonics up to 50th order 147 THD THD THD Odd THD Even 9 Flicker instantaneo...

Page 183: ...Phase Distorted Power 1 Single phase power factor 3 Three phase power factor 1 cos phi 3 Power Harmonic Power 150 Crest Factor 6 Energy 8 829 Delta Topology The following calculations are possible for...

Page 184: ...Negative Sequence 1 Unbalance and Zero Unbalance 2 Harmonics up to 50th order 150 Inter harmonics up to 50th order 147 THD THD THD Odd THD Even 9 Flicker instantaneous Pinst 32 Flicker short term 10 m...

Page 185: ...ve Power 1 Single Phase Reactive Power 0 Three Phase Reactive Power 1 Single Phase Apparent Power 0 Three Phase Apparent Power 1 Single Phase Distorted Power 0 Three Phase Distorted Power 0 Single pha...

Page 186: ...minutes 1 Signaling Voltages 3 3 10 12 cycle calculation Under and Over Deviation 6 Voltage Urms 1 2 Calculation RMS 3 Zero Sequence 1 Positive Sequence 1 Negative Sequence 1 Unbalance and Zero Unbala...

Page 187: ...gh speed monitoring and recording of the power system and equipment The recording is carried out when a system fault occurs which is user configurable The following types of sources can initiate a DFR...

Page 188: ...ypes Sensor Inhibit Using Software Configuration Each FR sensor can be individually enabled disabled by user configuration Sensor Inhibit Using Digital Input Configuration Each FR sensor can be inhibi...

Page 189: ...ggered If the computed value of that configured parameter exceeds the Under_Stop threshold calculated value later then the event is de triggered Corresponding logs and records are generated Both Appli...

Page 190: ...ositive Sequence angle 1 Negative Sequence amplitude 1 Negative Sequence angle 1 Zero Sequence amplitude 1 Voltage Zero Sequence angle 1 RMS Magnitude fundamental 3 Phase Angle fundamental 3 RMS Magni...

Page 191: ...ence amplitude 1 Negative Sequence angle 1 Zero Sequence amplitude 1 Voltage Zero Sequence angle 1 RMS Magnitude fundamental 6 Phase Angle fundamental 6 RMS Magnitude full 6 Positive Sequence amplitud...

Page 192: ...uence amplitude 1 Negative Sequence angle 1 Zero Sequence amplitude 1 Voltage Zero Sequence angle 1 RMS Magnitude fundamental 9 Phase Angle fundamental 9 RMS Magnitude full 9 Positive Sequence amplitu...

Page 193: ...nnel is A C 1 Stand alone channel 5 AC DC 1 Stand alone Channel5 angle if channel is A C 1 Stand alone channel 6 AC DC 1 Stand alone Channel6 angle if channel is A C 1 Stand alone channel 7 AC DC 1 St...

Page 194: ...Appendix C Recording Data Rates and Memory Consumtion Rates 187 www qualitrolcorp com Appendix C Recording Data Rates and Memory Consumption Rates...

Page 195: ...inutes Total Time Duration Taken to Fill Assigned Memory in minutes Mode of Operation Alarm Level PQ Permanent recording 10 min 40 1188 Max 10 147880 Linear Circular x alarm threshold Permanent record...

Page 196: ...shold Embedded recordings Histograms 61000 3 6 7 40 55 Max 10 17270 Linear Circular x alarm threshold Embedded recordings Histograms Free interval Histogram 40 512 Max 1 200 Linear Circular x alarm th...

Page 197: ...al Time Duration Taken to Fill Assigne d Memory in seconds DFR 300 1 128 Linear Circular x alarm threshold Memory Assigned in MB Record Duration in minutes Total Time Duration Taken to Fill Assigned M...

Page 198: ...qualitrolcorp com Functionality Default Memory Assigned in MB Number of Parame ters Record Duration in minutes Total Time Duration Taken to Fill Assigned Memory in minutes Mode of Operation Alarm Leve...

Page 199: ...Appendix D License Information 192 www qualitrolcorp com Appendix D License Information...

