background image

 16 

      7061-197P 

   

August 

13, 

2018

Explorer II

Appliance Set-Up

A. Outside Air Kit Installation 

A source of air (oxygen) is necessary in order for 

combustion to take place.  Whatever combustion air is 

consumed by the fire must be replaced.  Air is replaced via 

air leakage around windows and under doors. In homes 

that have tightly sealed doors and windows, an outside air 

source is needed. An optional Outside Air Kit is available. 

Optional OAK-ACC includes: 

Termination cap, (2) wire ties, flex adapter, and fasteners

Items Needed for Installation (not supplied)

• 

4 inch flex aluminum pipe, or if using alternate material, 

then it shall be made from durable, non-combustible, 

heat resistant material up to 350oF.  Cut the pipe to the 

required length for your installation. 

•  Phillips head screw driver 

•  Silicone sealant

•  Drills and saws necessary for cutting holes through the 

wall or flooring in your home.

Installation Instructions

1.  Remove all materials from packing box.

2.  Floor & Rear Installation:

  Cut a 4 inch (102mm) hole 

in outside wall or floor to accommodate outside air 

piping.  Use 4 inch (102mm) aluminum metal flex or 

rigid piping to directly connect outside air to appliance 

intake.  Use the supplied termination cap with a rodent 

screen.  Seal between the wall (or floor) and the pipe 

with silicone to prevent moisture penetration. 

Fire Risk.

Asphyxiation Risk.

Do not draw outside combustion air from:

• 

Wall, floor or ceiling cavity

•  Enclosed space such as an attic or garage

•  Close proximity to exhaust vents or chimneys

Fumes or odor may result

WARNING

Asphyxiation Risk.

Outside air inlet must be located to prevent 

blockage from:

•  Leaves

•  Snow or ice

•  Other debris

Block may cause combustion air starvation

Smoke spillage may set off alarms or irritate 

sensitive individuals.

WARNING

Asphyxiation Risk.

Length of outside air supply duct shall NOT 

exceed the length of the vertical height of the 

exhaust flue.

•  Fire will not burn properly

•  Smoke spillage occurs when door is opened 

due to air starvation.

WARNING

Figure 16.2 - Floor Installation

Figure 16.1 - Rear Installation

Summary of Contents for Explorer II series

Page 1: ...revendeur ou visitez www quadrafire com If the information in these instructions is not followed exactly a fire could result causing property damage personal injury or death WARNING Do not store or us...

Page 2: ...Chimney Termination Requirements 12 C 2 10 3 Rule 12 D Chimney Height Rise and Run 13 E Venting Components 13 F Chimney Systems 13 G Installing Chimney Components 15 H Proper Draft 15 5 Appliance Set...

Page 3: ...from the low and high EPA tests using Douglas Fir dimensional lumber A peak BTU out of the appliance calculated using the maximum first hour burn rate from the High EPA Test and the BTU content of cor...

Page 4: ...affle and other interior components NOTE Hearth Home Technologies manufacturer of this appliance reserves the right to alter its products their specifications and or price without notice Improper inst...

Page 5: ...chimney heights Ideal performance is with height of chimney between 14 16 feet 4 26 4 88m measured from the base of the appliance C Negative Pressure Negative pressure results from the imbalance of ai...

Page 6: ...ling winds during the heating season Ensure adequate outdoor air for all combustion appliances and exhaust equipment Ensure furnace and air conditioning return vents are not located in the immediate v...

Page 7: ...he party responsible for use and operation Hearth Home Technologies recommends the following Photographing the installation and copying this checklist for your file That this checklist remain visible...

Page 8: ...t View Figure 8 3 Side View 12 1 4 514MM 27 686mm 29 737mm 20 508mm 29 737mm Figure 8 2 Top View 13 3 8 340mm 7 8 22mm 2 3 8 60mm 25 7 8 657mm 3 8 9mm 29 737mm Figure 8 4 Side View with horizontal flu...

Page 9: ...he appliance See exception WARNING Fire Risk Hearth pads must be installed exactly as specified High temperatures or hot embers may ignite concealed combustibles Corner hearth pad dimensions with sing...

Page 10: ...4 1175 6 1 2 165 N A N A 55 1397 N A For alcove only Six inch diameter listed Double wall air insulated connector pipe with UL103 HT listed factory built Class A chimney or masonry chimney Maximum dep...

Page 11: ...space enclosed by the building envelope This helps to produce more draft especially during lighting and die down of the fire Penetrate the highest part of the roof This minimizes the affects of wind...

Page 12: ...or when there are other factors that affect flue draft B Chimney Termination Requirements Follow manufacturer s instructions for clearance securing flashing and terminating the chimney Figure 12 1 12...

Page 13: ...Listed Chimney Storm Collar Wall Support Roof Brace if required Thimble Figure 13 1 Prefabricated Exterior Chimney E Venting Components Chimney Connector It is also known as flue pipe or appliance pip...

Page 14: ...ey Figure 14 2 2 Entry hole to masonry chimney must be lined with an 8 inch 203mm minimum diameter clay liner or equivalent secured with refractory mortar 3 Construct a 17 inch x 17 inch 432mm x 432mm...

Page 15: ...is must be at least 24 gauge mild steel or 26 gauge blue steel The sections must be attached to the appliance and to each other with the crimped male end pointing toward the appliance All joints inclu...

Page 16: ...materials from packing box 2 Floor Rear Installation Cut a 4 inch 102mm hole in outside wall or floor to accommodate outside air piping Use 4 inch 102mm aluminum metal flex or rigid piping to directly...

Page 17: ...agnet under the bottom left rear corner See Owner s Manual for detailed operating instructions for the blower and snap disc Figure 17 1 Shock Risk Do NOT remove grounding prong from plug Route cord aw...

Page 18: ...op or rear venting installation The appliance is shipped with the flue collar in the top vent position Converting Collar For Rear Vent Installation and Installing Required Horizontal Flue Shield 1 Rem...

Page 19: ...ion requirements must be followed precisely 9 Use silicone to create an effective vapor barrier at the location where the chimney or other component penetrates to the exterior of the structure NOTE Of...

Page 20: ...20 7061 197P August 13 2018 Explorer II Date of Service Performed By Description of Service 7 Reference Materials A Service Maintenance Log...

Page 21: ...it Floor Rear OAK ACC Outside Air Collar Assembly 7033 039 Outside Air Shield 33271 Y Firescreen SCR 7061 FASTENERS Avk Rivnut Repair Kit 1 4 20 3 8 16 Rivnut Tools RIVNUT REPAIR Y Nut Ser Flange Smal...

Page 22: ...purchased installed _________________________________________________________________________ Serial Number ____________________________________ Location on appliance ___________________________ Deal...

Reviews: