Copyright Pyroban Ltd. Issue 1 Page 22 of 32
Part number PM1083ENG
16. Check for leaks by opening then closing the
bottle valve, taking note of the reading on the
gauge. Wait 10 minutes then check that the
pressure has not decreased.
17. Reconnect the battery to the vehicle in accordance with the manufacturer’s instructions.
18. Place the blue or green operator’s key on the Dallas Key receptacle on the Control Unit.
Check that Gascheka duo starts up satisfactorily (Refer to Operating Instructions earlier in
this manual). Close the valve on the bottle. Disconnect the test gas pipe from the Gas
Sensing Head.
19. Place plastic bag (bag that contains labels can be used) over the Gas Sensing Head.
20. Insert the test gas pipe into the
plastic bag. Secure/seal the plastic
bag and test gas pipe with
electricians tape. Fill the plastic
bag with test gas from the test gas
cylinder. Confirm that shutdown
occurs.
21. Remove the plastic bag; reinstall
the test gas pipe to the Gas
Sensing Head.
22. Check the operation of the red ‘supervisors’ key following gas shut down. (Refer to the
Operating Instructions).
23. The Gascheka duo system is now ready for operation.
24. Peel the protective backing off the two Pyroban
Gascheka duo labels and stick one to each side of
the vehicle.