Page16
If the device connected to the mA output is out of calibration, and cannot be
calibrated, then the low and high current levels can be trimmed by altering
P838 (Low Trim)
and
P839 (High Trim)
. To do this, simply enter the value
that ensures that 4 mA or 20 mA respectively are shown on the remote device.
You can use the left/right menu keys to alter the value until the correct
reading is shown on the remote device, rather than typing in a value.
Setting Security Passcodes
A passcode is used to switch the
IMP Lite
from
Run Mode
into
Program
Mode
.
You can set a new passcode to prevent anyone changing any of your settings
within your
IMP Lite
. The default
passcode
is
1997
, but this may be changed
as follows.
Additional Information
The passcode is also used for remote access using the RS232, so if this is
being used, be sure to ensure any additional equipment using this feature is
changed accordingly.
Using A Passcode
If you don’t want to use a passcode, you can disable it as follows. First, enter
Program Mode
and go to the
SyS1
(System
)
menu. Select
P921
which is the
passcode enable
parameter.
As shown on the display, setting the passcode enable to ‘
0
’ will
disable
it, or
‘
1
’ will
enable
the use of passcode.
Additional Information
If the use of a passcode has been disabled, then you can move straight into
Program Mode from Run Mode by pressing the ESC and
ENTER
button
simultaneously.
Changing the Passcode
You can set the
passcode
to any number from 0000 to 9999. To do this,
enter
Program Mode
and go to
SyS1
(System) menu. Select
P922
which is
the
Passcode
parameter which can be changed as required.