The SAK-60 is a 60 amp microprocessor controlled two-pole latching relay with built in functionality to 

lock out or manage loads on generator power, protect from over-voltage / under-voltage and brownouts. 

The SAK-60 can also work as conventional relay with dry contact inputs with adjustable on-time delay. The 

device is built around latching relays that are toggled on and off by a short pulse of energy to open and close 

the contacts. The relay incorporates SRT

®

 (Smart Relay Technology) to control switching at the zero cross 

over point of the sine-wave for reliability and maximum life expectancy of the contacts. The SAK-60 is self-

powered by the 120 VAC or 120/240 VAC line input voltage eliminating the need for a secondary power source 

normally required to power the coil of a conventional device. Additionally, the SAK-60 comes with a two year 

product warranty from the date of install.

Generator Detection & Load Lock-Out

The SAK-60 uses a proprietary Sine Wave-Distortion Index

®

 with user adjustable sampling rates to adapt 

to most utility and generator sine-waves. When Load-Drop is selected from the main menu Mode “B 0000”, 

at power the device will turn the relay off at power up. The system analyzes the sine-wave to determine if 

the power source is utility or generator. When utility is detected, the Gen-Util LED will turn green, the Load 

On relay LED will illuminate yellow, closing the relay contacts and restoring the connected load. When 

generator is detected, the Gen-Util LED will illuminate red, and the load will remain off until stable utility 

power is restored. The Sine Wave Distortion Index

®

 reading will be displayed on the LCD digital display. After 

utility power returns and is detected by the SAK-60, The Gen-Utility LED will turn green, the Load On LED 

illuminates yellow and the device enters sleep mode.

Generator Detection & Load Management With Under Frequency Control

In addition to Load-Lockout, the SAK-60 can Load-Manage using Under Frequency detection for air cooled 

generators. There are two modes for under frequency load management. The first Mode “C 0001” is fixed 

and the pre-set under frequency and delay times cannot be adjusted. These values should be suitable for 

most air-cooled applications. The second Mode “C 0000” provides field adjustments for frequency and delay 

time to allow the installer to adjust up to three levels of under frequency detection. The option to adjust these 

parameters allows the SAK-60 to adapt to the majority of load management applications 

Load Management Under Frequency Control

When power is restored after a power outage, and load management Mode “B 0001” is selected, the SAK-

60 disconnects the load. The system analyzes the sine-wave to determine if the power source is utility or 

generator. When a utility sine wave is detected, the Gen-Util LED turns green, the Load On LED illuminates 

closing the relay contacts to restore the connected load. The SAK-60 will now enter sleep mode. When 

generator sine-wave is detected, the Gen-Util LED illuminates Red indicating generator power is detected. 

After the adjustable delay “g 000.0”, the load is restored and the Gen-Util LED flashes red, indicating load 

management mode is active, and the yellow LED illuminates indicating the load is restored. The AC frequency 

is displayed on the front panel LCD. In the event of an under frequency condition meeting the trigger points of 

either Mode “C 0001” or “C 0000”, the load is disconnected for the delay time set in Mode “O 000.0”. When 

utility power is restored, the Gen-Util LED will illuminate green and device enters sleep mode.

Conventional Relay with Dry-Contact Control Input

The SAK-60 can work as a stand alone 60 amp relay, controlled by a normally open or normally closed logic 

dry contact control input. 

Do not apply voltage to the dry contact terminals. This will damage the SAK-60 

and void the warranty.

 The loads controlled by the relay can be either 120/240 VAC double pole or 120 VAC 

single pole. Relay control can be adjusted for instant closure of the contacts, or for delayed closure for up to 

10 minutes in one second increments. This device is also designed to be used as a standalone over-voltage / 

under-voltage protection cut off device with adjustable High/Low set points and restore delay adjustments.

Technical Assistance Call: 800-648-6802

Instructional Videos available at: www.sak60.com 

SAK-60

Installation and Programming Instructions

Summary of Contents for SAK-60

Page 1: ...re displayed on the LCD screen The program mode exits and saves settings after 7 seconds of inactivity Set Mode A to 0000 to disable dry contact control of relay Set Mode b to 0000 to enable load lock...

Page 2: ...after generator is detected For multiple loads stagger restore times based on priority of loads connected Set Mode C to 0001 to enable pre set under frequency cut off points or set to 0000 to enable u...

Page 3: ...estoration this extended delay U is activated and added to setting O normal restore delay Time Delay 2 Set delay time from 00 1 to 10 0 seconds for under frequency 2 under frequency load shed Default...

Page 4: ...event short cycling of connected load Set Mode J to adjust the set point for over voltage cut off from 201 to 300 VAC Set mode L to adjust the delay before the load is restored after an over or under...

Page 5: ...management under frequency drop of loads when generator detected Active in mode b0001 only Adjust the delay time in minutes before restoring load after generator sine wave has been detected C 0000 to...

Page 6: ...00Hz follows delay d2 Under frequency mode C 0001 fixed 56 00 Hz Active when Menu C 0000 Under Frequency F3 Set from 50 00 to 60 00 Hz Default setting 52 00Hz follows delay d3 Under frequency mode C 0...

Page 7: ...VC III Pollution degree PD2 Rated Impulse Voltage 2500 V Maximum phase to ground voltage of the supply source 150 V Protection against electric shock class Insulation encased Class II Equipment Enviro...

Page 8: ...quency load management The first Mode C 0001 is fixed and the pre set under frequency and delay times cannot be adjusted These values should be suitable for most air cooled applications The second Mod...