Components and Specifications
40
www.qualitrolcorp.com
Using IRIG-B
INFORMA PMD-A can be configured to use an external IRIG-B time source as the time
reference. Connect the IRIG-B cable from the IRIG-B time source to the BNC connector.
INFORMA PMD-A IRIG-B supports the following:
1. IRIG-B
001
Modulation Type :
Unmodulated, also called DC level shift.
Frequency/Resolution:
No carrier
Coded expression :
BCD (does not include year information), CF (includes year
information).
2. IRIG-B
121
Modulation Type:
Amplitude Modulated Sine Wave
Frequency/Resolution:
1000 Hz carrier
Coded expression:
BCD (does not include year information), CF (includes year
information).
The INFORMA PMD-A device to which the IRIG-B time source is connected will be the time
master. This time master INFORMA PMD-A device may now be used to provide time
synchronization to other slave INFORMA PMD-A devices, using the differential or Fiber
connection for PPS synchronization.
Using IRIG-J
INFORMA PMD-A can be configured to use an external IRIG-J time source as the time
reference. Connect the serial cable from the IRIG-J time source to the RS232-2 port.
INFORMA PMD-A IRIG-J supports IRIG-J-14.
IRIG-J-14
The IRIG-J-14 is a Time-of-Year format with a 1-second resolution and frame length. The
IRIG-J-14 baud rate is 1200.
The INFORMA PMD-A device to which the IRIG-J time source is connected will be the time
master. This time master INFORMA PMD-A device may now be used to provide time
synchronization to other slave INFORMA PMD-A devices, using the differential or Fiber
connection for PPS synchronization.
3.10.2. INFORMA PMD-A as Slave
When INFORMA PMD-A is configured as a time slave, it receives PPS input from the time
master and derives the time of the day by using NTP over the network.
INFORMA PMD-A can be configured as a time slave using iQ+, as shown in the following
figure. Refer to iQ+ help for additional information.
For INFORMA PMD-A to be fully time-synchronized as a time slave, both PPS
and NTP are required from the time master.
Summary of Contents for INFORMA PMD-A
Page 1: ...User Manual www qualitrolcorp com INFORMA PMD A Data Acquisition Unit Document ID 40 08557 01...
Page 7: ...Contents Contents iv www qualitrolcorp com References 240...
Page 8: ...About This Manual 1 www qualitrolcorp com Chapter 1 About This Manual...
Page 12: ...Overview 5 www qualitrolcorp com Chapter 2 Overview...
Page 15: ...Components and Specifications 8 www qualitrolcorp com Chapter 3 Components and Specifications...
Page 58: ...Installation 51 www qualitrolcorp com Chapter 4 Installation...
Page 86: ...Configuration 79 www qualitrolcorp com Chapter 6 Configuration...
Page 108: ...Configuration 101 www qualitrolcorp com Figure 6 22 PQ Free Interval Continuous Recording...
Page 120: ...Maintenance 113 www qualitrolcorp com Chapter 7 Maintenance...
Page 126: ...Maintenance 119 www qualitrolcorp com Figure 7 7 Voltage Calibration...
Page 166: ...Appendix B INFORMA PMD A Functions 159 www qualitrolcorp com Figure B 9 RMS Envelope PQRVC...
Page 199: ...Appendix D License Information 192 www qualitrolcorp com Appendix D License Information...
Page 246: ...References 239 www qualitrolcorp com References...