Page26
mA Output (LOOP) Menu
P834 mA Low Level
This parameter sets, in
Measurement Units (P104)
, the value of ‘level’,
‘distance’ or ‘space’, depending on the selected
Mode of Operation (P100)
,
at which 4mA will occur.
P835 mA High Level
This parameter sets, in
Measurement Units (P104)
, the value of ‘level’,
‘distance’ or ‘space’, depending on the selected
Mode of Operation (P100
),
at which 20 mA output will occur
.
P838 mA Low Trim
If the device you are connected to is not calibrated, and not showing the low
value, then you can trim it using this parameter. You can either type in the
offset directly or use the arrow keys to move the output up and down until
you get the expected result on the device that is connected.
P839 mA High Trim
If the device you are connected to is not calibrated, and not showing the high
value, then you can trim it using this parameter. You can either type in the
offset directly or use the arrow keys to move the output up and down until you
get the expected result on the device that is connected.
P840 mA Fail-safe Mode
This parameter determines what happens to the mA output in the event of the
unit going into fail-safe mode. The
default
is to do the same as the
system
fail-safe
(
P808
), but this can be overridden to force the mA output to an
independent fail-safe mode as follows:
Option
Description
0 = Default
mA output will fail as per
P808
.
1 = Hold
mA output will retain its last known value.
2 = Low
mA output will fail to its
low
condition.
3.5mA
3 = High
mA output will fail to its
high
condition.
22mA