Set Mode “H” to 0001 to activate over/under
voltage protection mode.
Note: over/under
protection does not work with other functions.
Set Mode “b” to 0000.
Set Mode “I” to adjust the set point for under
voltage cut-off, from 0 to 200 VAC.
Set Mode “d” start up delay on power
restoration between 000.1 and 999.9 minutes to
prevent short cycling of connected load.
Set Mode “J” to adjust the set point for over
voltage cut-off from 201 to 300 VAC.
Set mode “L” to adjust the delay before the load
is restored after an over or under voltage event
has occurred. Delay from 0.1 to 999.9 minutes.
Quick Start Chart : Over-Under Voltage and Brown Out Protection
0000
H
0000
1
0000
j
0000
L
0000
000.1
To
999.9
H 0000
To
H 0001
i 0000
To
i 0200
j 0201
To
j 0300
L 000.1
To
L 999.9
0000
0000
0001
0000
To
0001
Set Mode “A” to 0000 to disable dry contact
control of relay.
A
0000
A 0000
To
A 0003
SAK-60
Installation Programming Guide
Set To:
Mode
Adjustment Range
Adjustment Details