background image

 14 

 

 

 

 

                       7014-258B 

 

 

 

     November 30, 2017

CB1200 FREESTANDING

B. Avoiding Smoke and Odors

Negative Pressure, Shut-Down and Electrical Power 

Failure

To reduce the probability of back-drafting or burn-back in 

the pellet appliance during power failure or shut down con-

ditions, it must be able to draft naturally without exhaust 

blower operation.  
Negative pressure in the house will resist this natural draft if 

not accounted for in the pellet appliance installation.

Heat rises in the house and leaks out at upper levels.  This 

air must be replaced with cold air from outdoors which flows 

into lower levels of the house.  
Vents and chimneys into basements and lower levels of the 

house can become the conduit for air supply and reverse 

under these conditions.

Outside Air

An outside air kit is recommended in all installations.  The 

Outside Air Kit must be ordered separately.
Per national building codes, consideration must be given to 

combustion air supply to all combustion appliances.  Failure 

to supply adequate combustion air for all appliance demands 

may lead to back drafting of those and other appliances.  

When the appliance is roof vented (strongly recommended):

  

The air intake is best located on the exterior wall oriented 

towards the prevailing wind direction during the heating 

season.

When the appliance is side-wall vented: 

The air intake is best located on the same exterior wall as 

the exhaust vent outlet and located lower on the wall than 

the exhaust vent outlet.

The outside air supply kit can supply most of the demands of 

the pellet appliance, but consideration must be given to the 

total house demand.  

House demand may consume the air needed for the appli

-

ance.  It may be necessary to add additional ventilation to 

the space in which the pellet appliance is located.  

Consult with your local HVAC professional to determine the 

ventilation demands for your house.

Vent Configurations

When installing a pellet appliance with a horizontal vent con-

figuration the frequency of power outages should be consid

-

ered:

• 

Power outages during operation will cause the appliance 

to immediately turn off and may create conditions where 

smoke will back draft into the house. In order to reduce 

the likelihood of smoke back drafting into the house 

during a power outage, Hearth and Home Technologies 

strongly suggests:

• 

Installing the pellet venting with a minimum vertical 

run of 5 feet (1.52m).

• 

Installing the outside air kit at least 4 feet (1.22m) 

below the vent termination.

To prevent soot damage to exterior walls of the house and to 

prevent re-entry of soot or ash into the house:

  •   Maintain  specified  clearances  to  windows,  doors  and 

air inlets, including air conditioners.

  •   Vents  should  not  be  placed  below  ventilated  soffits.  

Run the vent above the roof.

  •   Avoid venting into alcove locations.
  •   Vents should not terminate under overhangs, decks or 

onto covered porches.

  •   Maintain  minimum  clearance  of  12  inches  (305mm) 

from  the  vent  termination  to  the  exterior  wall.    If  you 

see deposits developing on the wall, you may need to 

extend this distance to accommodate your installation 

conditions.

CAUTION

•  DO NOT CONNECT THIS Appliance TO A CHIMNEY FLUE 

SERVICING ANOTHER APPLIANCE.

•  DO NOT CONNECT TO ANY AIR DISTRIBUTION DUCT 

OR SYSTEM.

Summary of Contents for CB1200M-MBK

Page 1: ...allow children to touch glass Keep children away CAREFULLY SUPERVISE children in same room as fireplace Alert children and adults to hazards of high temperatures High temperatures may ignite clothing...

Page 2: ...4 B Thermostat Wall Control Location 5 C Tools And Supplies Needed 5 D Inspect Appliance and Components 5 E Install Checklist 6 3 Dimensions and Clearances 7 A Appliance Dimensions 7 B Clearances to...

Page 3: ...without legs attached if supplied with appliance Do NOT Over fire If appliance or chimney connector glows you are over firing Any such action that may cause a fire hazard WARNING Fire Risk Hearth Hom...

Page 4: ...the installation Location of the appliance and chimney will affect performance Consideration must be given to Safety convenience traffic flow Placement of the chimney and chimney connector and to mini...

Page 5: ...s location will have some affect on the appliance s operation Maximum wire length from appliance is 100 feet 30 48m continuous non spliced wire Recommended 20 gauge wire solid copper When located clo...

Page 6: ...ation and copying this checklist for your file That this checklist remain visible at all times on the appliance until the installation is complete Electrical 120 VAC unswitched power provided to the a...

Page 7: ...ESTANDING Figure 7 1 Top View Figure 7 2 Side View Figure 7 3 Front View 6 1 4 159 8 203 8 203 25 3 4 654 27 5 8 702 8 204 25 3 4 654 28 1 2 724 31 5 8 803 28 1 2 725 21 1 4 539 10 3 8 264 3 Dimension...

