Appendix A – Technical Specifications
142
www.qualitrolcorp.com
Category
Parameters
Specifications
Typical Load
25 VA for 3U INFORMA PMD-A device and
50 VA for 6U INFORMA PMD-A device
Auxiliary Output
DC output 12 VDC at 750 mA
Input Range
Nominal (
full scale
) in VAC:
63.5 (
140
)
120 (
270
)
240 (48
0
)
440 (8
00
)
Safety Rating
300 V CAT III, 150 V CAT IV
Maximum
Overload
1000 VAC continuous
Input Option 1:
TX_AFE
Impedance: > 2.5 M
Ω
(at 63.5 V) ,> 2 M
Ω
(at
120 V) , > 1 M
Ω
(at 240 V), > 0.1 M
Ω
(at 440
V)
16-bit resolution for voltage
Input Option 2:
HIA-AFE
Impedance: > 4M
Ω
24-bit resolution for voltage/current channels:
Accuracy
≤
0.1°
Analog Inputs -
Voltage AC
Optional for
HIA-AFE:
Fast Transient
Recording
The transient voltage (up to 6 kV) is detected
by the TR module with a bandwidth of 2.5 kHz
to 5 MHz.
Sampling rates (user configurable):
20 MHz, 10 MHz, 5 MHz, 2.5 MHz, 1.25 MHz
12-bit resolution
Input Range
Full scale in VDC: 12, 120, 240, 480
Safety Rating
300 V CAT III, 150 V CAT IV
Maximum
Overload
500 VDC continuous
Analog Inputs -
Voltage DC
(optional
instead of AC)
Input Impedance
>= 420 K
Ω
- (TX-AFE and HIA-AFE)
Analog Inputs –
Current
Input Range
Nominal (
full scale
) in AAC: 1 (
10
), 2 (
20
), 5
(
50
), 10 (
100
)
Summary of Contents for INFORMA PMD-A
Page 1: ...User Manual www qualitrolcorp com INFORMA PMD A Data Acquisition Unit Document ID 40 08557 01...
Page 7: ...Contents Contents iv www qualitrolcorp com References 240...
Page 8: ...About This Manual 1 www qualitrolcorp com Chapter 1 About This Manual...
Page 12: ...Overview 5 www qualitrolcorp com Chapter 2 Overview...
Page 15: ...Components and Specifications 8 www qualitrolcorp com Chapter 3 Components and Specifications...
Page 58: ...Installation 51 www qualitrolcorp com Chapter 4 Installation...
Page 86: ...Configuration 79 www qualitrolcorp com Chapter 6 Configuration...
Page 108: ...Configuration 101 www qualitrolcorp com Figure 6 22 PQ Free Interval Continuous Recording...
Page 120: ...Maintenance 113 www qualitrolcorp com Chapter 7 Maintenance...
Page 126: ...Maintenance 119 www qualitrolcorp com Figure 7 7 Voltage Calibration...
Page 166: ...Appendix B INFORMA PMD A Functions 159 www qualitrolcorp com Figure B 9 RMS Envelope PQRVC...
Page 199: ...Appendix D License Information 192 www qualitrolcorp com Appendix D License Information...
Page 246: ...References 239 www qualitrolcorp com References...