background image

November 30, 2017 

 

 

 

 

7014-258B 

 

 

 

         

                  13

CB1200 FREESTANDING

Vent Information

A. Venting Termination Minimum Requirements

J or K

X

V

M

I

H

A

V

G

B

V

V

A

B

V

F V

C

B

B

E

L

V

D

V

Electrical

Service

V

N

V

N

V

N

N

V

Inside Corner

FIXED 

CLOSED

OPEN

OPEN

FIXED 

CLOSED

V

X

G

G

Termination Cap

Air Supply Inlet

Gas Meter

Restricted Area

O

P

Figure 13.1

A

12 in.

Above Finish Grade (the grade surface 

must be a non-combustible material

B

12 in.

48 in. no OAK

Open door or window: below or to the side

B

12 in.

Open door or window: above

C

6 in.

Permanently closed window: above, below 

or to the side

D

18 in.

36 in. no OAK

Vertical clearance to a ventilated soffit 

located above the terminal within a hori-

zontal distance of 2 ft from the center-line 

of the terminal 

E

12 in.

Clearance to unventilated soffit

F

12 in.

Clearance to outside corner

G

12 in.

Clearance to inside corner

H

36 in.

Above gas meter/regulator measured from 

horizontal center-line of regulator

I

36 in. USA

72 in. Canada

Clearance to service regulator vent outlet

J

12 in.

48 in. no OAK

Clearance to non-mechanical air supply 

inlet to the building or the combustions air 

inlet to any other appliance

K

10 ft horizontal

3 ft vertical

Clearance to mechanical air supply

L

7 ft.

Above paved sidewalk, paved driveway 

located on 

public

 property

M

12 in.

Under an open veranda, porch, deck or 

balcony

N

See Note 

below*

Electric service: above, below or to the 

side (location must not obstruct or interfere 

with access)

O

24 in.

Adjacent building, fences and protruding 

parts of the structure

P

12 in.

Clearance above roof line for vertical 

terminations

All minimum clearances are listed with an Outside Air Kit (OAK) installed, unless otherwise noted in table below.

24 in.

Above grass, top of plants, wood or any other com-

bustible

12 in.

36 in. no OAK

Clearance from any forced air intake of other appli-

ance

12 in.

Clearance horizontally from combustible wall

15 in.

Vented directly through a wall, minimum length of 

horizontal pipe

6 in. horizontal

12 in. vertical

Minimum horizontal or vertical terminations must 

protrude from wall

*NOTE: 

 Consult local building, fire officials or authorities having jurisdic

-

tion.  Local codes or regulations may require different clearances.

NOTICE:

Do NOT Terminate Vent:
• 

In any location that will allow flue gases or soot from en

-

tering  or staining the building

•  In any location which could create a nuisance or hazard

• 

In any enclosed or semi-enclosed area such as a carport, 

garage, attic, crawl space, under a sun deck or porch, 

narrow walkway 

•  Closely fenced area, or any location that can build up 

a concentration of fumes such as a stairwell, covered 

breezeway, etc.

NOTICE:

Termination must exhaust above air inlet elevation.  

Summary of Contents for CB1200M-MBK

Page 1: ...allow children to touch glass Keep children away CAREFULLY SUPERVISE children in same room as fireplace Alert children and adults to hazards of high temperatures High temperatures may ignite clothing...

Page 2: ...4 B Thermostat Wall Control Location 5 C Tools And Supplies Needed 5 D Inspect Appliance and Components 5 E Install Checklist 6 3 Dimensions and Clearances 7 A Appliance Dimensions 7 B Clearances to...

Page 3: ...without legs attached if supplied with appliance Do NOT Over fire If appliance or chimney connector glows you are over firing Any such action that may cause a fire hazard WARNING Fire Risk Hearth Hom...

Page 4: ...the installation Location of the appliance and chimney will affect performance Consideration must be given to Safety convenience traffic flow Placement of the chimney and chimney connector and to mini...

Page 5: ...s location will have some affect on the appliance s operation Maximum wire length from appliance is 100 feet 30 48m continuous non spliced wire Recommended 20 gauge wire solid copper When located clo...

Page 6: ...ation and copying this checklist for your file That this checklist remain visible at all times on the appliance until the installation is complete Electrical 120 VAC unswitched power provided to the a...

Page 7: ...ESTANDING Figure 7 1 Top View Figure 7 2 Side View Figure 7 3 Front View 6 1 4 159 8 203 8 203 25 3 4 654 27 5 8 702 8 204 25 3 4 654 28 1 2 724 31 5 8 803 28 1 2 725 21 1 4 539 10 3 8 264 3 Dimension...

Page 8: ...62 33 1 8 841 31 1 4 795 Figure 8 1 Top View with Top Vent Adapter TPVNT 1 and Offset Adapter 812 3570 Figure 8 2 Side View with Top Vent Adapter TPVNT 1 and Offset Adapter 812 3570 Figure 8 3 Top Vie...

Page 9: ...REESTANDING 2 3 8 62 2 3 4 69 3 7 8 100 6 1 4 159 8 203 8 203 15 51 8 398 14 357 Figure 9 1 Top View with Top Vent Adapter TPVNT 6 and Offset Adapter 811 0720 Figure 9 2 Side View with Top Vent Adapte...

Page 10: ...ack Wall to Appliance 7 5 191 Corner Installation Inches Millimeters G Side Wall to Flue Pipe 2 51 Installations with TPVNT 1 Top Vent Adapter with Heat Shield and Clean out TPVNT 6 Top Vent Adapter w...

Page 11: ...pipe shaded area to the wall thimble CANADA 47 3 4 in 26 1 4 in 21 1 2 in 41 3 8 in 6 in from the fuel door opening USA 1214mm 666mm 545mm 1051mm 152mm front door opening CANADA Must extend 51mm beyo...

Page 12: ...strations diagrams are not drawn to scale Actual installation may vary due to individual design preference D Alcove Figure 12 1 All minimums listed are to a combustible surface Figure 12 2 Minimum Max...

Page 13: ...lk paved driveway located on public property M 12 in Under an open veranda porch deck or balcony N See Note below Electric service above below or to the side location must not obstruct or interfere wi...

Page 14: ...t of the demands of the pellet appliance but consideration must be given to the total house demand House demand may consume the air needed for the appli ance It may be necessary to add additional vent...

Page 15: ...mm diameter type L or PL venting system It can be vented vertically or horizontally 2 Mobile Home Approved for all Listed pellet vent If using the 3 inch 76mm vertical Top Vent Adapter Kit or the 3 to...

Page 16: ...F FEET 0 20 30 1 2 3 4 5 6 7 8 9 10 4 in 102mm Diameter Pipe Only 10 Example 1 Example 2 Example 1 If the equivalent length of pipe is 23 feet 7m with altitude of 8 000 feet 2438m you must use 4 inch...

Page 17: ...d for mobile home installa tions Must use 3 or 4 inch 76 102mm L or PL Listed pellet venting or Listed double wall pipe and a Quadra Fire Outside Air Kit in mobile homes NOTE In Canada where passage t...

Page 18: ...g Rain Cap 6 in 152mm Min Non combustible Hearth Pad 3 in 76mm Min 24 in 610mm Minimum 3 in to 3 in 76 76mm Top Vent Kit Clean out Cover All three installations are approved for mobile home installa t...

Page 19: ...pace Concrete Cap 1 in 25mm Clearance with Firestop 6 in 152mm Minimum Non Combustible Hearth Pad Sheathing 2 in 51mm Minimum 1 in 25mm Clearance Flashing Fireclay Flue Liner withAirspace Concrete Cap...

Page 20: ...utside termination cap with second hose clamp e Secure termination cap to outside surface f Secure trim ring to interior wall g Snip corners and remove plate Figure 20 1 h Align and secure collar asse...

Page 21: ...ppliance using the outer shield as a pattern make sure the assembly is vertical Figure 21 1 4 Install the 4 mounting screws 5 Install the vent pipe into the top vent adapter be sure to silicone all jo...

Page 22: ...2 studs into the already drilled holes See Figure 22 4 Figure 22 3 F Thermostat Installation and Operation There is a 4 screw terminal block located on the back lower left corner of the stove directly...

Page 23: ...REPLACE BATTERY warning begins flashing The warning flashes about two months before the batteries are depleted Even if the warning does not appear you should replace batteries once a year If batteries...

Page 24: ...CFR 3280 Part 24 NEVER INSTALL IN A SLEEPING ROOM WARNING Spark Arestor Cap Roof Flashing Storm Collar Joist Shield Firestop Double Wall Connector Pipe Figure 24 1 CAUTION Never draw outside combustio...

Page 25: ...November 30 2017 7014 258B 25 CB1200 FREESTANDING 8 Accessory List A Service Maintenance Log Date of Service Performed By Description of Service...

Page 26: ...26 7014 258B November 30 2017 CB1200 FREESTANDING Date of Service Performed By Description of Service...

Page 27: ...er Outside Air Kit Floor 411 1071 Hose Alum Flex 2 Inch x 3 Ft Qty 3 Ft Req SRV200 0860 Outside Air Cap Assembly 7001 044 Outside Air Collar Assembly SRV7001 045 Trim Plate Outside Air Kit 412 7100 Sm...

Page 28: ...e purchased installed _________________________________________________________________________ Serial Number ____________________________________ Location on appliance ___________________________ Dea...

Reviews: