PureAire Monitoring Systems, Inc.
55
To set Alarm 2, Press the Alarm 2 button for two seconds to enter the alarm change mode. The display
will show the current alarm setting and the left most decimal point will be lit. Use the UP or DOWN
buttons to increase or decrease the alarm value. When done, push the Alarm 2 button for 2 seconds to
get back to the monitoring mode.
How to connect a Horn and Strobe to the monitor
+ + - - - -
45101 Power supply
115 VAC / 24 VDC 1 amp
Regulated power supply
NC Common NO
Common
Main Power Board
Alarm 2
Alarm 1
Fault
Relay Board
Federal Signal
Horn & Strobe
42002
*
This drawing shows how to connect a remote Horn
and strobe to PureAire’s Universal Gas Detector with
the Alarm relay #1 set to a Normally Open position.
*
Note: Federal Signal Horn/Strobe or equivalent
18 AWG, two conductor,
stranded
control and
instrumentation cable,
Belden 8461 or equivalent
+24VDC