MVI56E-AFC / MVI69E-AFC ♦ Enhanced Liquid and Gas Flow Computer
Configuring Meter Factors
ControlLogix® and CompactLogix™
Setup and Configuration Guide
ProSoft Technology, Inc.
Page 99 of 151
In order for the AFC module to accept the values you entered, the following conditions
are required:
All values are non-negative.
At least one meter factor is non-zero.
If a meter factor is zero, the corresponding flow rate is also zero.
The flow rates corresponding to non-zero meter factors are all different.
You do not need to enter factor/flowrate pairs in any particular order, or even enter them
all as a contiguous group. You may enter each factor-flowrate pair into any of the five
table entries and the AFC module will sort it.
If you do not want to enter meter factor linearization data, then populate only one entry
leaving the other four empty (all zero). In this case, the flow rate value does not matter
and the single meter factor applies to all flow rates. The EAFC Manager
’s initial default
table is populated in this way with a meter factor of 1.