Page 200: ...eq file refer to Section D 1 When the TCP IP communication is established between the device and the computer open a Web browser and enter the URL in the following format http IP_Address mfgindex html...

Page 201: ...ady exists then the System Information Web page is displayed The Web page shows the existing license information such as the device serial number customer ID order number features included in the curr...

Page 202: ...provided by the sales representative Figure D 2 Modifying the License Request 3 Click Modify Request 4 A new serial_number req file is generated on the device s file system Save the serial_number req...

Page 203: ...ile on the computer 6 Using the Browse button locate the file and click Install license Figure D 4 Installing the License 7 The license is transferred to the INFORMA PMD A device s file system and the...

Page 204: ...Appendix E Battery Replacement Procedure 197 www qualitrolcorp com Appendix E Battery Replacement Procedure...

Page 205: ...Device To replace a battery the following steps must be performed 1 Switch off the main power supply to the INFORMA PMD A 3U device and disconnect the input power cord 2 Switch off the battery by usi...

Page 206: ...igure E 2 CN5 Connector 5 Uninstall the old battery by removing the screws as shown below 6 Install the new battery 7 Connect the new battery to the CN5 connector Figure E 3 Rajamane Battery 8 Reconne...

Page 207: ...Appendix F On Board LED Functionalities and CPU MMI Modes 200 www qualitrolcorp com Appendix F On Board LED Functionalities and CPU MMI Modes...

Page 208: ...Modes 201 www qualitrolcorp com Appendix F On Board LED Functionalities LED Functions on the Motherboard All LEDs are red in color Figure F 1 LEDs on the Motherboard D701 D703 D36 D34 D1 D35 D37 D21 D...

Page 209: ...occurred and is still in reset condition D21 Debug LED Reserved for future use D22 CPU_DONE indicates that FPGA is programmed D704 Debug LED for PIC D35 Voltage indicator for 12 V D37 Voltage indicato...

Page 210: ...Dip switch position the MMI mode is decided There are two Dip switch positions one indicates the CPU mode 1 CPU mode or 2 CPU mode and the other indicates if the LCD is available The 2 CPU mode alway...

Page 211: ...e CPU must be connected to the first UART port refer to legend J1 on MMI card Figure F 3 MMI Card Dip Switch S1 and First UART Port J1 If the CPU is connected to the second UART port J2 on MMI card th...

Page 212: ...Appendix G On Board Jumper Settings 205 www qualitrolcorp com Appendix G On Board Jumper Settings...

Page 213: ...hen the TX AFE HIA AFE board is tested without Motherboard Standalone With motherboard Normal Mode 1 2 1 2 Channel Configured as Voltage Channel Configuration for CH1 J13 2 3 Channel Configured as Cur...

Page 214: ...ion 2 3 Mounted for Input 140V FSD J25 1 2 Mounted for Input 270V FSD 2 3 Mounted for Input 480V FSD Voltage J31 1 2 Mounted for Input 800V FSD Voltage Range Selection 1 2 Mounted for Input 10A FSD J4...

Page 215: ...Mounted for Input 20A FSD 1 2 Mounted for Input 50A FSD Current J67 2 3 Mounted for Input 100A FSD Current Range Selection 1 2 Channel Configured as Voltage Channel Configuration for CH4 J18 2 3 Chan...

Page 216: ...Channel Configured as Current For Channel Configuration 2 3 Mounted for Input 140V FSD J26 1 2 Mounted for Input 270V FSD 2 3 Mounted for Input 480V FSD Voltage J32 1 2 Mounted for Input 800V FSD Vol...

Page 217: ...nge Selection 1 2 Mounted for Input 10A FSD J69 2 3 Mounted for Input 20A FSD 1 2 Mounted for Input 50A FSD CH6 Current J65 2 3 Mounted for Input 100A FSD Current Range Selection 1 2 Channel Configure...

Page 218: ...hannel Configuration for CH8 J41 2 3 Channel Configured as Current For Channel Configuration 2 3 Mounted for Input 140V FSD J27 1 2 Mounted for Input 270V FSD 2 3 Mounted for Input 480V FSD Voltage J3...

Page 219: ...or Input 480V FSD Voltage J53 1 2 Mounted for Input 800V FSD Voltage Range Selection 1 2 Mounted for Input 10A FSD J68 2 3 Mounted for Input 20A FSD 1 2 Mounted for Input 50A FSD CH9 Current J64 2 3 M...

Page 220: ...J152 2 3 Channel Configured as Current J16 2 3 J25 1 2 J162 2 3 J15 1 2 J40 2 3 J41 2 3 Channel Configured as DC Voltage J16 2 3 J25 1 2 J15 2 3 J162 2 3 J40 1 2 J41 1 2 Channel Configured as mA loop...

Page 221: ...election 1 2 Mounted for Input 12VDC FSD J12 2 3 Mounted for Input 120VDC FSD 1 2 Mounted for Input 240VDC FSD DC Voltage J13 2 3 Mounted for Input 480VDC FSD DC Voltage Range Selection J37 1 2 J42 2...

Page 222: ...Mounted for Input 800V FSD Voltage Range Selection 1 2 Mounted for Input 10A FSD J6 2 3 Mounted for Input 20A FSD 1 2 Mounted for Input 50A FSD Current J7 2 3 Mounted for Input 100A FSD Current Range...

Page 223: ...nel Configured as DC Voltage J46 2 3 J47 1 2 J44 2 3 J164 2 3 J72 1 2 J73 2 3 Channel Configured as mA loop J72 1 2 J73 2 3 J154 1 2 Channel Configured as CC 2 3 Mounted for Input 140V FSD J19 1 2 Mou...

Page 224: ...r Input 480VDC FSD DC Voltage Range Selection J52 1 2 J53 2 3 J24 1 2 J90 2 3 J91 1 2 Channel Configured as Voltage J90 1 2 J91 2 3 J155 2 3 Channel Configured as Current J52 2 3 J53 1 2 J24 2 3 J50 1...

Page 225: ...20A FSD 1 2 Mounted for Input 50A FSD Current J21 2 3 Mounted for Input 100A FSD Current Range Selection 1 2 Mounted for Input 12VDC FSD J48 2 3 Mounted for Input 120 VDC FSD 1 2 Mounted for Input 240...

Page 226: ...hannel Configured as CC 2 3 Mounted for Input 140V FSD J56 1 2 Mounted for Input 270V FSD 2 3 Mounted for Input 480V FSD Voltage J57 1 2 Mounted for Input 800V FSD Voltage Range Selection 1 2 Mounted...

Page 227: ...ge J116 1 2 J117 2 3 J157 2 3 Channel Configured as Current J78 2 3 J45 2 3 J79 1 2 J76 1 2 J116 2 3 J117 1 2 Channel Configured as DC Voltage J78 2 3 J79 1 2 J76 2 3 J45 2 3 J116 1 2 J117 2 3 Channel...

Page 228: ...ent Range Selection 1 2 Mounted for Input 12VDC FSD J74 2 3 Mounted for Input 120VDC FSD 1 2 Mounted for Input 240VDC FSD DC Voltage J75 2 3 Mounted for Input 480VDC FSD DC Voltage Range Selection J96...

Page 229: ...ed for Input 480V FSD Voltage J88 1 2 Mounted for Input 800V FSD Voltage Range Selection 1 2 Mounted for Input 10A FSD J80 2 3 Mounted for Input 20A FSD 1 2 Mounted for Input 50A FSD Current J81 2 3 M...

Page 230: ...138 2 3 J139 1 2 Channel Configured as DC Voltage J109 2 3 J110 1 2 J107 2 3 J51 2 3 J138 1 2 J139 2 3 Channel Configured as mA loop J138 1 2 J139 2 3 for CH8 J159 1 2 Channel Configured as CC 2 3 Mou...

Page 231: ...240VDC FSD DC Voltage J106 2 3 Mounted for Input 480VDC FSD DC Voltage Range Selection J122 1 2 J123 2 3 J64 1 2 J140 2 3 J141 1 2 Channel Configured as Voltage J140 1 2 J141 2 3 J160 2 3 Channel Con...

