Adjust set point to detect over voltage cut-off,
from 201 to 300 VAC.
Adjust the delay before the load is restored
after an over or under voltage condition
occurred. Delay from 000.1 to 999.9 minutes.
Active when Menu “C” = 0000
Under frequency F1 Set from 50.00 to 60.00 Hz
Default setting 57.00 Hz follows delay d1
Under frequency mode“ C 0001” fixed 58.00 Hz
Active when Menu “C” = 0000
Under Frequency F2 Set from 50.00 to 60.00 Hz
Default setting 55.00Hz follows delay d2
Under frequency mode“ C 0001” fixed 56.00 Hz
Active when Menu “C” = 0000
Under Frequency F3 Set from 50.00 to 60.00 Hz
Default setting 52.00Hz follows delay d3
Under frequency mode“ C 0001” fixed 53.00 Hz
Adjust the delay for turning on relay with dry
contact input when modes A=1 or A=3 are
selected. Delay can be adjusted from 0 to 999
seconds.
Service adjustment. Default 15.
Consult technical support.