PULSAR MEASUREMENT
45
PARAMETER
DEFAULT
DESCRIPTION
P823
Totaliser
Multiplier
1 = /1000
Sets the factor by which the calculated volume
will be divided or multiplied by before it is
displayed.
1 = /1000
3 = /10
5 = *10
7 = *1000
9 = *100,000
2 = /100
4 = *1
6 = *100
8 = *10,000
10 = *1,000,000
The remaining parameters required to finalise the setup of your application
will follow on immediately from the above. These parameters relate to
details required to carry out the calculation for flow and will be dependent
on the PMD chosen and the method of calculation chosen, please enter
values for the parameters concerned as requested.
PARAMETER
DEFAULT
DESCRIPTION
P705
Max Flow
0.00
If Ratiometric is selected: When requested enter the
known maximum flowrate, in units of volume (P706)
and Time (P707) which occurs at maximum head
(P704). If Absolute is selected: The maximum
flowrate will be shown here as calculated by the unit.
P710
Dimension A
0
When requested enter, in measurement units, P104,
the required dimension.
P711
Dimension B
0
When requested enter, in measurement units, P104,
the required dimension.
P712
Dimension C
0
When requested enter, in measurement units, P104,
the required dimension.
P717
Exponent
Dependent
on chosen
PMD
Where available the FlowCERT will automatically enter
the default exponent value for the PMD chosen, but
this can be changed if required. When P700=7
(Other), enter the exponent value as defined by the
manufacturer of the PMD.
P718
K Factor
Enter the ‘K’ factor for the PMD, obtained from the
manufacture’s specification
P719
Throat Width
Enter the Throat Width for the Parshall Flume,
obtained from the manufacturer’s ‘
specification