Totalisers
P798 Max Flow Cut Off (From Soft Revision 6.4.2 (6.7.3 released))
This parameter can be set to inhibit the flow totalisers to a maximum value of
4 times the maximum flow rate
. So for example with a max flow of 20 l/s, set in
the P705, the totaliser will be stop totalling the flow when it reaches 80 l/s or
higher.
Options: Min = 1
Max = 9
Display
P817 Auxiliary Display Offset (From Soft Rev 6.5 (6.7.3 released))
This parameter will allow the Auxiliary display to be offset to an appropriate value
in system units. It can be used to ensure a more operator friendly reading is seen in
the auxiliary display.
Values: Min. 99999m
Max. 99999m
Default = 4
Default = 0m