Comms / Logging Board
Only available if Comms is enabled (Profibus or modbus).
P141 Serial to Comms Board
To allow RS232 communication with the integrated comms processor. This must
be set remotely via Ultra PC or Windows Terminal. The parameter will
automatically revert back to 0 = No when the RJ11 cable has been removed and
“updating” has been displayed on the LCD.
Options: 0 = No
1 = Yes
P142 Reset Comms Board
Options: 0 = No
1 = Yes
P358 Log Time
The unit has 10 daily totals that start and end at midnight. This parameter can be
used to alter the start time at which logging begins for the 24 hour period.
Default = 0
Default = 0
Default = 0000 (00:00)