Pump Control
P194 – P199 Pumping Rate
This parameter is a simulation parameter in units of metres/min that sets the rate
of pumping for any pump assigned the appropriate relay whilst in test mode.
P359 Maximum Pumps (From Software Version 6.3 to 6.4.5
This parameter will restrict the number of pumps that will run regardless of the
number of pumps set in the unit and the level shown on the display. This can be
used to ensure if a rising main can only take so much flow the limit is not
accidentally exceeded.
P361 – P362 Max Pumps on (groups 1 & 2) (From S/W ver. 6.7.3)
This parameter will restrict the number of pumps that will run regardless of the
number of pumps set in the unit and the level shown on the display. This can be
used to ensure that if a rising main can only take a certain amount of flow, the
limit is not accidentally exceeded.
Default = 1.0
Default = 0
Default = 0