PULSAR MEASUREMENT
111
Auxiliary
P810 Units
This parameter determines whether the
Measurement units
(
P104
) are
displayed on the auxiliary line of the display in run mode.
OPTION
DESCRIPTION
0 = No
Measurement units
will not
be displayed
1 = Yes (Default)
Measurement units
will
be displayed
P811 Alarm Messages
This parameter determines whether notification messages are displayed on
the auxiliary line of the display in run mode when an alarm relay is switched
on or off. The message is in the form “Alarm
High ON”, where the ‘High’ is
determined by the setting of the relay
Alarm ID
(
P212, 222, 232
).
OPTION
DESCRIPTION
0 = No (Default)
Alarm messages
will not
be displayed
1= Yes
Alarm messages
will
be displayed
P812 General Control or Pump Messages
This parameter determines whether notification messages are displayed on
the auxiliary line of the display in run mode when a pump or general control
rela
y is switched on or off. The message is in the form “General 1 ON”, where
the number displayed is the number of the relay.
OPTION
DESCRIPTION
0 = No (Default)
Pump messages
will not
be displayed
1= Yes
Pump messages
will
be displayed