FLOWCERT LITE (UL) INSTRUCTION MANUAL
46
For More Options Hit Ent
er….
PARAMETER
DEFAULT
DESCRIPTION
P213 / P214
Relay 1 ON/OFF
setpoints
depends on
application
Set required Alarm Setpoints.
P223 / P224
Relay 2 ON/OFF
setpoints
depends on
application
Set required Alarm Setpoints.
P233 / P234
Relay 3 ON/OFF
setpoints
depends on
application
Set required Alarm Setpoints.
P243 / P244
Relay 4 ON/OFF
setpoints
depends on
application
Set required Alarm Setpoints.
P253 / P254
Relay 5 ON/OFF
setpoints
depends on
application
Set required Alarm Setpoints.
P708 Flow
Decimal
2
Set the number of decimal points required in the
flow rate display
P709 Flow Cut
Off
5.00%
Enter as a percentage of maximum flow, the
minimum flow rate to be added to the totaliser.
P830
mA Out Range
2= 4 to 20
mA
What the mA output uses for the range.
0= Off, 1= 0 to 20 mA, 2= 4 to 20 mA, 3= 20 to
0 mA, 4= 20 to 4 mA.
P870
Fill Damping
10m/min
Rate of maximum fill rate (set above the actual
fill rate of the vessel).
P871
Empty Damping
10m/min
Rate of maximum empty rate (set above the
actual empty rate of the vessel).
Default values used for determining the
relay setpoints
, when setting
Alarm
relays, via the
Quick Setup
menu are entered as a % of span and are
as follows:
PARAMETER
ALARM ID
ON SETPOINT
OFF SETPOINT
Alarm
Hi Hi
90%
85%
Alarm
High
85%
80%
Alarm
Low
10%
15%
Alarm
Lo Lo
5%
10%