Qualified Person Only!
Damage to the INVERTER due to the use of cleaning agents. If the INVERTER
is dirty, clean the enclosure, the enclosure lid, the type label and the LEDs using
only clean water and a cloth.
CAUTION
Do not disassemble the parts in operation for cleaning purposes.
High voltage can cause lethal damage to the human body.
1. Please make sure that the AC and DC switch relay in the distribution box is
disconnected.
2. Open the bottom cover of the Battery pack, and then turn off the circuit
breaker to cut off the Battery DC.
3. Disassembling the system.
6.2.1 Fuse Check
•
Check the fuse when the device fails to work with significant error.
•
Do not perform Fuse Check when the device is working.
•
Check the fuse after turning off the DC disconnect switch and the AC circuit breaker.
•
Measure both ends of the Filter PBA F101, F102, and F401 check the resistance value.
•
If the resistance value is open state (Mega ohms or Infinite value), perform PBA exchange.
Ensure that the INVERTER is free of dust, foliage and other dirt.
25
I
Maintenance for Problem Solving
6. Maintenance for Problem Solving