October 12, 2017
7080-162B
11
MT VERNON E2-C
USA INSTALLATIONS
: A non-c
ombustible floor protec
-
tion is recommended
extending beneath the flue pipe when
installed with horizontal venting or under the Top Vent
Adapter with vertical installation.
CANADA INSTALLATIONS
: A non-c
ombustible floor pro
-
tection
extending beneath the flue pipe
is
required
with hor-
izontal venting or under the Top Vent Adapter with vertical
installation.
32-1/8 in.
minimum
30-1/4 in.
minimum
6 in
(FROM FUEL DOOR
OPENING)
6 in
USA
6 in
FUEL DOOR OPENING
24-1/4 in.
minimum
152mm
from fuel door opening
816mm
minimum
768mm
minimum
CANADA
Must extend 51mm
beyond each side
of pipe (shaded area)
to the wall thimble.
152mm
152mm
FUEL DOOR OPENING
514mm
minimum
44-1/8 in.
22-5/8 in.
24-1/4 in.
39-3/4 in.
USA
6 in.
from the fuel door
opening
1121mm
575mm
616mm
1010mm
152mm
(front door opening)
CANADA
Must extend 51mm
beyond each side
of pipe (shaded area)
to the wall thimble.
Figure 11.1
Figure 11.2
Figure 11.3
Figure 11.4
C. Hearth Pad Requirements (UL & ULC)
Fire Risk.
Comply with all minimum clearances to combustibles
as specified.
Failure to comply may cause house fire.
WARNING
EMBER PROTECTION:
It is necessary to install a Type I
floor protector.
Floor protector must be non-combustible material, extending
beneath appliance with a minimum of 6 inches (152mm) in
front of glass and 6 inches (152mm) to both sides of the
fuel loading door. Open the door and measure 6 inches
(152mm) from the side edge of the opening in the face of the
appliance.*
See exception.