Module Configuration
MVI56-BDW
♦
ControlLogix Platform
BARDAC Drive Web Interface
ProSoft Technology, Inc.
Page 23 of 82
September 4, 2008
Select the 1756- Module (Generic 1756 Module) from the list and click the OK
button. The following dialog box appears:
Fill in the dialog boxes as shown adjusting the Name, Description and Slot
options for your application. You must select the
Comm Format
as
Data - INT
in
the dialog box. Failure to set the
Assembly Instance
and
Size
values correctly
will result in a module that will not communicate over the backplane of the
ControlLogix rack. Click Next to display the next dialog box.
Select the Request Packet Interval value for scanning the I/O on the module.
This value represents the minimum frequency the module will handle scheduled
events. This value should not be set to less than 1 millisecond. Values between 1
and 10 milliseconds should work with most applications.