16. Thermostat
The appliance is designed to run on a 12 volt AC
thermostat. The heat anticipator should be set on the
lowest setting available.
17.
Snap Disc #1 (Convection Blower) 145°F
Snap disc #1 is located on the right side of the
appliance on the top of the heat exchanger box. There
are 2 purple wires connected to it. This snap disc turns
the convection blower on and off as needed. Power is
always present at snap disc #1.
18.
Snap Disc #2 (Thermostat Override) 200°F
Snap disc #2 is also located on the right side of the
appliance between snap disc #1 and convection
blower. There are 2 yellow wires connected to it. This
snap disc will turn off the feed system, which will turn
off the appliance if an over fire condition should occur
or if the convection blower should fail to operate.
19.
Snap Disc #3 (Back Burn Protector) 250°F
Snap disc #3 is mounted on the side of the auger tube
just below the feed motor and has a red reset button.
To access it remove the feed motor cover box from
inside the hopper. If the fire tries to burn back into the
feed system or push exhaust up the feed tube, this
snap disc will shut the entire system off. This disc must
be manually reset.
20. Vacuum Switch
The vacuum switch is located on the left side of the
appliance behind the inner shield. This switch turns the
feed system on when vacuum is present in the firebox.
The vacuum switch is a safety device to shut off the
feed motor if the exhaust or the heat exchanger system
is dirty or plugged or if the firebox door is open.
21. Wiring Harness
See
Figure 31.1
below.
Figure 31.1