MVI56E-FLN ♦ ControlLogix Platform
Start Here
FA Control Network Ethernet Communication Module
User Manual
ProSoft Technology, Inc.
Page 29 of 155
3
Enter the
Name, Description
and
Slot
options for your application. You must
select the
Comm Format
as
D
ATA
-
INT
in the dialog box, otherwise the
module will not communicate. Click
OK
to continue.
Parameter
Value
Name
Enter a module identification string. Example:
FLN_2
Description
Enter a description for the module. Example:
FA
C
ONTROL
N
ETWORK
C
OMMUNICATION
M
ODULE
Comm Format
Select
D
ATA
-INT
.
Slot
Enter the slot number in the rack where the MVI56E-FLN
module is located.
Input Assembly Instance
1
Input Size
250
Output Assembly Instance
2
Output Size
248
Configuration Assembly Instance
4
Configuration Size
0
4
Select the
Requested Packet Interval
value for scanning the I/O on the
module. This value represents the minimum frequency that the module will
handle scheduled events. This value should not be set to less than
1
millisecond. The default value is
5
milliseconds. Values between
1
and
10
milliseconds should work with most applications.