background image

August 

13, 

2018     7061-197P 

     

15

Explorer II

Trim Collar 

Chimney Section 

with 2 inch 

(51mm) 

Clearance to 

Combustibles

Chimney 

Connector 

Fire Clay Flue 

Liner 

with Airspace 

Masonry 

 Chimney 

Wall Band to 

Secure Chimney 

Section 

Wood Studs Used 

for Framing - Spaced 

2 inch (51mm) 

clearance from 

Masonry Chimney

Wall Spacer 

Solid Pack Chimney with Metal Supports as a Thimble

Figure 15.1

Fire Risk.

Do NOT pack insulation or other combustibles 

between spacers.

• 

ALWAYS maintain specified clearances around 

venting and spacers.

• 

Install spacers as specified.

Failure to keep insulation or other material away 

from vent pipe may cause fire.

WARNING

Chimney Flue

Liner

Fireclay

Liner or

Equivalent

Masonry Chimney

Constructed to NFPA 211

Wall Spacer

Wall Band

Trim Collar

Chimney

 Connector

1 inch (25mm) Air

Space to Chimney

Section

Min. Clearance

2 inch (51mm)

Min. Chimney Clearance to

Wall Spacer and

Combustibles - 2 inch (51mm)

Chimney Section

Figure 15.2

Solid Pack Chimney with Metal Supports as a Thimble 

(Cont’d)

Flue Gas

Direction

Crimped

End

Toward

Appliance

Secure pipe sections with a

minimum of 3 screws

Figure 15.3   Chimney 

Connector  (Appliance Pipe)

G. Installing Chimney Components

Chimney Connector

Single wall connector or appliance pipe.  

This must be at least 24 gauge mild steel or 26 gauge blue 

steel.  The sections must be attached to the appliance and 

to each other with the crimped (male) end pointing toward 

the appliance.  All joints, including the connection at the flue 

collar, should be secured with 3 sheet metal screws.  Make 

sure to follow the minimum clearances to combustibles.   

Where passage through the wall, or partition of combustible 

construction is desired in Canada, the installation shall 

conform to CAN/CSA-B365.

Factory-built listed chimney connector (vented).

A listed connector (vented) must be used when installing 

this appliance in a mobile home.  The listed connectors 

must conform to each other to ensure a proper fit and seal.

WARNING

Fire Risk.

Follow Chimney Connector Manufacturer’s 

Instructions for Proper Installation.

ONLY use connector:

• 

Within the room, between appliance and ceiling or 

wall.

Connector shall NOT pass through:

•  Attic or roof space

•  Closet or similar concealed space

•  Floor or ceiling

Maintain minimum clearances to combustibles

NOTE:

 Optional Fire Screen, Part SCR-7061, can only 

be used in FULL Vertical installations.

H. Proper Draft

To be sure that your Quadra-Fire insert burns properly, the 

chimney draft (static pressure) should be approximately 

-0.10 inches water column (W.C.) during a high burn and 

-0.04 inches W.C. during a low burn, measured 6 inches 

(152mm) above the top of the insert after one hour of 

operation at each burn setting.

Summary of Contents for Explorer II series

Page 1: ...revendeur ou visitez www quadrafire com If the information in these instructions is not followed exactly a fire could result causing property damage personal injury or death WARNING Do not store or us...

Page 2: ...Chimney Termination Requirements 12 C 2 10 3 Rule 12 D Chimney Height Rise and Run 13 E Venting Components 13 F Chimney Systems 13 G Installing Chimney Components 15 H Proper Draft 15 5 Appliance Set...

Page 3: ...from the low and high EPA tests using Douglas Fir dimensional lumber A peak BTU out of the appliance calculated using the maximum first hour burn rate from the High EPA Test and the BTU content of cor...

Page 4: ...affle and other interior components NOTE Hearth Home Technologies manufacturer of this appliance reserves the right to alter its products their specifications and or price without notice Improper inst...

Page 5: ...chimney heights Ideal performance is with height of chimney between 14 16 feet 4 26 4 88m measured from the base of the appliance C Negative Pressure Negative pressure results from the imbalance of ai...

Page 6: ...ling winds during the heating season Ensure adequate outdoor air for all combustion appliances and exhaust equipment Ensure furnace and air conditioning return vents are not located in the immediate v...

Page 7: ...he party responsible for use and operation Hearth Home Technologies recommends the following Photographing the installation and copying this checklist for your file That this checklist remain visible...

Page 8: ...t View Figure 8 3 Side View 12 1 4 514MM 27 686mm 29 737mm 20 508mm 29 737mm Figure 8 2 Top View 13 3 8 340mm 7 8 22mm 2 3 8 60mm 25 7 8 657mm 3 8 9mm 29 737mm Figure 8 4 Side View with horizontal flu...

Page 9: ...he appliance See exception WARNING Fire Risk Hearth pads must be installed exactly as specified High temperatures or hot embers may ignite concealed combustibles Corner hearth pad dimensions with sing...

Page 10: ...4 1175 6 1 2 165 N A N A 55 1397 N A For alcove only Six inch diameter listed Double wall air insulated connector pipe with UL103 HT listed factory built Class A chimney or masonry chimney Maximum dep...

Page 11: ...space enclosed by the building envelope This helps to produce more draft especially during lighting and die down of the fire Penetrate the highest part of the roof This minimizes the affects of wind...

Page 12: ...or when there are other factors that affect flue draft B Chimney Termination Requirements Follow manufacturer s instructions for clearance securing flashing and terminating the chimney Figure 12 1 12...

Page 13: ...Listed Chimney Storm Collar Wall Support Roof Brace if required Thimble Figure 13 1 Prefabricated Exterior Chimney E Venting Components Chimney Connector It is also known as flue pipe or appliance pip...

Page 14: ...ey Figure 14 2 2 Entry hole to masonry chimney must be lined with an 8 inch 203mm minimum diameter clay liner or equivalent secured with refractory mortar 3 Construct a 17 inch x 17 inch 432mm x 432mm...

Page 15: ...is must be at least 24 gauge mild steel or 26 gauge blue steel The sections must be attached to the appliance and to each other with the crimped male end pointing toward the appliance All joints inclu...

Page 16: ...materials from packing box 2 Floor Rear Installation Cut a 4 inch 102mm hole in outside wall or floor to accommodate outside air piping Use 4 inch 102mm aluminum metal flex or rigid piping to directly...

Page 17: ...agnet under the bottom left rear corner See Owner s Manual for detailed operating instructions for the blower and snap disc Figure 17 1 Shock Risk Do NOT remove grounding prong from plug Route cord aw...

Page 18: ...op or rear venting installation The appliance is shipped with the flue collar in the top vent position Converting Collar For Rear Vent Installation and Installing Required Horizontal Flue Shield 1 Rem...

Page 19: ...ion requirements must be followed precisely 9 Use silicone to create an effective vapor barrier at the location where the chimney or other component penetrates to the exterior of the structure NOTE Of...

Page 20: ...20 7061 197P August 13 2018 Explorer II Date of Service Performed By Description of Service 7 Reference Materials A Service Maintenance Log...

Page 21: ...it Floor Rear OAK ACC Outside Air Collar Assembly 7033 039 Outside Air Shield 33271 Y Firescreen SCR 7061 FASTENERS Avk Rivnut Repair Kit 1 4 20 3 8 16 Rivnut Tools RIVNUT REPAIR Y Nut Ser Flange Smal...

Page 22: ...purchased installed _________________________________________________________________________ Serial Number ____________________________________ Location on appliance ___________________________ Deal...

Reviews: