![ProSoft MVI56E-FLN User Manual Download Page 38](http://html1.mh-extra.com/html/prosoft/mvi56e-fln/mvi56e-fln_user-manual_1618868038.webp)
Configuring the MVI56E-FLN Module
MVI56E-FLN ♦ ControlLogix Platform
User Manual
FA Control Network Ethernet Communication Module
Page 38 of 155
ProSoft Technology, Inc.
Use the following settings to configure the data to transfer from the module to the
remote node. This data is transferred from the ControlLogix processor to the
MVI56E-FLN module through the
FLNETDATA.Output.Area1
and
FLNETDATA.Output.Area2
controller tag arrays.
Area 1 Top : 0
Area 1 Size : 50
Area 2 Top : 0
Area 2 Size : 100
Use the following settings to configure the data to transfer from the Common
Memory to the processor. This data is transferred from the MVI56E-FLN module
to the ControlLogix processor through the
FLNETDATA.Input.Area1
and
FLNETDATA.Input.Area2
controller tag arrays.
BP Area 1 Top : 50
BP Area 1 Size : 50
BP Area 2 Top : 100
BP Area 2 Size : 100
The next illustration shows how the data is transferred through the module
between Common Memory and the ControlLogix processor controller tags
arrays: