Page 25
Quadra-Fire • Hudson Bay • 7003-121_R20 • 11/14
• A small amount of air will be in the gas supply lines.
When first lighting appliance it will take a short time for
air to purge from lines. When purging is complete the
appliance will light and operate normally.
Air only needs to be purged again if gas valve has been
turned to the OFF position.
Fire hazard.
Do NOT change the valve settings.
• This valve has been preset at the factory.
• Changing valve settings may result in fire
hazard or bodily injury.
CHECK FOR GAS LEAKS
Explosion Risk
Fire Risk
Asphyxiation Risk
• Check all fittings and connections.
• Do not use open flame.
• After the gas line installation is complete, all
connections must be tightened and checked
for leaks with a commercially-available, non-
corrosive leak check solution. Be sure to rinse
off all leak check solution following testing.
Fittings and connections may have loosened
during shipping and handling.
Omni-Test Laboratories listed gas appliances are tested
and approved without requiring changes for elevations
from 0 to 2000 feet in the U.S.A. and 0 to 4500 feet in
Canada.
When installing this appliance at an elevation above 2000
feet, it may be necessary to decrease the input rating by
changing the existing burner orifice to a smaller size. Input
rate should be reduced by 4% for each 1000 feet above a
2000 foot elevation in the U.S.A. If the heating value of the
gas has been reduced, these rules do not apply. To identify
the proper orifice size, check with the local gas utility.
If installing this appliance at an elevation above 4500 feet
(in Canada), check with local authorities.
NOTE:
A listed (and Commonwealth of Massachusetts
approved) 1/2 inch (13mm) T-handle manual shut-off valve and
flexible gas connector are connected to the 1/2 inch (13mm)
control valve inlet.
• If substituting for these components, please consult local
codes for compliance.
NOTE:
The gap between the supply piping and gas access
hole may be plugged with non-combustible insulation to prevent
cold air infiltration.
C. Gas Connection
NOTE:
Have the gas supply line installed in accordance with
local building codes, if any. If not, follow ANSI Z223.1. Instal-
lation should be done by a qualified installer approved and/or
licensed as required by the locality. (In the Commonwealth of
Massachusetts, installation must be performed by a licensed
plumber or gas fitter.)
Leak test all gas line joints and the gas control valve prior
to and after starting the fireplace.
Before making the gas connection, ensure that the appliance
you are installing is designed for the type of gas being
supplied. This information can be found on the Ratings Label
under the appliance. If the appliance has been converted to
propane (LP), the valve cover should have a label stating
that the unit has been converted to propane.
Connect the gas line at the 3/8 in. (9.5mm) pipe connector
on the valve at the back of appliance. We recommend
connecting the appliance with an approved flex gas line.
If flex gas lines are not approved in your area, you must
connect a hard pipe to the gas hookup.
You must supply a manual shut-off valve in a visible location
within 3 feet (914mm) of the appliance.
Gas Leak Risk.
• Support control when attaching pipe to prevent
bending gas line.
Fire or Explosion Hazard
• Gas build-up during line purge may ignite.
• Purge should be performed by qualified technician.
• Ensure adequate ventilation.
• Ensure there are no ignition sources such as
sparks or open flame.
WARNING
!
WARNING
!
WARNING
!
WARNING
!