9.2 Faults without error messages

Faults and malfunctions that cannot be displayed as well as possible causes and 

their error source can be identified using the following table. If you cannot remedy 

the fault using the description below, contact the supplier or installer. 

Problem

Possible causes

Measures

Display does not 

function

 

230V mains voltage not 

 

available

   Switch on or connect  

controller

   Check the connection's 

main fuse

Defective fuse inside the 

 

device

   Check the fuse*,  

replace with a new type 

2A/T, if necessary.

   Check the 230V compo-

 Check the 230V compo-

Check the 230V compo-

nents for short-circuits

Defect device

 

   Contact the supplier

Output is not 

switched on

Switch-on condition is not 

 

fulfilled.

   Wait until switch-on 

condition is satisfied.

"Pump" symbol 

rotates, but the 

pump is not on 

 

Connection to the pump 

 

interrupted.

  Check the cable leading 

to the pump

Pump is blocked.

 

  Free the pump

No voltage present at the 

 

switching output.

   Contact the supplier.

Temperature 

display strongly 

fluctuates at short 

intervals

Sensor cables are installed 

 

near the 230V cables

   Relocate sensor cables, 

shield sensor cables

Long sensor cables ex-

 

tended without shielding

   Shield sensor cables

Defect device

 

   Contact the supplier

 

Faults that affect the 
230V/A mains power 

supply must only be remedied by 
a specialist!

Summary of Contents for Sunny Scout 1328

Page 1: ...Microcontroller controlled temperature difference controller for solar thermal systems Operatingmanual Sunny Scout 1328...

Page 2: ...7 1 2 Thermostat 8 7 1 3 RPM control 8 7 2 Protective functions 8 7 2 1 Anti freeze protection Jumper on 8 7 2 3 System protection 8 7 2 3 Pump blocking protection 8 8 System monitoring 9 8 1 Sensor...

Page 3: ...onnection box Immersion sleeves 2 Safety instructions Always completely disconnect the device from the operating voltage before performing installation or wiring work on the electrical equipment Never...

Page 4: ...nductor terminals N are electrically connected and are not switched The switching output A1 is electronic 230V N O contact If potential free contacts are required the appropriate corresponding accesso...

Page 5: ...side of the housing using a suitable tool Briefly pressing the button switches the controller from the Info menu to the Basic Setup menu Here you can scroll through and select the variables and infor...

Page 6: ...nge Factory setting Current setting max 65 C Storage tank Maximum permissible tempe rature 15 95 C 60 C dT max 7 K Storage tank Switch on difference 3 40K 10K dT min 3 K Storage tank Switch off differ...

Page 7: ...Mains phase N Neutral conductor mains and outputs A1 Solar circuit pump switching output 1 Sensor connections S1 Collector sensor S2 Lower storage tank Switch positions Temp diff controller all off H...

Page 8: ...he output A1 can be operated using an RPM control Minimum 30 7 2 Protective functions The controller is equipped with the following protective functions 7 2 1 Anti freeze protection This function must...

Page 9: ...s that are automatically detected by the controller and therefore can be displayed using error messages Faults that the controller cannot detect 9 1 Faults with error messages LED s Display Meaning Me...

Page 10: ...230V compo nents for short circuits Defect device Contact the supplier Output is not switched on Switch on condition is not fulfilled Wait until switch on condition is satisfied Pump symbol rotates b...

Page 11: ...cording to EN 60730 DIN VDE 0631 IEC 60664 IEC Output Voltage Power switching output 230V 1A approx 230VAfor cos 0 7 1 0 Fuse protection Fine wire fuse 5 x 20mm 2A T 2 amperes delayed action fuse Misc...

Page 12: ...itory action reduction of price is excluded Warranty claims may only be submitted by the customer and are non transferable If a defect occurs during the warranty period please contact the supplier ins...

Reviews: