![ProSoft MVI56E-FLN User Manual Download Page 89](http://html1.mh-extra.com/html/prosoft/mvi56e-fln/mvi56e-fln_user-manual_1618868089.webp)
MVI56E-FLN ♦ ControlLogix Platform
Reference
FA Control Network Ethernet Communication Module
User Manual
ProSoft Technology, Inc.
Page 89 of 155
4.1.2 General Specifications
Backward compatible with previous MVI56-FLN versions
Single-slot 1756 ControlLogix backplane compatible
10/100 Mbps auto crossover detection Ethernet configuration and application
port
User-definable module data memory mapping of up to 5000 16-bit registers
ProSoft Configuration Builder (PCB) software supported, a Winows-based
graphical user interface providing simple product and network configuration
Sample ladder logic is used for data transfer between module and processor
Internal web server provides access to product documentation, module
status, diagnostics, and firmware updates
4-character, alpha-numeric, scrolling LED display of status and diagnostics
data in plain English
– no cryptic error or alarm codes to decipher
ProSoft Discovery Service (PDS) software used to locate the module on the
network and assign temporary IP address
Personality Module - a non-volatile industrial-grade Compact Flash (CF) card
used to store network and module configuration, allowing quick in-the-field
product replacement by transferring the CF card
4.1.3 Hardware Specifications
Specification
Description
Backplane Current Load
800 mA @ 5 Vdc
3 mA @ 24 Vdc
Operating Temperature
0°C to 60°C (32°F to 140°F)
Storage Temperature
-40°C to 85°C (-40°F to 185°F)
Shock
30 g operational
50 g non-operational
Vibration: 5 g from 10 to 150 Hz
Relative Humidity
5% to 95% (without condensation)
LED Indicators
Battery Status (ERR)
Application Status (APP)
Module Status (OK)
4-Character, Scrolling, Alpha-
Numeric LED Display
Shows Module, Version, IP, Application Port
Setting, Port Status, and Error Information
Debug/Configuration Ethernet port (E1)
Ethernet Port
10/100 Base-T, RJ45 Connector, for CAT5 cable
Link and Activity LED indicators
Auto-crossover cable detection
FL-net Application Ethernet port (E2)
Ethernet Port
10 base-T, RJ45 Connector, for CAT5 cable
Link and Activity LED indicators
Auto-crossover cable detection
Shipped with Unit