PureAire Monitoring Systems, Inc.
50
7.0 Appendix
Remote Display Alarm Indicator
The Remote Display Alarm Indicator is designed to display remote concentration
information from PureAire monitors. All PureAire monitors have a built in 4-
20mA output. The remote display alarm easily connects to the monitor’s input
power and mA output connection. An 18 AWG, three conductor, shielded control
and instrumentation cable, Belden 8770 or equivalent is recommended for the
connection. The maximum permissible cable length is 250 feet. You can
simultaneously connect one remote display to one PureAire monitor and one
programmable logic controller, PLC.