background image

PSP Products, Inc.  |  8618 Phoenix Drive  |  Manassas, VA 20110  |  pspproducts.com  |  1-800-648-6802  |  [email protected]

Revised: 9/23/2021

 

0000

To

 

0001

001

To

999

9 0001

To

9 999.9

Set Mode “A” to 0000 to disable dry contact

control of relay.

A = 0 Dry contact input disabled

A = 1 Dry contact closed relay closed

A = 2 Same as A0001 with 5 min delay

A = 3 Dry contact open relay closed

Set Mode “d” to a minimum of 000.2 to provide 

12 second (2/10 Min) delay after power up 

to allow power to stabilize. Increase time as 

needed.

Set Mode “b” to 0000 to enable load lockout

mode on generator.

Ad = Delay for turning on relay with dry contact 

input when modes A 0001 or A 0003 are 

selected. Delay from 1 to 999 seconds. Set to 

000 for no delay.

Set Mode “g” for the delay in minutes before 

load is restored after generator is detected . For 

multiple loads stagger restore times based on 

priority of loads connected.

Set Mode “C” to 0001 to enable pre-set under 

frequency cut off points or set to 0000 to 

enable user adjustable under frequency cut off 

settings. See advanced settings for adjustable 

settings.

Set Mode “0” for the delay in minutes before 

load is restored after an under frequency over 

load event has occurred. This setting generally 

mirrors Mode “g” above, however the delay 

can be customized based on the devices under 

control and priority of the load.

Quick Start Chart : Load Management (Under Frequency) on Generator Menu Settings

Quick Start Chart : Dry Contact Input Relay Control

0000

0000

0000

 

0000

000

0000

0000

0000

0001

A 0000

To

A 0003

A 0000

To

A 0003

c 0000

To

c 0001

 

000.0

To

 

999.9

0

 

000.1

To

0

 

999.9

Note: Upper Case C

SAK-60

Installation Programming Guide

 

Set To: 

Mode 

Adjustment Range 

Adjustment Details

 

Set To: 

Mode 

Adjustment Range 

Adjustment Details

Summary of Contents for SAK-60

Page 1: ...re displayed on the LCD screen The program mode exits and saves settings after 7 seconds of inactivity Set Mode A to 0000 to disable dry contact control of relay Set Mode b to 0000 to enable load lock...

Page 2: ...after generator is detected For multiple loads stagger restore times based on priority of loads connected Set Mode C to 0001 to enable pre set under frequency cut off points or set to 0000 to enable u...

Page 3: ...estoration this extended delay U is activated and added to setting O normal restore delay Time Delay 2 Set delay time from 00 1 to 10 0 seconds for under frequency 2 under frequency load shed Default...

Page 4: ...event short cycling of connected load Set Mode J to adjust the set point for over voltage cut off from 201 to 300 VAC Set mode L to adjust the delay before the load is restored after an over or under...

Page 5: ...management under frequency drop of loads when generator detected Active in mode b0001 only Adjust the delay time in minutes before restoring load after generator sine wave has been detected C 0000 to...

Page 6: ...00Hz follows delay d2 Under frequency mode C 0001 fixed 56 00 Hz Active when Menu C 0000 Under Frequency F3 Set from 50 00 to 60 00 Hz Default setting 52 00Hz follows delay d3 Under frequency mode C 0...

Page 7: ...VC III Pollution degree PD2 Rated Impulse Voltage 2500 V Maximum phase to ground voltage of the supply source 150 V Protection against electric shock class Insulation encased Class II Equipment Enviro...

Page 8: ...quency load management The first Mode C 0001 is fixed and the pre set under frequency and delay times cannot be adjusted These values should be suitable for most air cooled applications The second Mod...

Reviews: