Appendix B – INFORMA PMD-A Functions
182
www.qualitrolcorp.com
INFORMA PMD-A provides the following FR data types on which different types of sensors
can be configured.
FR Calculated
Quantity
Over
Under
BOTH
Power
Swing
ROC (dx/dt)
Frequency
x x x x x
RMS
Fundamental/Full
x x x - x
Power x x x x x
Sequence
components
amplitude
x x x - -
AC RMS /DC
Magnitude for
standalone
channels
x x x - -
Over:
Applied on all FR parameters. If the computed value of the configured parameters
exceeds the “Over_Start -threshold calculated” value, then the event is triggered. If the
computed value of that configured parameter reduces below the “Over_Stop -threshold
calculated” value later, then the event is de-triggered. Corresponding logs and records are
generated.
Under:
Applied on all FR parameters. If the computed value of the configured parameters
reduces below the “Under_Start -threshold calculated” value, then the event is triggered. If
the computed value of that configured parameter exceeds the “Under_Stop -threshold
calculated” value later, then the event is de-triggered. Corresponding logs and records are
generated.
Both:
Applied on all FR parameters. If the computed value of the configured parameters
reduces below the “Under_Start -threshold calculated” values,
OR
exceeds the “Over_Start -
threshold calculated” value, then the event is triggered. If the computed value of that
configured parameter exceeds the “Under_Stop -threshold calculated” value,
OR
reduces
below the “Over_Stop -threshold calculated” value later, then the event is de-triggered.
Retriggering happens if the parameter value swings between Under to Over and vice-versa.
Corresponding logs and records are generated.
Power Swing:
Applied on frequency and power values. The event is triggered when it
detects poorly dampened oscillations. It is de-triggered if normal condition resumes.
Dx/dt:
Applied on RMS values of voltage and current, frequency, and power values. The
event is triggered when it detects magnitude variations. It is de-triggered if normal condition
resumes.
Summary of Contents for INFORMA PMD-A
Page 1: ...User Manual www qualitrolcorp com INFORMA PMD A Data Acquisition Unit Document ID 40 08557 01...
Page 7: ...Contents Contents iv www qualitrolcorp com References 240...
Page 8: ...About This Manual 1 www qualitrolcorp com Chapter 1 About This Manual...
Page 12: ...Overview 5 www qualitrolcorp com Chapter 2 Overview...
Page 15: ...Components and Specifications 8 www qualitrolcorp com Chapter 3 Components and Specifications...
Page 58: ...Installation 51 www qualitrolcorp com Chapter 4 Installation...
Page 86: ...Configuration 79 www qualitrolcorp com Chapter 6 Configuration...
Page 108: ...Configuration 101 www qualitrolcorp com Figure 6 22 PQ Free Interval Continuous Recording...
Page 120: ...Maintenance 113 www qualitrolcorp com Chapter 7 Maintenance...
Page 126: ...Maintenance 119 www qualitrolcorp com Figure 7 7 Voltage Calibration...
Page 166: ...Appendix B INFORMA PMD A Functions 159 www qualitrolcorp com Figure B 9 RMS Envelope PQRVC...
Page 199: ...Appendix D License Information 192 www qualitrolcorp com Appendix D License Information...
Page 246: ...References 239 www qualitrolcorp com References...