Page 232: ...for Input 50A FSD Current J112 2 3 Mounted for Input 100A FSD Current Range Selection 1 2 Mounted for Input 12VDC FSD J118 2 3 Mounted for Input 120VDC FSD 1 2 Mounted for Input 240VDC FSD CH9 DC Vol...

Page 233: ...2 3 J83 1 2 2 3 J29 2 3 1 2 J130 1 2 2 3 J133 2 3 1 2 J135 2 3 1 2 J134 2 3 1 2 J129 1 2 2 3 J84 2 3 1 2 J128 2 3 1 2 J147 2 3 1 2 J131 2 3 1 2 J149 1 2 2 3 J127 1 2 2 3 J148 1 2 2 3 J143 2 3 1 2 J144...

Page 234: ...Position Selection Description Default jumper setting 1 2 12V IRIG OUT Signal For Modulated IRIG output 1 IRIG OUT Voltage Selection CN712 2 3 5V IRIG OUT Signal For TTL IRIG output AM Modulator oper...

Page 235: ...led WDI Control Jumper 1 2 1 2 COM 3 Port is configured as CPU COM Port 7 IRIG J or User Port Selection CN18 2 3 COM 3 Port is configured as PIC COM PORT for IRIG J IN PIC or CPU as COM3 Port 1 2 1 2...

Page 236: ...PS Antenna Voltage Select JPR3 2 3 3 3V For antenna voltage input 1 2 The following table lists the DFE jumper settings DFE Jumper Table Sl No Purpose Jumper Legend Position Selection Description 1 2...

Page 237: ...J3 Mount J4 Unmount Output contacts open J3 Unmount Unmount 2 Relay Contact 2 J4 Mount Output contacts closed Mount J5 Mount J6 Unmount Output contacts open J5 Unmount Unmount 3 Relay Contact 3 J6 Mou...

Page 238: ...Appendix H Linearity Report of TX AFE and HIA AFE 231 www qualitrolcorp com Appendix H Linearity Report of TX AFE and HIA AFE...

Page 239: ...270 V FSD Frequency 50 Hz Nominal Voltage 120 V Input voltage applied in volts Voltage measured by the device in volts Error in terms of Input applied Error in terms of FSD 12 11 9999 0 000833333 3 7...

Page 240: ...tap setting 100 A FSD Frequency 50 Hz Nominal Voltage 10 A Input current applied in Amps Current measured by the device in Amps Error in terms of Input applied Error in terms of FSD 0 5 0 496845 0 631...

Page 241: ...Appendix H Linearity Report of TX AFE and HIA AFE 234 www qualitrolcorp com Figure H 3 Error in Terms of FSD for Current Channel Figure H 4 Error in Terms of Fed Input for Current Channel...

Page 242: ...d by the device in volts Error in terms of Input applied Error in terms of FSD Error in terms of of Nominal voltage 12 12 002 0 016666667 0 000740741 0 001666667 24 24 0037 0 015416667 0 00137037 0 00...

Page 243: ...Appendix H Linearity Report of TX AFE and HIA AFE 236 www qualitrolcorp com Figure H 6 Error in Terms of FED Input 120 VAC nominal Figure H 6 Error in Terms of Udin 120 VAC...

Page 244: ...Voltage 10 A Input current applied in Amps Current observed in Amps Error in terms of Input Error in terms of FSD 0 5 0 5000132 0 00264 1 32E 05 1 1 000136 0 0136 0 000136 2 1 999933 0 00335 6 7E 05 3...

Page 245: ...Appendix H Linearity Report of TX AFE and HIA AFE 238 www qualitrolcorp com Figure H 8 Error in Terms of FED Input for Current Channel 10 AAC nominal...

Page 246: ...References 239 www qualitrolcorp com References...

Page 247: ...References 240 www qualitrolcorp com References For Configuration forms refer to the document 36 8218 xx For details of error log messages codes and their meanings refer to the document 40 08576 01...

Page 248: ...ALITROL produces thousands of different types of products on demand each customized to customers unique requirements QUALITROL Field Services QUALITROL provides on site commissioning start up and comp...

Reviews: