MVI56E-AFC / MVI69E-AFC ♦ Enhanced Liquid and Gas Flow Computer
Configuring Site Parameters
ControlLogix® and CompactLogix™
Setup and Configuration Guide
ProSoft Technology, Inc.
Page 23 of 151
Parameter
Description
Important: The end-of-period (End-of-day hour and End-of-hour minute) settings are global
settings, unless these settings are set by meter on the Meter Configuration page. If these
parameters are set per meter, and enabled under control options, the options specified per
meter take precedence over the same settings on the Site Configuration page. For more
information see section 4.3,
“Setting End-of-Period Parameters,”
Barometric pressure
This parameter sets the barometric pressure used on the module
calculations. The module expects each meter's pressure input to be in gauge
units. Because the AGA8, AGA3, and some API2540 calculations require the
pressure of the fluid to be in absolute units, the module adds barometric
pressure to the gauge pressure in order to obtain the absolute pressure.
The calculation assumes that all meters measured by a single AFC are
located at the same site and have the same barometric pressure.
Site Options
See
on page 24 for details.
Pass-Thru Options
See
“Configuring Pass-Thru Options”
on page 24 for details..
Site configuration status
This series of indicators in the upper-right corner of the dialog show the
status of various site parameters. See
“Viewing Site Configuration Status”
page 25 for details.
UDT tag prefix
This field shows the prefix used for generated UDT names. See
on page 26 for details.
Network
Click thiis button to configure Modbus TCP/IP. See
on page 26 for details.
Serial 1 and Serial 2
Click these buttons to configure the two serial port connections. See
“Configuring Serial 1 and Serial 2”
on page 35 for details.
Remapping
Click this button to configure the data remapping between two slaves using
the
Indirect Address Remapping
dialog. For more information see the
AFC
Reference Guide
.
Poll
Click this button to update the site-status indicators. For more information see
on page 38.
Read
Click this button to read the current site configuration from the module to the
local PC. See
on page 39 for more information.
Write
Click this button to transfer the site configuration from the local PC to the
module. See
on page 40 for more information.
Special wnd
Click this button to open the
Special Windows Configuration
dialog to set
tmeout values for various processes. See
on page 41
for details.
Meters
Click this button to open the
Meter Configuration
dialog. For more information
see chapter 4,
“Configuring Meter Parameters,”
on page 42
Prover
Click this button to open the
Prover Configuration
dialog. For more
information, see the
AFC Reference Guide
.
Done
Click this button to store your settings temporarily and close the
Site
Configuration
dialog. Note that you must also save your project before closing
EAFC Manager; otherwise your configuration will be discarded.