ProSoft MVI56E-FLN User Manual Download Page 83

MVI56E-FLN ♦ ControlLogix Platform 

Diagnostics and Troubleshooting 

FA Control Network Ethernet Communication Module  

User Manual 

 

 

ProSoft Technology, Inc. 

Page 83 of 155 

 

 

3.3.3  Non-Scrolling LED Status Indicators 

The non-

scrolling LEDs indicate the module’s operating status as follows: 

 

LED Label 

Color 

Status 

Indication 

LER 
(FL-net Link 
Status LED) 

Red or 
Green 

OFF 

The module is not receiving adequate power or is not securely 
plugged into the rack. May also be OFF during configuration 
download. 

GREEN 

The MVI56E-FLN is 'in-ring' and working normally. 

RED 

The most common cause is that the module has detected a 
communication error during operation of its application port. 
The following conditions may also cause a RED LED: 

 

The module is 'out-ring' or has a duplicate node number 
(Watchdog timeout error or Wait error may cause this) 

 

The module is rebooting due to a ColdBoot or WarmBoot 
request from the ladder logic or Debug Menu 

 

The firmware is initializing during startup 

 

The firmware detects an on-board hardware problem 
during startup 

 

Failure of application port hardware during startup 

 

The module is shutting down 

OK 

Red or 
Green 

OFF 

The module is not receiving adequate power or is not securely 
plugged into the rack. 

GREEN 

The module is operating normally. 

RED 

The module is initializing, has detected an internal error, or is 
re-booting. If the LED remains RED for over 10 seconds, the 
module is not working. Remove it from the rack and re-insert it 
to restart its internal program. 

 

Summary of Contents for MVI56E-FLN

Page 1: ...MVI56E FLN ControlLogix Platform FA Control Network Ethernet Communication Module July 10 2019 USER MANUAL...

Page 2: ...and RadioLinx are Registered Trademarks of ProSoft Technology Inc All other brand or product names are or may be trademarks of and are used to identify products and services of their respective owners...

Page 3: ...C These products are intended to be mounted in an IP54 enclosure The devices shall provide external means to prevent the rated voltage being exceeded by transient disturbances of more than 40 This dev...

Page 4: ...battery may become fully discharged and require recharging by being placed in a powered up ControlLogix chassis The time required to fully recharge the battery may be as long as 24 hours Once it is f...

Page 5: ...or 31 1 10 4 Downloading the Sample Program to the Processor 32 2 Configuring the MVI56E FLN Module 33 2 1 Using ProSoft Configuration Builder Software 33 2 1 1 Setting Module Parameters 34 2 2 Module...

Page 6: ...f FL net 116 4 4 2 Data Frame ID of FL net 116 4 4 3 Allowable Refresh Cycle Time 117 4 4 4 Memory Resources 117 4 4 5 Message Transmissions 118 4 4 6 Message Transmission Function 120 4 4 7 Data Volu...

Page 7: ...MVI56E FLN ControlLogix Platform Contents FA Control Network Ethernet Communication Module User Manual ProSoft Technology Inc Page 7 of 155 Glossary of Terms 149 Index 153...

Page 8: ...Contents MVI56E FLN ControlLogix Platform User Manual FA Control Network Ethernet Communication Module Page 8 of 155 ProSoft Technology Inc...

Page 9: ...ary IP Address 17 Connecting to the Module s Web Page 22 Using the RSLogix 5000 Sample Project 23 To get the most benefit from this User Manual you should have the following skills Rockwell Automation...

Page 10: ...ware for diagnostics connecting via the module s Ethernet port to upload download module configuration information and access troubleshooting features and functions ProSoft Discovery Service PDS Utili...

Page 11: ...ng systems o Microsoft Windows 10 o Microsoft Windows 7 Professional 32 or 64 bit o Microsoft Windows XP Professional with Service Pack 1 or 2 o Microsoft Windows Vista o Microsoft Windows 2000 Profes...

Page 12: ...with your MVI56E FLN module and are all required for installation and configuration Important Before beginning the installation please verify that all of the following items are present Qty Part Name...

Page 13: ...r to leave the Setup pins jumpered That way you can update the module s firmware without requiring physical access to the module Security considerations Leaving the Setup pin jumpered leaves the modul...

Page 14: ...fter you have checked the placement of the jumpers insert the MVI56E FLN into the ControlLogix chassis Use the same technique recommended by Rockwell Automation to remove and install ControlLogix modu...

Page 15: ...You must identify the slot in which the module is installed in order for the sample program to work correctly Slot numbers are identified on the green circuit board backplane of the ControlLogix rack...

Page 16: ...t is for exclusive use on the FL net network and cannot be used for configuration To configure the module once it is securely mounted connect one end of an Ethernet cable to the Config E1 port and con...

Page 17: ...sages may be blocked by routers or layer 3 switches In that case ProSoft Discovery Service will be unable to locate the modules To use ProSoft Configuration Builder arrange the Ethernet connection so...

Page 18: ...onsists of a tree view on the left and an information pane and a configuration pane on the right side of the window When you first start PCB the tree view consists of folders for DEFAULT PROJECT and D...

Page 19: ...LE TYPE This action opens the Choose Module Type dialog box 5 In the Product Line Filter area of the dialog box select MVI56E In the SELECT MODULE TYPE dropdown list select MVI56E FLN and then click O...

Page 20: ...TEST CONNECTION button to verify if the module is accessible with the current settings 9 If PCB is still unable to connect to the module click the BROWSE DEVICE S button to open the ProSoft Discovery...

Page 21: ...rolLogix Platform Start Here FA Control Network Ethernet Communication Module User Manual ProSoft Technology Inc Page 21 of 155 13 On the shortcut menu choose DIAGNOSTICS This action opens the Diagnos...

Page 22: ...e right mouse button to open a shortcut menu 2 On the shortcut menu choose VIEW MODULE S WEBPAGE The Web page contains general product information firmware download link and links to ProSoft Technolog...

Page 23: ...of your ControlLogix processor The firmware version and sample program version must match Determining the Firmware Version of Your Processor Important The RSLinx service must be installed and running...

Page 24: ...hernet Communication Module Page 24 of 155 ProSoft Technology Inc 5 On the Connected To Go Online dialog box click the GENERAL tab This tab shows information about the processor including the Revision...

Page 25: ...ram tags and variables are correct and do not conflict with other modules in the rack Changing the slot number 1 In the Controller Organization list select the module and then click the right mouse bu...

Page 26: ...tablish communication with the processor follow these steps 1 Open RSLinx 2 Open the COMMUNICATIONS menu and choose CONFIGURE DRIVERS This action opens the Configure Drivers dialog box Note If the lis...

Page 27: ...button RSLinx will attempt to configure your serial port to work with the selected driver 5 When you see the message Auto Configuration Successful click the OK button to dismiss the dialog box Note I...

Page 28: ...Existing Project 1 Select the I O Configuration folder in the Controller Organization window of RSLogix 5000 and then click the right mouse button to open a shortcut menu On the shortcut menu choose...

Page 29: ...or the module Example FA CONTROL NETWORK COMMUNICATION MODULE Comm Format Select DATA INT Slot Enter the slot number in the rack where the MVI56E FLN module is located Input Assembly Instance 1 Input...

Page 30: ...the module Click OK to dismiss the dialog box The Controller Organization window now displays the module s presence 6 Copy the User Defined Data Types from the sample program into your existing RSLogi...

Page 31: ...g steps show how to establish communication through the serial interface It is not mandatory that you use the processor s serial interface You may access the processor through whatever network interfa...

Page 32: ...hrough the processor s serial port as shown here You may download through any available network connection 2 When communication is established RSLogix 5000 will open a confirmation dialog box Click th...

Page 33: ...that transfers the data to a TOYODA PC3JG P processor located on the same rack For this example the MVI56E FLN node address is 40 and the FL ET T V2 module node address is 10 2 1 Using ProSoft Configu...

Page 34: ...n the tree view Renaming an Object 1 Select the object and then click the right mouse button to open a shortcut menu From the shortcut menu choose RENAME 2 Type the name to assign to the object 3 Clic...

Page 35: ...ialog box appears 3 Enter your comment and click OK to save your changes Printing a Configuration File 1 Select the module icon and then click the right mouse button to open a shortcut menu 2 On the s...

Page 36: ...le to properly transfer data between the ControlLogix processor and the remote FL net node Toyoda PLC TPLC Node Name Up to 10 ASCII characters This is a user defined node identification It can be set...

Page 37: ...rs can be set from the upper layer or by a network parameter write message When nodes receive a network parameter write message for setting these parameters the node secedes from the network and rejoi...

Page 38: ...ETDATA Output Area2 controller tag arrays Area 1 Top 0 Area 1 Size 50 Area 2 Top 0 Area 2 Size 100 Use the following settings to configure the data to transfer from the Common Memory to the processor...

Page 39: ...is a unique for each node and is set from the FA link protocol upper layer as the initial value If this value is not set the node is inoperable The allowable minimum frame interval means The time int...

Page 40: ...n the my_ip1 parameter set 1 Determine the network settings for the two ports on your module with the help of your network administrator if necessary You will need the following information For the co...

Page 41: ...e ProSoft Configuration Builder main window Node Number Node number Applications 1 to 249 Used for standard FL net Version 2 00 devices 250 to 254 Used for FL net Version 2 00 maintenance purposes 255...

Page 42: ...ion Builder click once to select the MVI56E FLN module 2 Open the PROJECT menu and then choose MODULE DOWNLOAD This action opens the Download dialog box Notice that the Ethernet address field contains...

Page 43: ...will see an error message To correct the error follow these steps 1 Click OK to dismiss the error message 2 On the Download dialog box click BROWSE DEVICES to open ProSoft Discovery Service 3 Select t...

Page 44: ...s are available This procedure will consider the first option ID Code C9 8kbytes of Link Memory Capacity Switch Positions I O module ID Code Link Memory Capacity Data Link Capacity maximum number of t...

Page 45: ...e MVI56E FLN Module FA Control Network Ethernet Communication Module User Manual ProSoft Technology Inc Page 45 of 155 2 4 2 FL ET V2 Configuration with PCwin Specifying I O Module ID Code 1 Expand th...

Page 46: ...le MVI56E FLN ControlLogix Platform User Manual FA Control Network Ethernet Communication Module Page 46 of 155 ProSoft Technology Inc 2 Select the FL net module Setting Up the FL ET V2 Link Parameter...

Page 47: ...ation Module User Manual ProSoft Technology Inc Page 47 of 155 2 Select the link number to assign to the FL ET T V2 module For this example use Link No 1 for the FL ET T V2 module Double click the lin...

Page 48: ...Communication Module Page 48 of 155 ProSoft Technology Inc 3 Click the DETAIL button to configure the following link parameters Node Number 10 Communication Method N N or 1 N Master 4 Click the DATA...

Page 49: ...kes place as described in the following illustration the Transmit Area in the TOYODA PLC must be configured inside the Link Area 5 Click OK to close the Data Link window and then click the NETWORK but...

Page 50: ...ownload it to the TOYODA PLC 2 4 4 Connecting the MVI56E FLN Module to the FL ET T V2 Use standard CA5 Ethernet cables to connect the Ethernet port on the MVI56E FLN through a 10 Megabit Ethernet hub...

Page 51: ...ured FL net network assuming that both the FL ET T V2 module and the MVI56E FLN module were configured according to the previous sections 2 5 1 Using the Diagnostics Menu in ProSoft Configuration Buil...

Page 52: ...Communication Module Page 52 of 155 ProSoft Technology Inc If there is no response from the module 1 Click the SET UP CONNECTION button to browse for the module s IP address 2 In the Connection Setup...

Page 53: ...e module then right click and choose SELECT FOR PCB 2 Close ProSoft Discovery Service and click the CONNECT button again 3 If all of these troubleshooting steps fail verify that the Ethernet cable is...

Page 54: ...ions describe several items in the Diagnostics menu useful for verifying communication in a newly set up module For information on the remaining menu items see Diagnostics Menu Items The Diagnostics m...

Page 55: ...equence that corresponds to the status of each FL net node The following tables show the correlation between the bits and the nodes on the FL net network for the first three words Word 0 Bit 0 1 2 3 4...

Page 56: ...each FL net node The following tables show the correlation between the bits and the nodes on the FL net network for the first three words Word 0 Bit 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Node 0 1 2 3...

Page 57: ...dule FA Control Network Ethernet Communication Module User Manual ProSoft Technology Inc Page 57 of 155 Checking the Log Data From the FL NET submenu select LOG DATA 1 or LOG DATA 2 to display informa...

Page 58: ...ol Network Ethernet Communication Module Page 58 of 155 ProSoft Technology Inc Checking the Network Status From the FL NET submenu select NETWORK STATUS to display network information Token holding no...

Page 59: ...56E FLN Module FA Control Network Ethernet Communication Module User Manual ProSoft Technology Inc Page 59 of 155 Checking the Own Node Data From the FL NET submenu select OWN NODE DATA to view settin...

Page 60: ...ntrol Network Ethernet Communication Module Page 60 of 155 ProSoft Technology Inc Checking the Participating Node Status From the FLN NET PARTICIPATION LIST submenu select NODES 0 127 and NODES 128 25...

Page 61: ...soft technology com http www prosoft technology com for the sample ladder logic for the MVI56E FLN module THE FLNETSTATUS controller tag contains status information that is copied from the module and...

Page 62: ...FLNETSTATUS General Nodes_Exchanging_Data_Table controller tag to see if each node is currently exchanging data The following illustration shows that only node 10 is currently exchanging data with the...

Page 63: ...blocks 0 and 1 Monitor the FLNETSTATUS General Nodes_Participating_Table controller tag to check if each node is currently participating in the FL net network The following illustration shows that onl...

Page 64: ...gs token watchdog time TW Each block can retrieve status for up to 10 participating nodes The user application must initially select the number of nodes to retrieve up to 10 and the first node address...

Page 65: ...56E FLN Module FA Control Network Ethernet Communication Module User Manual ProSoft Technology Inc Page 65 of 155 Note The sample ladder will copy the status for 10 nodes Edit this logic according to...

Page 66: ...User Manual FA Control Network Ethernet Communication Module Page 66 of 155 ProSoft Technology Inc The participating node status is read to the FLNETSTATUS Participation controller tag array The stat...

Page 67: ...uest special block 9250 Log Data Block from the module The following rung in the Write Data routine requests block 9250 To trigger this logic set the FLNETMODULE CONTROL GetParticipation bit to 1 The...

Page 68: ...ntrolLogix Platform User Manual FA Control Network Ethernet Communication Module Page 68 of 155 ProSoft Technology Inc You can view the Log Data read from the module in the FLNETSTATUS LogData control...

Page 69: ...rk for general FL net network information the token node that is currently holding the token the refresh cycle measurement time RMT minimum maximum and current values allowable minimum frame interval...

Page 70: ...ed by the sample ladder program supplied by ProSoft For this example use the following MVI56E FLN Area1 and Area 2 settings in the FLNET CFG configuration file Area 1 Top 0 0 511 top address for area...

Page 71: ...Transferring Data from MVI56E FLN Area 1 to FL ET T V2 Module Relay Area The FLNETDATA Output Area1 controller tags transfer data from the module Area 1 to the remote FL net node Relay link area For...

Page 72: ...Page 72 of 155 ProSoft Technology Inc Transferring Data from FL ET T V2 Link Area to MVI56E FLN Area 1 Use the PCWin Register Address Monitor to set the value to transfer to the module address L32W fo...

Page 73: ...sferring Data from MVI56E FLN Area 2 to FL ET T V2 module Register Area Use the FLNETDATA Output Area2 controller tags to transfer data from the module Area 1 to the remote FL net node Relay link area...

Page 74: ...74 of 155 ProSoft Technology Inc Transferring Data from FL ET T V2 Register Area to MVI56E FLN Area 2 Use the PCWin Register Address Monitor to set the value to transfer to the module address R0064 f...

Page 75: ...transferred from the module to the processor 3 1 Reading Status Data from the Module The MVI56E FLN module returns a block of status data in the input image that can be used to determine the module s...

Page 76: ...on node number conflicted to see whether any node having the same node number as the self node setting exists on the network or not 0x0001 1 TW Error 1 Error Token watchdog time error flag indicates...

Page 77: ...ommon memory of the node is completed 0x0040 7 Address Overlap 1 Error 0 No Error Indicates that there is a duplication in the common memory among the nodes connected to the network 0x0080 Only report...

Page 78: ...menu please refer to Using the Diagnostic Menu in Prosoft Configuration Builder For specific information on items in the FL NET submenu please see The Diagnostics Menu page 54 3 2 1 Monitoring Module...

Page 79: ...Module User Manual ProSoft Technology Inc Page 79 of 155 Viewing Configuration Information From the MODULE submenu select CONFIG to view backplane configuration settings for the MVI56E FLN module Thi...

Page 80: ...dule Viewing Backplane Status From the BACKPLANE submenu select STATUS to view current backplane status including Number of retries Backplane Status Fail Count Number of words read Number of words wri...

Page 81: ...time through the module s web page or with the optional MVI56E Advanced Add On Instruction C0 Client CmdCnt X MinDly X CmdOffs X RespTmout X Retries X ErrOffs X ARPTmout X ErrDelay X FltFlag X FltSt X...

Page 82: ...ulted or is in program mode IP Address Module IP address C0 OK Port is communicating without error Communication Errors port is having communication errors Refer to Diagnostics and Troubleshooting pag...

Page 83: ...on of its application port The following conditions may also cause a RED LED The module is out ring or has a duplicate node number Watchdog timeout error or Wait error may cause this The module is reb...

Page 84: ...condition follow these steps 1 Turn off power to the rack 2 Remove the card from the rack 3 Verify that all jumpers are set correctly 4 If the module requires a Compact Flash card verify that the car...

Page 85: ...just the MVI56E FLN Verify that all modules in the rack are correctly configured in the ladder logic Module Errors Problem Description Steps to take MVI56E modules with scrolling LED display Backplan...

Page 86: ...Diagnostics and Troubleshooting MVI56E FLN ControlLogix Platform User Manual FA Control Network Ethernet Communication Module Page 86 of 155 ProSoft Technology Inc...

Page 87: ...0 OPCN 2 defined by JEMA The Japan Electrical Manufacturers Association for the standard FA control network FL net is a master less system The MVI56E FLN module acts as a gateway between the FL net ne...

Page 88: ...area Message transfer Server Functionality o Log data read service o Log data clear service o Network Parameter Read o Profile Read o Return Message Network Management Table According to FL net versi...

Page 89: ...module on the network and assign temporary IP address Personality Module a non volatile industrial grade Compact Flash CF card used to store network and module configuration allowing quick in the fie...

Page 90: ...ControlLogix Form Factor Single Slot Connections o 1 RJ45 10 BaseT 10 Mbps connection to the FA Control Ethernet network FL net o 1 RJ45 10 100 BaseT 10 or 100 Mbps Ethernet connection for configurat...

Page 91: ...omputers and FA controllers such as programmable controllers PLCs or computerized numeric controllers CNCs by different manufacturers to be interconnected controlled and monitored as shown in the foll...

Page 92: ...et Communication Module Page 92 of 155 ProSoft Technology Inc Data Communication Between Nodes FL net supports data communications by cyclic transmission and message transmission Multi access data exc...

Page 93: ...ble With cyclic communications the Common Memory is refreshed on a fixed cycle time Message communications are controlled so that the Common Memory refresh time does not exceed the allowable refresh c...

Page 94: ...ach node updates and broadcasts its memory contents Each node broadcasts its data in a fixed cycle and all the nodes in a network share the same data on the Common Memory A user can use the Common Mem...

Page 95: ...e within Area 1 and Area 2 of the Common Memory Both areas can be assigned at any word size within the maximum A node s memory assignment within a Common Memory area is defined by the top address star...

Page 96: ...User Manual FA Control Network Ethernet Communication Module Page 96 of 155 ProSoft Technology Inc Common Memory Function A node can use the whole Common Memory as receiving area Node for Reception On...

Page 97: ...ication Module User Manual ProSoft Technology Inc Page 97 of 155 Node Having No Common Memory The FA link protocol allows for the existence of nodes that do not have Common Memory because they only pa...

Page 98: ...K words Area 2 4 High speed response High speed response time of 50 milliseconds 32 nodes for 2K bits and 2K words is provided The absence of a Master in the FL net network enables nodes to be added o...

Page 99: ...roSoft Technology Inc Page 99 of 155 4 2 2 Data Flow between Module and Processor The following discussion outlines the flow of data between the two pieces of hardware ControlLogix processor and MVI56...

Page 100: ...ata Block Range Descriptions 0 1 Status Data 1 to 3 Area 1 Data From Common Memory 4 to 35 Area 2 Data From Common Memory 1000 to 1004 Message Request ACK Blocks future 1100 to 1104 Message Response B...

Page 101: ...0 Area 1 data from field 240 241 Reserved 1 242 Reserved 1 243 Reserved 1 244 Reserved 1 245 Reserved 1 246 Reserved 1 247 Reserved 1 248 Reserved 1 249 Read Block ID 1 to 3 1 Area 2 Input Read Data B...

Page 102: ...and Byte 1 247 Upper Layer Status for Module 1 Area 1 Output Write Data Block Offset Description Length 0 Write Block ID 1 to 3 1 1 to 240 Area 1 Data to field 240 241 Reserved 1 242 Reserved 1 243 Re...

Page 103: ...pation Data fourth node 20 82 to 101 Participation Data fifth node 20 102 to 121 Participation Data sixth node 20 122 to 141 Participation Data seventh node 20 142 to 161 Participation Data eighth nod...

Page 104: ...ge Rx 2 26 to 27 Cyclic Rx errors 2 28 to 29 Cyclic Rx address size errors 2 30 to 31 Cyclic Rx CBN errors 2 32 to 33 Cyclic Rx TBN errors 2 34 to 35 Cyclic Rx BSIZE errors 2 36 to 37 Message retrans...

Page 105: ...oSoft Technology Inc Page 105 of 155 Offset Description Length 80 Node holding token 1 81 Network allowable min frame interval 1 82 Network allowable refresh cycle time 1 83 Current measured refresh c...

Page 106: ...2 Not applicable Optional Optional Optional Notes 1 Sending of cyclic transmission indicates a function that the node allocates common memory and that it transmits data in the common memory of the own...

Page 107: ...Area 2 data size Optional Supported Upper layer status Mandatory Token watchdog time Optional Supported Allowable minimum frame interval time Optional Supported Vendor code Optional Manufacturer model...

Page 108: ...0 and 250 255 are special function Common Memory Area 1 first word 2 bytes Word address 0 to 1FFH Common Memory Area 1 data size 2 bytes Size 0 to 200H Common Memory Area 2 first word 2 bytes Word ad...

Page 109: ...mber 1 byte 1 to 249 if participating a zero in this field for a node indicates the node is not participating on the network Upper layer status 2 bytes RUN STOP ALARM WARNING NORMAL See status block f...

Page 110: ...is running STOP Indicates that the upper layer program is at a stop Upper layer error information NORMAL Indicates that the upper layer is normal and both cyclic data and message data are guaranteed W...

Page 111: ...ic data and message data are not guaranteed Both cyclic data and message data are not guaranteed The Upper Layer Status word is structured as follows Upper Layer Status Word Bit Description Value 0 to...

Page 112: ...ndicates that updating of the existence signal of the upper layer cannot be recognized Node in ring out ring Indicates the information managed to see whether each node joins the network or secedes fro...

Page 113: ..._RingCommand controller tag will set the MVI56E FLN module again to in ring Firmware Version 1 04 or higher The in ring state can be checked by the FA Link status which now indicates that bit 0 is set...

Page 114: ...imum value and the minimum value from the start time are held in units of 1 ms Allowable minimum frame interval time Set from the upper layer The maximum value on the network is effective in units of...

Page 115: ...ied as 192 168 250 N N node No 1 to 125 The default value of the transmission destination is specified as 192 168 250 255 Remarks For the IP address it is recommended that class C is used and that the...

Page 116: ...thout token 65002 Participation request frame 65003 Byte block read frame request 65004 Byte block write frame request 65005 Word block read frame request 65006 Word block write frame request 65007 Ne...

Page 117: ...time 1 2 is specified as the allowable refresh cycle time When the network is started the allowable refresh cycle time is set to 0 When a token directed to the node is received 3 times at the start u...

Page 118: ...chnology Inc 4 4 5 Message Transmissions A token holding node can send up to one message frame 1 1 transmission and 1 N transmission are provided Message acknowledges is available for 1 1 transmission...

Page 119: ...d byte block data Not supported Write byte block data Not supported Read word block data Not supported Write word block data Not supported Read network parameter Supported Write network parameter Not...

Page 120: ...reception Total number of transmission at socket unit Y Total number of transmission errors at socket unit Y Number of Ethernet transmission errors N Total number of receptions Y Total number of rece...

Page 121: ...ded Y Number of tokens re issued Y Number of token holding timeouts Y Number of token monitoring timeouts Y Total service time Number of frame waiting states Y Number of participations Y Number of sel...

Page 122: ...ends on the data volume consisting of Area 1 and Area 2 1 When the data volume is 1024 bytes or less This data is transmitted by one frame Figure when the transit data volume is 1024 bytes or less 2 W...

Page 123: ...ode monitors it Node state management Network status and upper layer status are attached in the cyclic frame 4 4 9 Masterless Transmission Management Token 1 A node can transmit data only while holdin...

Page 124: ...er The node with the largest node number releases a token to the node with the smallest node number Token and Frames There are six types of frames sent with a token 1 When there is no cyclic data to b...

Page 125: ...ication Module User Manual ProSoft Technology Inc Page 125 of 155 6 When there is cyclic data and message data and the cyclic data is sent in divided form The message frame is transmitted and then onl...

Page 126: ...uest frame after the participation request frame transmission waiting time is up The participation request frame is transmitted regardless of token holding A node that has recognized a node number con...

Page 127: ...erlapping check are made when the node does not yet join the network At the initial startup status a conflict of node number address overlapping check are made for both nodes that transmitted a partic...

Page 128: ...e Number protocol 1 42 FL Status Own Status 1 43 Top Area 1 1 44 Size Area 1 1 45 Top Area 2 1 46 Size Area 2 1 47 Upper Layer Status 1 48 Watchdog Timeout MFT 1 49 to 53 Vendor Code 10 bytes 5 54 to...

Page 129: ...er 3 REV INTEGER 1 0 System parameter revision date 7 REVDATE INTEGER 2 0001 to 9999 INTEGER 1 01 to 12 INTEGER 1 01 to 31 2 2006 1 5 1 30 Device type 10 DVCATEGORY Printable String 5 OTHER Vendor nam...

Page 130: ...Soft Technology Inc 2 Value Definition syspara nameCOMVER COMVER paraCOMVER 1 nameID ID paraID SYSPARA nameREV REV paraREV 0 nameREVDATE REVDATE paraREVDATE year 2006 month 5 day 30 nameDVCATEGORY DVC...

Page 131: ...fier Length Content 02 02 07D6 02 01 05 02 01 1E Identifier Length Content 13 0A DVCATEGORY 13 05 OTHER 13 06 VENDOR 13 18 PROSOFT TECHNOLOGY INC 13 07 DVMODEL 13 09 MVI56E FLN MVI56E FLN Profile Data...

Page 132: ...4 8 1 A State Definitions 1 Initialization monitoring state Waits for an initialization request from the upper layer and judges if the network link is established 2 Network initialization state Link e...

Page 133: ...N ControlLogix Platform Reference FA Control Network Ethernet Communication Module User Manual ProSoft Technology Inc Page 133 of 155 5 Token holding state State where a token is held in the link join...

Page 134: ...Reference MVI56E FLN ControlLogix Platform User Manual FA Control Network Ethernet Communication Module Page 134 of 155 ProSoft Technology Inc 4 8 2 B Initialization Monitoring...

Page 135: ...the network are set by the upper layer Waiting for joining token detection timeout Time for judging the current network status The time starts after an initialization request from the upper layer is...

Page 136: ...Reference MVI56E FLN ControlLogix Platform User Manual FA Control Network Ethernet Communication Module Page 136 of 155 ProSoft Technology Inc 4 8 3 C Network Initialization...

Page 137: ...MVI56E FLN ControlLogix Platform Reference FA Control Network Ethernet Communication Module User Manual ProSoft Technology Inc Page 137 of 155 4 8 4 D Halfway Joining Initialization...

Page 138: ...Reference MVI56E FLN ControlLogix Platform User Manual FA Control Network Ethernet Communication Module Page 138 of 155 ProSoft Technology Inc 4 8 5 E Waiting for Token...

Page 139: ...MVI56E FLN ControlLogix Platform Reference FA Control Network Ethernet Communication Module User Manual ProSoft Technology Inc Page 139 of 155 4 8 6 F Token Holding...

Page 140: ...Reference MVI56E FLN ControlLogix Platform User Manual FA Control Network Ethernet Communication Module Page 140 of 155 ProSoft Technology Inc 4 8 7 G Message Transmission State Transition...

Page 141: ...MVI56E FLN ControlLogix Platform Reference FA Control Network Ethernet Communication Module User Manual ProSoft Technology Inc Page 141 of 155 4 8 8 H Message Reception State Transition...

Page 142: ...static fixed IP address that is not shared with any other device on the Ethernet network Obtain a list of suitable IP addresses from your network administrator BEFORE configuring the Ethernet port on...

Page 143: ...Soft Technology Inc Page 143 of 155 Ethernet Cable Configuration Note The standard connector view shown is color coded for a straight through cable Crossover cable Straight through cable RJ 45 PIN RJ...

Page 144: ...Reference MVI56E FLN ControlLogix Platform User Manual FA Control Network Ethernet Communication Module Page 144 of 155 ProSoft Technology Inc...

Page 145: ...uct Version Number 2 System architecture 3 Network details If the issue is hardware related we will also need information regarding 1 Module configuration and associated ladder files if any 2 Module o...

Page 146: ...888 neasia prosoft technology com Languages spoken English Chinese Japanese Korea Phone 60 3 7941 2888 korea prosoft technology com Languages spoken English Korean Regional Office Phone 33 0 5 34 36 8...

Page 147: ...rosoft technology com Mexico Phone 52 222 264 1814 mexico prosoft technology com Languages spoken Spanish English REGIONAL TECH SUPPORT support la prosoft technology com Andean Countries Central Ameri...

Page 148: ...MVI56E FLN ControlLogix Platform User Manual FA Control Network Ethernet Communication Module Page 148 of 155 ProSoft Technology Inc...

Page 149: ...value of frame interval that allows a node to receive a frame Allowable refresh cycle time This time is used for a node to judge whether message transmission should be performed or not B Bit area Thi...

Page 150: ...occurs between nodes N Network management table This table manages the common parameters on the network P Participating node management table This table manages the status of each node participating i...

Page 151: ...ernet Communication Module User Manual ProSoft Technology Inc Page 151 of 155 V Version number This number is used for message transmission The version number is initialized by random number when a no...

Page 152: ...Glossary of Terms MVI56E FLN ControlLogix Platform User Manual FA Control Network Ethernet Communication Module Page 152 of 155 ProSoft Technology Inc...

Page 153: ...ET T V2 50 Connecting to the Module s Web Page 22 Connecting Your PC to the ControlLogix Processor 31 Connecting Your PC to the Module 16 Contacting Technical Support 145 Creating Optional Comment Ent...

Page 154: ...ation 2 R Read Block 101 Reading Status Data from the Module 75 Reference 87 Renaming an Object 34 Resend function 150 S Scrolling LED Status Indicators 81 Selecting the Slot Number for the Module 25...

Page 155: ...ion Module User Manual ProSoft Technology Inc Page 155 of 155 V Verifying Communication 51 Version number 151 Viewing Backplane Status 80 Viewing Configuration Information 79 Viewing Version Informati...

Reviews: