background image

August 

13, 

2018     7061-197P 

     

19

Explorer II

Approved for USA Installation only!

You must use a Quadra-Fire Outside Air Kit Part 

OAK-ACC; which is available from you dealer, for 

installation in a mobile home.

1.  An outside air inlet must be provided for combustion.

2.  Appliance must be secured to the mobile home 

structure by bolting the legs to the floor.  

3.  Appliance must be grounded with #8 solid copper 

grounding wire or equivalent and terminated at each 

end with N.E.C. approved grounding device.

4.  Appliance must be installed with an approved 

UL103 

HT

 ventilated chimney connector, 

UL103 HT

 chimney, 

and terminal cap with spark arrestor.  Never use a 

single wall connector (appliance pipe) in a mobile home 

installation.  Use only double-wall connector pipe, 

Dura-Vent DVL, Selkirk Metalbestos DS or Security 

DL double-wall connector or any listed double-wall 

connector pipe.

5. 

In Canada, this appliance must be connected to a 6 

inch (152mm) factory-built chimney conforming to 

CAN/

ULC-

629M, STANDARD FOR FACTORY BUILT 

CHIMNEYS

6.  Follow the chimney and chimney connector 

manufacturer’s instructions when installing the flue 

system for use in a mobile home.

7.  Maintain clearance to combustibles.

8.  Floor protection requirements must be followed 

precisely.

9.  Use silicone to create an effective vapor barrier at 

the location where the chimney or other component 

penetrates to the exterior of the structure.

NOTE:

  Offsets from the vertical, not exceeding 45°, 

are allowed per

 Section 905(a) of the Uniform 

Mechanical Code (UMC)

. Offsets greater than 45° 

are considered horizontal and are also allowed, 

providing the horizontal run does not exceed 75% 

of the vertical height of the vent. Construction, 

clearance and termination must be in compliance 

with the

 UMC Table 9C. 

This installation must also 

comply with

 NFPA 211.

NOTE:

 Top sections of chimney must be removable to 

allow maximum clearance of 13.5 feet (411cm) 

from ground level for transportation purposes.

Asphyxiation Risk.

NEVER INSTALL IN A SLEEPING ROOM.

Consumes oxygen in the room.

WARNING

CAUTION

THE STRUCTURAL INTEGRITY OF THE MOBILE 

HOME FLOOR, WALL AND CEILING/ROOF MUST BE 

MAINTAINED

Do NOT cut through:

•  Floor joist, wall, studs or ceiling trusses.

•  Any supporting material that would affect the structural 

integrity.

10. Burn seasoned cord wood only.  Other types of 

fuels may generate poisonous gases (e.g., carbon 

monoxide).

11. 

If appliance burns poorly while an exhaust blower is on 

in home, (i.e., range hood), increase combustion air.

12. 

Installation shall be in accordance with the 

Manufacturers Home & Safety Standard (HUD) CFR 

3280, Part 24.

Mobile Home Installation

Summary of Contents for Explorer II series

Page 1: ...revendeur ou visitez www quadrafire com If the information in these instructions is not followed exactly a fire could result causing property damage personal injury or death WARNING Do not store or us...

Page 2: ...Chimney Termination Requirements 12 C 2 10 3 Rule 12 D Chimney Height Rise and Run 13 E Venting Components 13 F Chimney Systems 13 G Installing Chimney Components 15 H Proper Draft 15 5 Appliance Set...

Page 3: ...from the low and high EPA tests using Douglas Fir dimensional lumber A peak BTU out of the appliance calculated using the maximum first hour burn rate from the High EPA Test and the BTU content of cor...

Page 4: ...affle and other interior components NOTE Hearth Home Technologies manufacturer of this appliance reserves the right to alter its products their specifications and or price without notice Improper inst...

Page 5: ...chimney heights Ideal performance is with height of chimney between 14 16 feet 4 26 4 88m measured from the base of the appliance C Negative Pressure Negative pressure results from the imbalance of ai...

Page 6: ...ling winds during the heating season Ensure adequate outdoor air for all combustion appliances and exhaust equipment Ensure furnace and air conditioning return vents are not located in the immediate v...

Page 7: ...he party responsible for use and operation Hearth Home Technologies recommends the following Photographing the installation and copying this checklist for your file That this checklist remain visible...

Page 8: ...t View Figure 8 3 Side View 12 1 4 514MM 27 686mm 29 737mm 20 508mm 29 737mm Figure 8 2 Top View 13 3 8 340mm 7 8 22mm 2 3 8 60mm 25 7 8 657mm 3 8 9mm 29 737mm Figure 8 4 Side View with horizontal flu...

Page 9: ...he appliance See exception WARNING Fire Risk Hearth pads must be installed exactly as specified High temperatures or hot embers may ignite concealed combustibles Corner hearth pad dimensions with sing...

Page 10: ...4 1175 6 1 2 165 N A N A 55 1397 N A For alcove only Six inch diameter listed Double wall air insulated connector pipe with UL103 HT listed factory built Class A chimney or masonry chimney Maximum dep...

Page 11: ...space enclosed by the building envelope This helps to produce more draft especially during lighting and die down of the fire Penetrate the highest part of the roof This minimizes the affects of wind...

Page 12: ...or when there are other factors that affect flue draft B Chimney Termination Requirements Follow manufacturer s instructions for clearance securing flashing and terminating the chimney Figure 12 1 12...

Page 13: ...Listed Chimney Storm Collar Wall Support Roof Brace if required Thimble Figure 13 1 Prefabricated Exterior Chimney E Venting Components Chimney Connector It is also known as flue pipe or appliance pip...

Page 14: ...ey Figure 14 2 2 Entry hole to masonry chimney must be lined with an 8 inch 203mm minimum diameter clay liner or equivalent secured with refractory mortar 3 Construct a 17 inch x 17 inch 432mm x 432mm...

Page 15: ...is must be at least 24 gauge mild steel or 26 gauge blue steel The sections must be attached to the appliance and to each other with the crimped male end pointing toward the appliance All joints inclu...

Page 16: ...materials from packing box 2 Floor Rear Installation Cut a 4 inch 102mm hole in outside wall or floor to accommodate outside air piping Use 4 inch 102mm aluminum metal flex or rigid piping to directly...

Page 17: ...agnet under the bottom left rear corner See Owner s Manual for detailed operating instructions for the blower and snap disc Figure 17 1 Shock Risk Do NOT remove grounding prong from plug Route cord aw...

Page 18: ...op or rear venting installation The appliance is shipped with the flue collar in the top vent position Converting Collar For Rear Vent Installation and Installing Required Horizontal Flue Shield 1 Rem...

Page 19: ...ion requirements must be followed precisely 9 Use silicone to create an effective vapor barrier at the location where the chimney or other component penetrates to the exterior of the structure NOTE Of...

Page 20: ...20 7061 197P August 13 2018 Explorer II Date of Service Performed By Description of Service 7 Reference Materials A Service Maintenance Log...

Page 21: ...it Floor Rear OAK ACC Outside Air Collar Assembly 7033 039 Outside Air Shield 33271 Y Firescreen SCR 7061 FASTENERS Avk Rivnut Repair Kit 1 4 20 3 8 16 Rivnut Tools RIVNUT REPAIR Y Nut Ser Flange Smal...

Page 22: ...purchased installed _________________________________________________________________________ Serial Number ____________________________________ Location on appliance ___________________________ Deal...

Reviews: