MVI56E-AFC / MVI69E-AFC ♦ Enhanced Liquid and Gas Flow Computer
Configuring Meter Parameters
ControlLogix® and CompactLogix™
Setup and Configuration Guide
ProSoft Technology, Inc.
Page 45 of 151
4.3.1 End-of-day hour
This parameter sets the minute of the day when the daily archives are created. The
default value of 0 (zero) creates the daily archive at midnight. The entry format is hh :
mm, where hh represents hour and mm represents minute of the hour. Valid values for
hour are between 0 and 23. Valid values for minute of the hour are between 0 and 59.
The entered hour and minute of the hour values are converted to end-of-day minute
values in a range from 0 to 1439 before being written to the module. This moment is
relative to the module’s wallclock, which is expected to be UTC time.
4.3.2 End-of-hour minute
This parameter sets the minute of the hour when the hourly archives are created. The
default value of 0 (zero) creates hourly archives at the top of each hour. Valid values are
between 0 and 59.
4.3.3 Setting Precedence
Global settings for
End-of-day hour
and
End-of-hour minute
are located in the
Site
Configuration
dialog box. By default, these take precedence over the
End-of-day hour
and
End-of-hour minute
parameters in the
Meter Configuration
dialog box. However, you
can give the meter setting precedence using the
Meter Control Options
dialog.
1
From the
Meter Configuration
dialog, click on the
C
ONTROL
O
PTS
button.
2
Select the
Enable per-meter end-of-day
and
Enable per-meter end-of-hour
check
boxes.
3
Click
D
ONE
.