MVI56E-AFC / MVI69E-AFC ♦ Enhanced Liquid and Gas Flow Computer
Configuring Meter Groups
ControlLogix® and CompactLogix™
Setup and Configuration Guide
ProSoft Technology, Inc.
Page 54 of 151
In this example the hexadecimal value of the register is 8413, which is 1000 0100 0001
0011 in binary. The
Meter-group relationship
data point (position 15) has a value of 1,
indicating that the meter has a relationship to a meter group. The
Group-parent meter
channel
data point (positions 10
– 14) has a value of 1, indicating that Meter 2 is a
member of the group having Meter 1 as its parent.
5.2
Configuring the Meter-Group Parent
This selection configures the meter channel as a group-parent. There is no physical
metering device directly associated with the channel. Instead, the function of the channel
is to summarize the results of other group-member channels that do have associated
physical metering devices and perform the actual measurement.
Note: The meter-group parent must be configured prior to the members of the group.
Note: If downloading multiple meter configurations to a module at once in the meter-group relationship, the
meter index of the meter-group parent must be less than the meter index of all the meter-group members of
the meter-group parent.
To configure the meter-group parent:
1
From the
Project
menu, select
Meter Configuration
.