Page 8: ...62 33 1 8 841 31 1 4 795 Figure 8 1 Top View with Top Vent Adapter TPVNT 1 and Offset Adapter 812 3570 Figure 8 2 Side View with Top Vent Adapter TPVNT 1 and Offset Adapter 812 3570 Figure 8 3 Top Vie...

Page 9: ...REESTANDING 2 3 8 62 2 3 4 69 3 7 8 100 6 1 4 159 8 203 8 203 15 51 8 398 14 357 Figure 9 1 Top View with Top Vent Adapter TPVNT 6 and Offset Adapter 811 0720 Figure 9 2 Side View with Top Vent Adapte...

Page 10: ...ack Wall to Appliance 7 5 191 Corner Installation Inches Millimeters G Side Wall to Flue Pipe 2 51 Installations with TPVNT 1 Top Vent Adapter with Heat Shield and Clean out TPVNT 6 Top Vent Adapter w...

Page 11: ...pipe shaded area to the wall thimble CANADA 47 3 4 in 26 1 4 in 21 1 2 in 41 3 8 in 6 in from the fuel door opening USA 1214mm 666mm 545mm 1051mm 152mm front door opening CANADA Must extend 51mm beyo...

Page 12: ...strations diagrams are not drawn to scale Actual installation may vary due to individual design preference D Alcove Figure 12 1 All minimums listed are to a combustible surface Figure 12 2 Minimum Max...

Page 13: ...lk paved driveway located on public property M 12 in Under an open veranda porch deck or balcony N See Note below Electric service above below or to the side location must not obstruct or interfere wi...

Page 14: ...t of the demands of the pellet appliance but consideration must be given to the total house demand House demand may consume the air needed for the appli ance It may be necessary to add additional vent...

Page 15: ...mm diameter type L or PL venting system It can be vented vertically or horizontally 2 Mobile Home Approved for all Listed pellet vent If using the 3 inch 76mm vertical Top Vent Adapter Kit or the 3 to...

Page 16: ...F FEET 0 20 30 1 2 3 4 5 6 7 8 9 10 4 in 102mm Diameter Pipe Only 10 Example 1 Example 2 Example 1 If the equivalent length of pipe is 23 feet 7m with altitude of 8 000 feet 2438m you must use 4 inch...

Page 17: ...d for mobile home installa tions Must use 3 or 4 inch 76 102mm L or PL Listed pellet venting or Listed double wall pipe and a Quadra Fire Outside Air Kit in mobile homes NOTE In Canada where passage t...

Page 18: ...g Rain Cap 6 in 152mm Min Non combustible Hearth Pad 3 in 76mm Min 24 in 610mm Minimum 3 in to 3 in 76 76mm Top Vent Kit Clean out Cover All three installations are approved for mobile home installa t...

Page 19: ...pace Concrete Cap 1 in 25mm Clearance with Firestop 6 in 152mm Minimum Non Combustible Hearth Pad Sheathing 2 in 51mm Minimum 1 in 25mm Clearance Flashing Fireclay Flue Liner withAirspace Concrete Cap...

Page 20: ...utside termination cap with second hose clamp e Secure termination cap to outside surface f Secure trim ring to interior wall g Snip corners and remove plate Figure 20 1 h Align and secure collar asse...

Page 21: ...ppliance using the outer shield as a pattern make sure the assembly is vertical Figure 21 1 4 Install the 4 mounting screws 5 Install the vent pipe into the top vent adapter be sure to silicone all jo...

Page 22: ...2 studs into the already drilled holes See Figure 22 4 Figure 22 3 F Thermostat Installation and Operation There is a 4 screw terminal block located on the back lower left corner of the stove directly...

Page 23: ...REPLACE BATTERY warning begins flashing The warning flashes about two months before the batteries are depleted Even if the warning does not appear you should replace batteries once a year If batteries...

Page 24: ...CFR 3280 Part 24 NEVER INSTALL IN A SLEEPING ROOM WARNING Spark Arestor Cap Roof Flashing Storm Collar Joist Shield Firestop Double Wall Connector Pipe Figure 24 1 CAUTION Never draw outside combustio...

Page 25: ...November 30 2017 7014 258B 25 CB1200 FREESTANDING 8 Accessory List A Service Maintenance Log Date of Service Performed By Description of Service...

Page 26: ...26 7014 258B November 30 2017 CB1200 FREESTANDING Date of Service Performed By Description of Service...

Page 27: ...er Outside Air Kit Floor 411 1071 Hose Alum Flex 2 Inch x 3 Ft Qty 3 Ft Req SRV200 0860 Outside Air Cap Assembly 7001 044 Outside Air Collar Assembly SRV7001 045 Trim Plate Outside Air Kit 412 7100 Sm...

Page 28: ...e purchased installed _________________________________________________________________________ Serial Number ____________________________________ Location on appliance ___________________________ Dea...

Reviews: