Outdoor and Open Vessel Installation
The
IMP Lite
can be simply mounted on a bracket, suitable for the application
and secured using the thread located at the top of the transducer
(2"BSP/NPT).
Care should be taken to ensure that the
IMP Lite
is not installed in direct
sunlight, in order to avoid errors in the measurement of ambient temperature.
Attention should also be taken, when mounting the unit, to ensure that strong
windy conditions are avoided, wherever possible, to prevent abnormal
operation.
IMP
Model
Range
L =
Blanking
Lite 3
3 metres
(9.84 feet)
200mm
(0.66 feet)
Lite 6
6 metres
(19.69 feet)
300mm
(0.98 feet)
Lite 10
10 metres
(32.18 feet)
300mm
(0.98 feet)
“L” should as a minimum be at least that as detailed in the table above
but can be greater if required.
Closed Vessel Installation
“L” should as a minimum be at least that as detailed in the table above but can
be greater if required. The
IMP Lite
can be simply screwed into a flange and
secured using the thread located at the top of the transducer (1.5" or 2"BSP/
NPT, dependent on model).
Where possible use a flange made of a synthetic material such as PVC, in
cases where a metal flange is used it is advisable to fit a suitable gasket
between the flange of the
IMP Lite
and the connection to the vessel.