Adjust set point to detect over voltage cut-off,

from 201 to 300 VAC.

Adjust the delay before the load is restored 

after an over or under voltage condition 

occurred. Delay from 000.1 to 999.9 minutes.

Active when Menu “C” = 0000

Under frequency F1 Set from 50.00 to 60.00 Hz

Default setting 57.00 Hz follows delay d1

Under frequency mode“ C 0001” fixed 58.00 Hz

Active when Menu “C” = 0000

Under Frequency F2 Set from 50.00 to 60.00 Hz 

Default setting 55.00Hz follows delay d2

Under frequency mode“ C 0001” fixed 56.00 Hz

Active when Menu “C” = 0000

Under Frequency F3 Set from 50.00 to 60.00 Hz

Default setting 52.00Hz follows delay d3

Under frequency mode“ C 0001” fixed 53.00 Hz

Adjust the delay for turning on relay with dry

contact input when modes A=1 or A=3 are

selected. Delay can be adjusted from 0 to 999

seconds.

Service adjustment. Default 15.

Consult technical support.

Service adjustment. Default 15.

Consult technical support.

0270

 

0015

001.0

F i

57.0

000

F 2

55.0

0015

F 3

52.0

j 0201

To

j 0300

 0010

To

 0200

L 000.1

To

l

 

999.9

F 1

50.0

To

F 1

60.0

000

To

999

F 2

50.0

To

F 2

60.0

5 0010

To

5 0200

F 3

50.0

To

F 3

60.0

Note: Lower Case c

SAK-60

Flow Chart Menu continued

  Mode/Default 

Adjustment Range 

Adjustment Details

Summary of Contents for SAK-60

Page 1: ...re displayed on the LCD screen The program mode exits and saves settings after 7 seconds of inactivity Set Mode A to 0000 to disable dry contact control of relay Set Mode b to 0000 to enable load lock...

Page 2: ...after generator is detected For multiple loads stagger restore times based on priority of loads connected Set Mode C to 0001 to enable pre set under frequency cut off points or set to 0000 to enable u...

Page 3: ...estoration this extended delay U is activated and added to setting O normal restore delay Time Delay 2 Set delay time from 00 1 to 10 0 seconds for under frequency 2 under frequency load shed Default...

Page 4: ...event short cycling of connected load Set Mode J to adjust the set point for over voltage cut off from 201 to 300 VAC Set mode L to adjust the delay before the load is restored after an over or under...

Page 5: ...management under frequency drop of loads when generator detected Active in mode b0001 only Adjust the delay time in minutes before restoring load after generator sine wave has been detected C 0000 to...

Page 6: ...00Hz follows delay d2 Under frequency mode C 0001 fixed 56 00 Hz Active when Menu C 0000 Under Frequency F3 Set from 50 00 to 60 00 Hz Default setting 52 00Hz follows delay d3 Under frequency mode C 0...

Page 7: ...VC III Pollution degree PD2 Rated Impulse Voltage 2500 V Maximum phase to ground voltage of the supply source 150 V Protection against electric shock class Insulation encased Class II Equipment Enviro...

Page 8: ...quency load management The first Mode C 0001 is fixed and the pre set under frequency and delay times cannot be adjusted These values should be suitable for most air cooled applications The second Mod...

Reviews: