GARNET DIRECT VENT ROOM HEATER
250-6443B October 7, 2003 Page 15
R
GARNET DIRECT VENT ROOM HEATER
250-6443B October 7, 2003 Page 16
R
3/4
3/4
3/4
Fig. 1 Solid Trim Ring Shown
Fig. 3 Ventilated Trim Ring Shown
INSTALLING SLIM LINE TRIM RING
and HEAT SHIELD
1. Measure from floor to center line of the vent pipe. Cut
out a 9-1/2" hole in the wall. Hold the Trim Ring/Heat Shield
Assembly in place and place a mark on the shield with a
black marker where it protrudes through the exterior wall.
See Fig. A on Page 17.
2. Use that mark as a guide to trim off excess Heat Shield
with a pair of sheet metal shears.
Note:
When installing the Trim Ring/Heat Shield assembly
make sure the Trim Ring is centered in the hole and that
the shield is above the pipe. There must be a minimum of
3/4" minimum clearance maintained to combustibles from
the top of the Heat Shield.
See Fig. 4.
3. Ensure that framing on the inside of the wall is a minimum
inner framing diameter of 10" x 10".
4. The four Trim Ring mounting screws provided should be
replaced with appropriate fasteners for stucco, brick, concrete,
or other types of sidings.
BEFORE YOU BEGIN:
Venting configuration will determine which Trim Ring you
use in your installation. Review
Figures A, B
and
C
on
Page 17
.
Figures A
and
B
can use either Trim Ring, while
Figure C
REQUIRES the Ventilated Trim Ring.
ASSEMBLING SLIM LINE TRIM RING
and HEAT SHIELD
1. Choose the appropriate Trim Ring for your installation.
Lay on flat surface and bend up the 6 welded brackets into
a 90 degree position. The brackets along the outer edge of
the ring are for locating the ring in the center of the hole.
See Fig. 1.
2. The Heat Shield is shipped flat and must be hand bent
into a half circle before attaching to Trim Ring. Bend Heat
Shield.
See Fig. 2
.
Note:
Wear leather gloves when bending the Heat Shield
to prevent injury.
3. Attach the Heat Shield to the Trim Ring with the four
screws provided. Screws go through the Heat Shield and
into the brackets on the Trim Ring.
See Fig. 3.
Fig. 2 Bending Heat Shield
Maintain minimum 3/4" clearance to
combustibles from top of shield.
Fig. 4
3/4"
3/4"
3/4"
SLIM LINE WALL THIMBLE
Part #844-9550